ICT Electrical System Diagram 01

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

LOGIC CONTROL IN ATP­A/B

PANNEL
STATUS ATP­A ATP­B
CB
STATUS
TR. A ON
Q1=ON Q1=ON
STATUS 1 TR. B ON
Q2=OFF Q2=OFF
NORMAL D.G­A OFF
Q3=OFF Q3=OFF
D.G­B OFF

TR. A OFF
Q1=OFF Q1=ON
TR. B ON
STATUS 2 D.G­A OFF
Q2=OFF Q2=OFF
Q3=ON Q3=ON
D.G­B OFF 15/0.4KV 33/0.4KV
1600KVA 1600KVA
TR. A ON
Q1=ON Q1=OFF
TR. B OFF
STATUS 3 D.G­A OFF
Q2=OFF Q2=OFF
Q3=ON Q3=ON
D.G­B OFF

ACB

ACB
3200A/3P

3200A/3P
TR. A OFF
Q1=OFF Q1=OFF
TR. B OFF
STATUS 4 D.G­A ON
Q2=ON Q2=OFF
Q3=ON Q3=ON
D.G­B OFF

TR. A OFF
Q1=OFF Q1=OFF AVR AVR
TR. B OFF
STATUS 5 D.G­A OFF
Q2=OFF Q2=ON
Q3=ON Q3=ON
D.G­B ON

ACB

ACB

ACB

ACB
3200A/3P

3200A/3P

3200A/3P

3200A/3P
D.G. A D.G. B
DG 400V
1500KW(DCC)
400V
1500KW(DCC)
DG

ATP‐A ATP‐B

ACB

ACB
3200A/4P

3200A/4P
ACB

ACB
3200A/4P

3200A/4P
Spare

Spare
ACB

ACB
3200A/4P

3200A/4P
ACB

ACB
3200A/4P

3200A/4P
Q4

Q4
Q1

Q2

Q3

Q3

Q2

Q1
ACB
3200A/4P

ACB
3200A/4P
Q5

Q5
LV‐1‐A LV‐1‐B
4*(8*240+1*240)mm²

4*(8*240+1*240)mm²
4*(8*240+1*240)mm²

1FU1~3 1HY 1HG 1HR 1HR 1HG 1HY 1FU1~3


1L11~1L31,1N 1L11~1L31,1N

Electrical
3200A/4P ACB

3200A/4P ACB
interlocking
1QF

1QF
3200A/4P ACB

3200A/4P ACB
1L13,1N 1L13,1N
2QF

2QF
1FU7 1FU7

Power Power
Voltage 1FU4~6 1L12~1L32,1N 1L12~1L32,1N
1FU4~6 Voltage
Power Meter Power Meter

Current Current
3200/5A,0.5 3200/5A,0.5
250A/3P MCCB

250A/3P MCCB

250A/3P MCCB

160A/3P MCCB

160A/3P MCCB

160A/3P MCCB

160A/3P MCCB

250A/3P MCCB

250A/3P MCCB

250A/3P MCCB
1000A/3P ACB

1000A/3P ACB

1000A/3P ACB

1600A/4P ACB

1600A/4P ACB

1000A/3P ACB

1000A/3P ACB

1000A/3P ACB
800A/4P ACB

800A/4P ACB
QF10

QF10
QF1

QF2

QF3

QF4

QF5

QF6

QF7

QF8

QF9

QF9

QF8

QF7

QF6

QF5

QF4

QF3

QF2

QF1

You might also like