Professional Documents
Culture Documents
NG Ubm 30 Netd 044007 - 01 - Ifa - 20230407
NG Ubm 30 Netd 044007 - 01 - Ifa - 20230407
This document has been generated by an Electronic Document Management System. When printed it is considered as "For information
only”. The control copy is the screen version and it is the holder's responsibility that he/she holds the latest valid version
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
TABLE OF CONTENTS
1 GENERAL ........................................................................................................................................5
1.1 Purpose.................................................................................................................................5
1.2 Scope ....................................................................................................................................5
2 REFERENCE DOCUMENTS ...........................................................................................................5
2.1 Project Documents ..............................................................................................................5
2.2 Company Documents..........................................................................................................5
2.3 Company General Specifications ......................................................................................6
2.4 Codes and Standard............................................................................................................6
3 LIST OF HOLDS ..............................................................................................................................7
4 DEFINITIONS AND ABBREVIATIONS...........................................................................................7
4.1 Definitions ............................................................................................................................7
4.2 Abbreviations .......................................................................................................................7
5 GENERAL ........................................................................................................................................8
5.1 Environmental Conditions..................................................................................................8
5.2 Location ................................................................................................................................8
5.3 VENDOR Responsibilities...................................................................................................8
5.4 Omissions.............................................................................................................................9
5.5 Conflicts................................................................................................................................9
5.6 Exceptions and Deviations.................................................................................................9
5.7 Sub Orders ...........................................................................................................................9
5.8 Review of Documents .........................................................................................................9
6 PFP DESIGN BASIS......................................................................................................................10
6.1 Type of PFP ........................................................................................................................10
6.2 Performance Criteria .........................................................................................................10
6.2.1 Maximum Allowable Surface Temperature........................................................................... 10
6.2.2 Fire Rating.......................................................................................................................... 11
6.2.3 Explosion Resistance ........................................................................................................... 11
7 TYPES OF PFP PRODUCTS ........................................................................................................11
7.1 Pre-Fabricated Panels/Boxes ...........................................................................................11
7.2 Fire Blankets ......................................................................................................................12
7.3 Spray-Applied Epoxy Intumescent ..................................................................................12
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
1 GENERAL
1.1 Purpose
This specification outlines the requirements for the selection, design, procurement, manufacture,
inspection, testing and shipment of the Passive Fire Protection (PFP) for the new facilities at Obite TC
as part of the UBETA Main Development Project.
1.2 Scope
This specification focusses on the passive fire protection to be supplied for the new facilities added at
Obite TC as part of the UBETA Main Development Project.
2 REFERENCE DOCUMENTS
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
3 LIST OF HOLDS
Hold number Description of Hold Section
[HOLD 1] The type of PFP to be selected for the ESDV is to be defined 6.1
at next Project Detailed Engineering Phase.
[HOLD 2] Closed
[HOLD 3] The design overpressure of the PFP shall be defined later in 6.2.3, 9.2
the course of the Project.
4.1 Definitions
COMPANY (CPY) Means TotalEnergies EP Nigeria.
ENGINEER (ENG) Means DORIS Engineering and NETCO
PROJECT Ubeta Main Development Project
4.2 Abbreviations
ALARP As Low As Reasonably Practicable
EER Escape, Evacuation and Rescue
ESDV Emergency Shut Down Valve
GRP Glass-Fiber Reinforced Plastic
HF Hydrocarbon Fire
JF Jet Fire
PFP Passive Fire Protection
TC Treatment Center
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
5 GENERAL
5.1 Environmental Conditions
The passive fire protection shall be permanently available for intermittent exposure to fire whilst located
in the prevailing environmental conditions described in ‘’Ubeta Main - Equipment Design Conditions
Specification’’, Ref.[8].
5.2 Location
Passive fire protection will be installed in outdoor location at the arrival facilities of Obite Treatment
Center onshore Nigeria.
The following items are excluded from the VENDOR’s scope of supply :
• Identification of items requiring PFP,
• Responsibility for identifying PFP rating and insulating period,
• Responsibility for identifying details of location.
In order to meet the stringent safety requirements of the Project, passive fire protection must offer a
high degree of reliability under all weather conditions and shall require the minimum of maintenance in
order to maintain this level of availability. Ease of repair of the passive fire protection is of paramount
importance.
As per ''Ubeta Main - Equipment Design Conditions Specification'', Ref.[8], the design life of the Project
is 20 year life in continuous service with at least 3 years of uninterrupted service. PFP design shall
withstand the Project design life.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
The CONTRACTOR shall be solely responsible for providing complete, new, unused, and operable
passive fire protection materials in full compliance with all referenced Codes and Standards,
COMPANY Standards and documents listed section 2 of this specification.
5.4 Omissions
Any omission in the requirements detailed herein shall not relieve VENDOR of his responsibility to
provide a system that delivers the specified performance.
5.5 Conflicts
Any conflicts between the referenced documents shall be identified to CONTRACTOR in writing for
resolution before proceeding with the design. Verbal communications shall not be considered official.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
In terms of fire rating, structures, partition, and equipment, PFP systems shall satisfy three main criteria
throughout a prescribed time of exposure to heat:
1. Stability: the structure shall fulfil its load-bearing capacity throughout the fire exposure period,
2. Integrity: the partitions shall prevent spread of flames and hot fumes throughout the fire
exposure period,
3. Insulation: the unexposed side of the partitions shall not reach surface temperatures in excess
of a certain level throughout the fire exposure period.
Fireproofing shall be easily installed and repaired and shall not interfere with the maintenance of (or
access to) the surrounding equipment. Areas such as critical welds, inspection parts which need to be
inspected shall be protected by means of removable PFP systems. In addition, PFP of supporting
features shall have the same fire rating as the main equipment protected with PFP.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
The fire rating shall be written as T/XF/t, with: T max. surface temperature (as defined under section
6.2.1), XF: type X of fire (as defined in section 6.1), and t: specified period of time.
Considering the requirements of GS EP SAF 337, Ref.[38], the existing design philosophy at Obite TC
‘’Passive Fire Protection Philosophy & Schedule’’, Ref.[23], and the conclusions of the Detailed Risk
Assessment, Ref.[9], the PFP shall comply with the following fire ratings :
• ESDV : 200/JF/t with t equal to 60 minutes minimum,
• Upstream pipe : 350/JF/t with t equal to 60 minutes minimum.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
It is noted that penetrations through a fire rated partition for the passage of cables, pipes, ducting or
structural members shall be via certified penetrations that maintain the fire rating integrity of the
division.
With regard to the duration and type of fire, VENDOR shall provide evidence acceptable to COMPANY
that the proposed PFP product has been tested and shown to provide adequate protection. VENDOR
shall provide fire performance test details and explosion resistance in accordance with section 6.2.2 of
this specification.
In addition, the following general considerations shall be taken into account in the selection and
proposal of a suitable PFP product for use on the PROJECT:
8.2 Density
The weight limitations imposed by the strength of the structural steel to be fireproofed shall be assessed
and consideration shall be given to minimizing the applied weight of fireproofing when selecting the
appropriate system.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
The different fireproofing materials should be compared on a weight per square meter basis taking into
account the required Dry Film Thickness (DFT) and the specific gravity.
VENDOR shall provide specific gravity test results conducted by an independent test house in
accordance with the method A of ISO 1183-1, Ref.[19], and the test results given in g/cm 3.
VENDOR shall have tested the adhesion of the fireproofing to steel and provide evidence that the
adhesion value is not less than 5 MPa measured with hydraulic Pull-off Adhesion Tester (PAT)
instrument in accordance with standard ISO 4624, Ref.[17].
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
To ensure sufficient resistance to mechanical damage the fireproofing VENDOR shall provide evidence
that the mechanical properties meet the following minimum criteria:
VENDOR shall provide evidence that the fireproofing has sufficient flexibility to withstand strains to
failure of 1.6%. This value should accommodate designs where there has been allowance for plastic
deformation.
The fireproofing VENDOR shall provide independent test evidence of hose stream testing in
accordance with NFPA 290, Ref.[20].The test provides a minimum thickness which should be applied
to meet the requirement of the test.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
In general the PFP system shall be suitable for direct application to surfaces operating between -30ºC
and 80ºC.
For substrate temperatures above 80ºC up to 120ºC and below -30ºC to -45ºC VENDOR may provide
a sprayable epoxy syntactic insulation system fire-tested in conjunction with the fireproofing. The
appropriate thickness of insulation shall be specified by VENDOR as necessary to restrict the
fireproofing to the appropriate temperature.
For substrate temperatures above 120ºC and below -45ºC VENDOR shall specify a suitable insulation
system tested in conjunction with the fireproofing. The insulation system must be resistant to corrosion
under insulation and the fireproofing shall be epoxy intumescent due to the requirement for flexibility
and corrosion protection. The insulation system shall be applied at a thickness provided by the
insulation supplier and shall be applied in accordance with the fireproofing VENDOR application
guidelines.
Standard industry practice for coatback is 450mm unless evidence is provided to demonstrate the
validity of a shorter distance.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
PFP VENDOR shall state the maximum acceptable deflection value (straining) of structural members
that would not de-rate the system's fire performance.
Where local heat transfer may occur due to secondary or tertiary steelwork connected to the protected
steel members, the steelwork shall be protected to the required distance to prevent local heat transfer
to the protected member (coat-back). The passive fire protection VENDOR shall advise the required
length of coat-back and shall provide all necessary test results and data to confirm the coat-back
requirements to the satisfaction of the CONTRACTOR and the Certifying Authority. A default value of
450-500 mm shall be used unless evidence is provided to demonstrate the validity of a shorter distance,
in accordance with section 4.4.8 of GS-EP-SAF-337, Ref.[11].
As fires may be preceded by explosion, evidence shall be provided that the PFP can resist without
damage the explosion overpressure and subsequent under pressure. Design values of overpressure
and under pressure shall be provided by CONTRACTOR, [HOLD 3].
Should any doubt exist regarding the suitability or compatibility of primed surfaces with the passive fire
protection, consultation with the PFP material VENDOR must be made. No further work on the area in
question shall proceed until the VENDOR’s representative has attended site, inspected the area in
question and given his recommendations in the presence of both the VENDOR and the
CONTRACTOR.
Any pins or attachments to be welded to the protected surface shall be welded prior to final surface
preparation and priming and located in accordance with the VENDOR’s recommendations.
Where the protected surface may operate at an elevated temperature, such as on vessels or piping,
the VENDOR shall provide and install an insulating layer in accordance with the requirements of the
PFP material VENDOR. The insulating layer must be compatible with both the surface primer and the
PFP product.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
9.3 Application
Prior to initiation of work the VENDOR shall meet with the CONTRACTOR, COMPANY, and
APPLICATOR to review the project drawings and specifications. The VENDOR shall survey the job
site and material storage facilities, examine the APPLICATOR equipment, review APPLICATOR’s safe
working practices, personnel protective equipment, material handling procedures, application methods
and quality control, and approve each to ensure compliance with PROJECT specifications.
VENDOR shall appraise the environmental conditions at the job site and considering the prevailing
conditions advise APPLICATOR of measures to be put in place to ensure that installation can be
accomplished without weather-related quality problems. The VENDOR shall advise COMPANY in
writing if conditions are such that installation should not take place. It is the responsibility of the
VENDOR to ensure that PFP application is in accordance with VENDOR's requirements.
Reinforcement of the PFP is to be of the type, material, and attachment method appropriate to the
surface protected and is to be in strict accordance with VENDOR’s specification and the Certifying
Authority requirements. All reinforcement shall be fully encapsulated by the PFP. Exposed areas of
reinforcement will not be tolerated and will be subject to re-work at the VENDOR’s expense.
Reference shall be made at all times to VENDOR’s product data sheets and written procedures for
guidance on storage, handling, repair and if applicable mixing, thinning, application, and drying / curing
of the applicable PFP. Relevant guidance regarding matters of health safety and environment shall be
adhered to.
If the PFP system uses spray application all structures, components, and equipment not to be protected
but located in the vicinity of the spray operation shall be masked. Masking may be undertaken using
tarpaulins, polyethylene or equivalent (as instructed by the VENDOR). Release agents shall not be
used to prevent PFP material adhering to equipment, steelwork etc. that is not being protected. In
windy conditions additional precautions to control over-spray should be taken.
Spills, drips, or over-spray of spray applied PFP shall be removed promptly before the material has
cured.
Once spray applied PFP has gelled, masking materials shall be removed. Masking shall be removed
before PFP cures ensuring that the PFP is not disturbed.
The thickness of PFP shall be measured during application using a wet gauge.
9.4 Topcaot
Any protective topcoat applied to the intumescent coating shall be strictly in accordance with the
VENDOR’s recommendations.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
Appropriate Job Hazard Analysis and risks assessment shall be carried out prior to delivery of materials
to site, prior to all PFP preparation and prior to application work. Suitable control measures, including
low storage temperature, natural or forced ventilation requirements, respiratory protective equipment,
adequate clothing and eye protection, etc. shall be provided and their use enforced to reduce the risks
to personnel to an ALARP level.
10 QUALITY ASSURANCE
10.1 General Requirements
VENDOR shall assume unit responsibility and overall guarantee for the fireproofing. All Project QA/QC
documentation shall be submitted after completion of the PFP work in a dossier that shall include
release certificates and a photographic record of the work carried out.
In addition to quality assurance requirements within this specification, quality assurance requirements
as defined in the Main Contract will apply.
Refer to the section 9 of the GS-EP-COR-353, Ref.[12], for a full description of the requirements for
inspection and testing of the passive fire protection.
Any issues that are not covered within this specification or the application manual must be submitted
in writing in the form of a Technical Query Request (TQR) and the solution must be approved by the
supplier and client prior to work proceeding.
In addition, APPLICATOR shall have documented procedure covering all aspects of their operation in
line with ISO 9001 quality control systems.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
All QA/QC forms shall be completed within one week (maximum) of referenced PFP application and
shall be signed for acceptance of the work carried out by COMPANY or his authorised representative.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
The CONTRACTOR may, at any time, check the conditions under which the passive fire protection is
being stored to ensure they are in compliance with the VENDOR’s instructions.
The CONTRACTOR may, at any time, check the environmental conditions under which the passive
fire protection is being applied to ensure compliance with the VENDOR’s instructions.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
The CONTRACTOR reserves the right to carry out tests and inspections as appropriate to ensure that
the requirements of this specification have been met.
Inspection procedures and acceptance standards shall be agreed between CONTRACTOR and
VENDOR prior to commencement of work. Unacceptable work shall be replaced or repaired in an
approved manner at the VENDOR’s cost.
Inspection by the CONTRACTOR and/or the Certifying Authority shall not relieve the VENDOR of any
guarantees, responsibilities, or obligations with regard to supply and installation of materials to this
specification and the VENDOR’s specification.
Acceptance of the thickness of spray-applied PFP shall be based upon random measurements. In no
case shall the applied thickness be less than the specified minimum dry thickness.
12 DOCUMENTATION
VENDOR shall provide the documentation as listed in the VENDOR Documentation Requirement
Schedule included in the MATERIAL REQUISITION.
The documentation shall be in full compliance with the requirements from Management of
Documentation - Instructions to VENDORS, Ref.[4].
Refer to Packing, Marking and Shipping - Instructions to VENDORS, Ref.[5] for further details.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”
Document Identification Number
The storage of materials in spray machinery must be controlled so that the standing time does not
permit degradation of the materials or malfunction of the equipment. Any storage
instructions / requirements and details of any protective measures to be put in place shall be provided
by VENDOR.
VENDOR shall be responsible for the preservation and protection of all materials and equipment during
transit.
Refer to Preservation and Storage - Requirements and Instructions to VENDORS, Ref.[6], for further
details.
16 WARRANTIES
Specific guarantee given by CONTRACTOR shall complete guarantees and warranties defined in the
CONTRACT.
“This document is the property of TEPNG. It must not be reproduced or transmitted to others without written authorization from the
Company”