Carrier is participating in
the Eurovent Certification
Programme. Products are
as listed in the Eurovent
Directory of Certified
Products.
09GF
Nominal cooling capacity 9.8 to 187 kW (water)
09GF dry coolers are designed as heat exchangers for commercial Pro-Dialog option is available for dry coolers matching
and industrial cooling and refrigeration and air conditioning. 30RW water cooled chillers
Due to its construction, the range is especially suitable for places Quick installation, fans are connected to the cooler end
where easy assembly as well as a light and robust structure are Product selection with the Polar Power selection program
required. The units are designed for outdoor use, but the structure
and low sound level make them suitable also for indoor use, Technical data
where the cooling capacity can be utilized for heating. The heat transfer section is made of copper tubes and alumi-
09LF condensers are presented in a separate brochure. nium fins. Fin spacing is 2.3 mm. The coil of a dry cooler is
equipped with draining and venting nipples but the standard
Features version cannot be totally drained. Please take this into
18 sizes with nominal capacities from 9.8 to 187 kW consideration when specifying the freezing point of the heat
(water, EN 1048) transfer liquid.
Performance data according to Eurovent Rating Standard
7/C/003 The fan chambers are separated crosswise. The units are
Three fan sizes and four fan speed alternatives equipped with lifting lugs. All standard units are suitable for
Two mounting positions: V = vertical air flow and both horizontal and vertical mounting. The mounting position
H = horizontal air flow has to be defined in the order. Electrical connection including
Complete fan control systems available, based on infinitely safety switch is located at the end of the dry cooler.
variable fan speed control (VC) or stepped fan starting cycle
(Step Control) A manual including installation and service instructions is
shipped with each unit.
Product designation 100% 0
Capacity
09GFE-10-1 06-4D-9-V-29DN65-VC
90%
Hä? -2
80% -4
6D = 15.0 r/s 6Y = 11.7 r/s 20% Power input of fan motor -16
10% -18
9 = power supply 10 11 12 13 14 15 16 17 18 19 20 21 22 23
6 = 440 V-3 ph-60 Hz
r/s
7 = 230 V-1 ph-50 Hz
8 = 230 V-3 ph-50 Hz Required heat transfer capacity can be achieved steadily with variable
9 = 400 V-3 ph-50 Hz fan speed control. This results in a significant decrease of power input
and sound level.
Mounting position
V = vertical air flow
H = horizontal air flow
Heat transfer capacities
29 = number of circuits The capacities, air flows, sound power levels and liquid pressure
DN = tube connection drop shown on the Polar Power selection software and in the
DN = flange R =outer thread tables in this brochure are certified by Eurovent Certify-All
65 = connection size certification, and are verified by tests (EN 1048) in independent
laboratories.
Option:
VC = fan speed control The performance data of the dry coolers is given for water
– 1- / 2-circuited (-/2) +40/35 °C, air entering temperature of +25 °C according to
Eurovent, and for ethylene glycol 40 %, +42/36 °C, air entering
Fans temperature +27 °C. The performance data is given at the sea
3-phase fans are suitable for 400 V-3 ph-50 Hz and single-phase level and with normal atmospheric pressure. Lwa is the A-weighted
fans for 230 V-1 ph-50 Hz. For other power supplies, the fans sound power level [dB(A)]. The A-weighted sound pressure level
must be specified as special. All fans are suitable at least for Lpa [dB(A)] is given at fan deck height at a distance of 10 meters
+50 ºC air out temperatures. Suitability for higher temperatures from the end of the unit, with the unit in free field conditions
must be checked according to fan type. Protection class of all fan over one reflective plane (hemisphere).
motors is at least IP 44.
Selection
The fan power input at +20 ºC is given in the performance data The preliminary product selection can be made by using the tables
tables. The full load current is given at a temperature of –30 ºC in this leaflet. The exact cooler selection is made by Polar Power
for specifying the overload protector. The current value changes software, which is available on CD-rom.
according to air density. This data may also vary due to changes
in motor types; therefore the overload protectors should have The selection is based on required capacity, temperatures, noise
a +/-20 % adjustment margin. level at desired point and refrigerant. The program gives the most
suitable models with heat transfer capacities, connection data,
Infinitely variable fan speed control VC noise levels by octave bands, operating cost calculations and
For 3-phase fans dimensional drawings.
Adjustment range of fan speed approximately 35…100 %
Liquid temperature 0…65 ºC
Fans provided with automatic internal thermal protection
Alarm transmission possibility
Performance data 09GF
Air on +25 °C, water +40/35 °C, EN 1048 400 V-3 ph-50 Hz
09GF Fan 4D=23.3 r/s 4Y=19.2 r/s 6D=15.0 r/s 6Y=11.7 r/s
CAP Flow Lpa Lwa CAP Flow Lpa Lwa CAP Flow Lpa Lwa CAP Flow Lpa Lwa
Ø Qty. kW m 3/s dB(A) dB(A) kW m 3/s dB(A) dB(A) kW m 3/s dB(A) dB(A) kW m 3/s dB(A) dB(A)
Capacities depend on the tubing. The exact capacity is given by the selection software. CAP = Nominal capacity
Flow = Air flow
Lpa = Sound pressure level
Lwa = Sound power level
Technical data of fan motors, 400 V-3 ph-50 Hz Technical data of fan motors, 230 V-1 ph-50 Hz
4D=23.3 r/s 4Y=19.2 r/s 6D=15.0 r/s 6Y=11.7 r/s 4D=23.3 r/s 6D=15.0 r/s
Power Power Power Power Power Power
Fan input FLC input FLC input FLC input FLC Fan input FLC input FLC
diameter kW A kW A kW A kW A diameter kW A kW A
500 0.60 1.52 0.40 0.82 0.24 0.62 0.15 0.38 500 0.59 3.60 - -
630 0.90 2.30 0.62 1.35 0.44 1.20 0.25 0.57 630 - - 0.46 2.40
Performance data for single-phase fan motors corresponds to that of 3-phase motors
with the same fan diameter and fan speed.
Qty. Ø A B H C C1 C2 D m2 l kg
36 4 630 3825 1095 1000 3572 1786 1786 1015 271 50 285
44 4 630 3825 1095 1000 3572 1786 1786 1015 362 64 320
45 5 630 4725 1095 1100 4473 1786 2687 1015 340 53 360
46 5 630 4725 1095 1100 4473 1786 2687 1015 453 70 400
47 6 630 5625 1095 1100 5373 2686 2687 1015 407 64 430
48 6 630 5625 1095 1100 5373 2686 2687 1015 543 85 480
SA = Surface area
IV = Internal volume
NW = Net weight