Professional Documents
Culture Documents
Comparison of Health Index and Degree of Polymerization Based On 2-Furfuraldehyde Compound For Transformer Condition Estimation
Comparison of Health Index and Degree of Polymerization Based On 2-Furfuraldehyde Compound For Transformer Condition Estimation
Comparison of Health Index and Degree of Polymerization Based On 2-Furfuraldehyde Compound For Transformer Condition Estimation
com
Abstract
This paper presents a study on the comparison of Health Index (HI) and the Degree of Polymerization (DP) models based on
2-furfuraldehyde (2-FAL) compound to determine the transformer condition. In total, 30 transformers ranging in age from 13 to 25 years
were analyzed. First, the Transformer Health Index (THI) was computed based on yearly individual oil condition monitoring data that
consisted of oil quality, dissolved gases, and furanic compounds. Next, the DP was computed based on 2-FAL using five different furfural
analysis methods for DP models that are tavailable in literature. Next, the DP of each transformer was plotted against its 2-FAL values. Then,
the percentage of DP named as Health Index DP (HIDP) for each transformer was established based on the maximum estimated DP of each
model. Finally, the comparison between THI and HIDP were performed. It was found that there is an identical trend between THI and HIDP.
However, the average error between THI and HIDP for each transformer is ranging from 8.28% to 37.18% and the total average error is 17.97%.
(Submitted on July 25, 2022; Revised on August 7, 2022; Accepted on August 23, 2022)
1. Introduction
A transformer is a one of the most expensive components installed in an electrical substation. The transformer life defined by
manufacturers is between 20 to 40 years [1,2]. However, some transformers reached 50 years old of operation. Transformer
insulation consists of solid and liquid insulations. Cellulose based paper is widely used as solid insulation for transformers.
The degradation of cellulose paper is related to the transformer life. It happens when the cellulose paper loses mechanical
strength. The loss of mechanical strength begins with breaking in molecular chains of cellulose. It can be measured by the DP
value [3]. DP is computed by measuring the average number of glucose units chemically linked in a cellulose molecule [4].
The main chemical processes that are involved in the transformer aging are oxidation, hydrolysis, and pyrolysis [5,6]. Under
the thermal, mechanical, and electrical stresses, the degradation process of insulation paper could be accelerated. Three main
elements that cause solid insulation degradation are moisture, oxygen, and acidity [5-7]. The study on furanic compounds in
the insulating oil used in transformers had been presented since the mid-1980s [7]. The formation of furanic compounds in
transformers provides an indication for a transformer’s life. Almost 90% from 27 of the utilities, manufactures and researchers
around the world used furanic analysis as a diagnostic tool for their transformers study [7]. Many models had been introduced
by researchers to correlate the furanic compounds with DP such as Chen Dong [8], De Pablo [9], Burton [10], Feng [11]. The
aim of this paper is to compare the DP computed based on 2-FAL compound and THI for transformer condition estimation.
The case study will be performed based on the condition monitoring data of 30 in-service distribution transformers. The HIDP
computed from 2-FAL using five models are compared with the THI model adopted by utility.
Furanic compounds are generated during the thermal degradation of the insulation paper which are used extensively in
transformer. Typically, insulation papers are made by wood pulp through the kraft process. The main material of this type of
* Corresponding author.
E-mail address: sharil@utem.edu.my
Comparison of Health Index and Degree of Polymerization based on 2-Furfuraldehyde Compound for Transformer Condition Estimation 655
paper is cellulose, which is a natural polymer of glucose and consists of a bundle of molecules in different forms [3,4,6]. It has
been suggested that furanic compounds may primarily initiate from the degradation of hemicellulose compared to cellulose
[7]. Furanic compounds are produced due to the series of re-arrangement of molecules bonding via the thermal degradation
process like hydrolysis and pyrolysis [5]. There are five main furanic compounds produced through the accelerated aging in
the transformer which are 2-furfural (2-FAL), 2-acetylfuran (2-ACF), 5-methyl-2-furfural (5-MEF), 2-furfurylalcohol
(2-FOL), and 5-hydroxymethyl-2-furfural (5-HMF) [7,12]. Between five main furanic compounds, 2-FAL has the highest
generation rate and better stability in insulation oil [5,13]. Therefore, concentrations of 2-FAL are usually used as an aging
marker for furanic compound measurement in condition monitoring analysis. Furthermore, 2-FAL also provides information
on the condition of the insulation in a simple way without de-energizing the transformer. As furfural analysis is able to provide
a good indication to assess the condition of the transformer’s life, the correlation between the 2-FAL to the DP has been
modelled. The correlation between DP and 2-FAL is done based on the experimental and analytical process of paper from
aged insulation paper in laboratories and scrapped transformers units [10]. The researchers recommend that the DP for new
insulation paper is between 1200-800 [3,14-16]. Researchers also suggest that the insulation paper will be lost through
mechanical strength at a DP around 150-250.
2-FAL compound is a by-product of the aging process in a transformer. It can be detected in transformer insulation oil. The
2-FAL in the oil can be used as a bulk measurement of the DP of the solid insulation paper and gives a good marker for a
transformer’s life. There are several models that have been introduced by researchers to estimate the value of DP of insulation
paper from the 2-FAL. The models described the relationship between the increase of 2-FAL to the reduction of DP. Shroff
and Stannett had introduced the logarithmic relation between furanic compounds with the DP in mid 1880s [15]. Further
investigation based on data collected from free breathing transformers that used kraft paper has been performed by Chendong.
The correlation between DP and 2-FAL can be seen in Equation 1 [7,8,10,12].
log(2𝐹𝐴𝐿)−1.51
𝐷𝑃 = (1)
−0.0035
Based on research conducted by CIGRE WG 15.01, De Pablo introduced the linear model of DP and 2-FA. The
correlation was derived based on the cellulose chain scission theory and considered that the paper rarely decomposes
uniformly. This can be seen in Equation 2.
7100
𝐷𝑃 = 8.8+2𝐹𝐴𝐿 (2)
The model then improved by De Pablo by considering that paper aging condition is not even, assuming 20% of the inner
layers in the winding degrade twice faster than the rest of the insulation paper [7,8,10]. The updated correlation is shown by
Equation 3.
800
𝐷𝑃 = [0.186∗2𝐹𝐴𝐿]+1 (3)
Another DP to 2-FAL model based on logarithm scale was also introduced by Equation 4 [8,10].
log 2𝐹𝐴𝐿−2.5
𝐷𝑃 = −0.005
(4)
Recently, Feng explored and fine-tuned the DP to 2-FAL relationship. The model is fitting with the measured 2-FAL
from scrapped National Grid transformers [10,17] and can be seen in Equation 5.
1674
𝐷𝑃 = (5)
𝐹𝑢𝑟𝑎𝑛+2.09
656 M. S. Yahaya, N. Azisb, H. Zainuddinc, M. F. Basara, and M. H. Harun
There are differences between the models discussed above. It is due to the different methodology, data, and samples used
in correlating both parameters.
4. Case Study
In this study, the condition monitoring data from 30 distribution transformers with voltage and power rating 33/11 kV and 30
MVA were tested. The transformers’ age ranged from 13 to 43 years. The 2-FAL value for each transformer with its age is
shown in Figure 1. The 2-FAL measured from oil condition monitoring of in-service transformer were used to estimate the DP
of solid insulation.
16
14
12
2-FAL (ppm)
10
0
13 13 16 27 32 32 32 32 32 32 32 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 43
Age of Transformer (year)
Next, the THI computed based on individual oil condition monitoring data that consisted of oil quality, dissolved gases,
and furanic compounds can be seen in Figure 2.
100
90
80
70
60
% HI
50
40
30
20
10
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
No. of Transformer
The case study data show that there is no clear correlation between THI, 2-FAL, and transformer age. However, the plot
in Figure 3 between THI and 2-FAL shows that THI is inversely proportional with the value of 2-FAL.
Comparison of Health Index and Degree of Polymerization based on 2-Furfuraldehyde Compound for Transformer Condition Estimation 657
18
16
14
12
2-FAL (ppm)
10
8
6
4
2
0
0 20 40 60 80 100
THI (%)
Next, the DP was computed based on 2-FAL using five different models described in the section 3. The DP value then
was converted to percentage of DP named as Health Index DP (HI DP). The conversion was made based on the maximum DP
value estimated by each model and by assumption that the end of life of DP for all models is 200. The calculated data for THI
and DP based on 2-FAL for all models are tabulated in Table 1. Then, the comparison between THI and HIDP for five different
models can be seen in Figure 4.
100
THI
90 Chendong
80 Pablo 1
Pablo 2
HI and HIDP (%)
70
Feng
60
Burton
50
40
30
20
10
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Transformer No.
Overall, the comparison between THI and HIDP indicates that the average absolute error for five models is between
10.35%-25.19%. Feng’s model shows the smallest average absolute error with 10.35% followed by Burton’s model (13.95%),
Pablo’s 2 model (18.89%) and Chengdong’s model (19.67%). The highest average of absolute error is Pablo’s 1 model with
25.19%. The study shows HIDP provides a comparable result with THI since the 2-FAL is part of the component in THI
computation. However, for individual comparison as shown in Figure 5, only 18 from 30 transformers have absolute error less
than 10.00% while 12 from 30 transformers have absolute error between 10.40% to 40.10%. However, the approach can be
further validated in future studies if the THI from utilities and bigger transformer population can be obtained.
100
90
80
Absolute error (%)
70
60
50
40
30
20
10
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
Transformer No.
5. Conclusion
The approach of HIDP to estimate the transformers condition based on 2-FAL was carried out in this study. It was found that
HIDP can be used to estimate the condition of transformers based on 2-FAL. The DP obtained by 2-FAL compound show that
the estimated HIDP is acceptable for several transformers. Comparison with THI revealed the smallest average absolute error
by DP- 2-FAL Feng’s model was 10.35%. The individual comparison between THI and HI DP show that the absolute error for
18 to 30 transformers is less than 10.00%. Since several transformers have higher absolute error, this study can be further
validated in the future if more 2-FAL data from utilities can be obtained.
Acknowledgements
The authors would like to express their sincere gratitude to UTeM and MOHE Malaysia for the technical and financial support
of this research.
Comparison of Health Index and Degree of Polymerization based on 2-Furfuraldehyde Compound for Transformer Condition Estimation 659
References
1. Group, W. Life management techniques for power transformer. Cigre Brochure 227, June 2003.
2. Wilson, A. and Lapworth, J. A. Defining the life of major assets, in International Conference on, Condition Monitoring and
Diagnosis, pp. 609-613, 2008.
3. Emsley, A. M. and Stevens, G. C. Kinetics and mechanisms of the low-temperature degradation of cellulose. Cellulose, vol. 1, no.
1, pp. 26-56, 1994.
4. Martin, D. Cui, Y. and Saha, T. Life estimation techniques for transformer insulation. in ustralasian Universities Power
Engineering Conference, AUPEC 2013, Hobart, TAS, Australia, pp. 1-6, 2013.
5. Emsley, A. M. and Stevens, G. C. Review of chemical indicators of degradation of cellulosic electrical paper insulation in
oil-filled transformers. IEE Proceedings-Science, Measurement and Technology, vol. 141, no. 5, pp. 324-334, 1994.
6. Lundgaard, L. E. Hansen, W. Linhjell, D. and Painter, T. J. Aging of Oil-Impregnated Paper in Power Transformers. IEEE
Transactions on power delivery, vol. 19, no. 1, pp. 230–239, Jan. 2004.
7. Group, W. Furanic Compounds for Diagnosis, vol. 01, Cigre Brochure 494. April 2012.
8. Cheim, L. Platts, D. Prevost, T. and Xu, S. Furan analysis for liquid power transformers, IEEE Electrical Insulation Magazine, vol.
28, no. 2, pp. 8-21, 2012.
9. Mtetwa, N. S. Accuracy of furan analysis in estimating the degree of polymerization in power transformer. Master Thesis,
University of the Witwatersrand, Johanesburg, South Africa, 2011.
10. Feng, D. Life expectancy investigation of transmission power transformers. PhD Thesis, The University of Manchester, 2013.
11. Stebbins, D. Myers, D. S. and Shkolnik, A. B. Furanic compounds in dielectric liquid samples: review and update of diagnostic
interpretation and estimation of hulation Ageing. in lntemational Conference on Properties and Applications of Dielectric
Material. pp. 921-926, June 2003.
12. Cui, Y. Martin, D. Saha, T. Ma, H. and Lelekakis, N. Multi-variable approach for evaluating transformer paper insulation. in 11th
International Conference on the Properties and Applications of Dielectric Materials (ICPADM), pp. 320-323. 2015
13. Leibfried, T. Jaya, M. Majer, N. Schafer, M. Stach, M. and Voss, S. Postmortem investigation of power transformers - Profile of
degree of polymerization and correlation with furan concentration in the oil. IEEE Transactions on power delivery. vol. 28, no. 2,
pp. 886-893, 2013.
14. Urquiza, D. Statistical study on the reference in power transformers. vol. 31, no. 4, pp. 15-23, 2015.
15. Lelekakis, N. Guo, W. Martin, D. Wijaya, J. and Susa, D. A field study of aging in paper-oil insulation systems. I EEE Electrical
Insulation Magazine. vol. 28, no. 1, pp. 12-19, 2012.
16. Lundgaard, L. E. Hansen, W. Ingebrigtsen, S. Linhjell, D. and Dahlund, M. Aging of kraft paper by acid catalyzed hydrolysis. i
n IEEE International Conference on Dielectric Liquids, 2005. ICDL 2005, pp. 381-384, 2005.
17. Jones, D. and Wang, Z. Strategy for assessment of distribution transformer lifetime. in 23rd International Conference on
Electricity Distribution, pp. 15-18, June 2015.
M. S. Yahaya is a Senior Lecturer at Faculty of Electrical and Electronic Engineering Technology, Universiti Teknikal
Malaysia Melaka (UTeM), Malaysia. He received his Ph.D. in Electrical Power Engineering from Universiti Putra Malaysia
(UPM), Malaysia. He also received his Master of Science in Power Distribution Engineering in 2009 from Newcastle
University, UK and bachelor’s degree in electrical engineering in 2001 from Universiti Teknologi Malaysia (UTM), Malaysia.
He had 5 years industrial working experience as Application Engineer and Technical Service Engineer. His research interests
are predictive modeling, condition monitoring, condition assessment and asset management.
N. Azis received B. Eng degree in Electrical and Electronic Engineering (2007) from Universiti Putra Malaysia and Ph.D.
degree in Electrical Power Engineering (2012) from The University of Manchester in UK. Currently he is Associate Professor
at the Department of Electrical and Electronic Engineering, Universiti Putra Malaysia, Malaysia. His research interests are
in-service ageing of transformer insulation, condition monitoring, asset management and alternative insulation materials for
transformers.
H. Zainuddin received the B. Eng degree in Electrical Engineering from Universiti Teknologi Malaysia in 2003 and Ph.D.
degree in High Voltage Engineering (2013) from University of Southampton in UK. Currently, he is a Associate Professor and
Dean in the Department Faculty of Engineering, University Teknikal Malaysia Melaka (UTeM). His research interests include
high voltage engineering, condition monitoring and finite element modeling.
M. F. Basar attained his Ph.D. in the field of Renewable Energy from Universiti Kebangsaan Malaysia (UKM), Bangi in
2017. A professional engineer registered with the Board of Engineers Malaysia (BEM) since 2013. His primary research
interests are in the fields of renewable energy and electrical engineering. Currently, he is the Deputy Dean of Research at the
Faculty of Electrical & Electronic Engineering Technology, UTeM.
M. H. Harun is received the MSc. degree in electrical engineering from Universiti Teknikal Malaysia Melaka (UTeM), Malaysia in 2013.
Currently he is pursuing his Ph.D. study at Universiti Teknologi Malaysia (UTM), Malaysia in electrical engineering.