Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Section 4

Grilles
Introduction General Description Range

Wozair manufacture a comprehensive Frames are folded angle section • ADD


range of all stainless steel grilles with welded mitred corners. Flanges Adjustable Double Deflection with
designed specifically for the processing, are punched for bolting or fixing to front blades horizontal, rear blades
medical, leisure, marine, nuclear and ductwork, masonry, timber frames, vertical
offshore industries and other industrial doors, etc.
• ASD

Air Terminal Devices


applications such as tunnels and car
parks, where corrosion resistance, Supply grille blades are a unique roll Adjustable Single Deflection with
integrity and hygiene and aesthetics formed aerofoil section, retained in blades horizontal or vertical
are of prime importance. position with coiled pins which prevent
rattling and maintain the position once • FSD
The range is available in either 304 set at the desired attitude. Each blade Fixed Single Deflection with blades
(1.4301) or 316 (1.4404) stainless is individually adjustable. horizontal or vertical
steel. Standard finish is brushed satin
flanges although special finishes are Optional opposed blade dampers • FSD45
available upon request. Wozair are are available on grilles in the range. Fixed Single Deflection with blades
also able to offer grilles and diffusers Blades are single skin, linked to provide angled at 450
manufactured in extruded aluminium opposed motion and adjustable through
for areas with conditioned air such the front face of the grille. The gear • FEC
as offshore living quarters. Standard ratio ensures that airflow through the Fixed Eggcrate Core
finish is polyester powder coated to grille cannot move the blade setting.
RAL 9010 although other colours are The damper is constructed entirely in • FPF
available upon request. stainless steel. Fixed Perforated Face

If required plenum boxes or neck • LF


reducers can be supplied manufactured Louvred Face Transfer Grille
in either stainless steel or galvanised
sheet steel. • NS
No Sight Transfer Grille

• NSFR
No Sight Transfer Grille with rear
frame

• PFR
Perforated face Fire Retardant door
transfer grille with intumescent
element

• NSFR
No Sight Fire Retardant door transfer
grille with intumescent element

• MDFG(F)
Medium Duty Floor Grille Angle frame

• MDFG(R)
Medium Duty Floor Grille Recessed
frame

• SGC
Security Grille Concealed fixing

• SGT
Security Grille Tamperproof fixing


Section 4

Adjustable Supply Grilles

Dimensions (mm) and Types

•Minimum nominal height and width • The following can be supplied with
140mm. integral opposed blade damper
•Flange 32mm typ with 8mm Ø plain section. Add 85mm to length and
holes on 20mm backmark. ref. “/VCD” to grille code.
Air Terminal Devices

Fixed Extract Grilles

Dimensions (mm) and Types

• Minimum nominal height and • The following can be supplied


width 140 mm. complete with integral opposed
• Flange 32mm typ with 8mm Ø plain blade damper section. Add 85mm to
holes on 20mm backmark. length and ref. “ /VCD” to grille code.


Section 4

Transfer Grilles

Dimensions (mm) and types

• Note: Rear frame suitable for door to temperatures in excess of


widths 44mm and over. 200oC. They are fire resistant up to
• “No Light” arrangements are 3 hours when tested in accordance
available upon request. with BS476 Part 20.
• Intumescent elements where • Flange 25mm Typ with 6mm dia
specified shall seal off the holes on 15mm backmark.

Air Terminal Devices


ventilation opening when exposed

Floor Grilles

Dimensions (mm) and Types

Medium Duty
Max core length 1200/section
Max core width 600/section

Heavy Duty
Max core length 1200/section
Max core width 600/section

• Note: Fixing arrangements shown are typical. Other fixings available upon request.


Section 4

Security Grilles

Dimensions (mm) and types


Air Terminal Devices

Grille Ordering

ADD/VCD / 316 / 1.5 / 400W / 300H

Nom. Duct Height(mm)

Nom. Duct Width(mm)

Frame Material Thickness


1.5 = 1.5mm
Grade of Stainless Steel 2.0 = 2.0mm
304 = 1.4301 3.0 = 3.0mm
316 = 1.4404 Omit for Floor Grilles with recess frame

Grille Code
ADD = Adjustable Double Deflection Supply Grille
ASD = Adjustable Single Deflection Supply Grille
FSD = Fixed Single Deflection Extract Grille
FSD45 = Fixed Single Deflection (blades at 45o) Extract Grille
FEC = Eggcrate Core Extract Grille
FPF = Perforated Face Grille Extract Grille
LF = Louvred Face Transfer Grille
NS = No Sight Transfer Grille
NSRF = No Sight with Rear Frame Transfer Grille
PFR = Perforated Face Fire Retardant Door Transfer Grille
NSFR = No Sight Fire Retardant Door Transfer Grille
MDFG(F) = Medium Duty Floor Grille Angle Frame
MDFG(R) = Medium Duty Floor Grille Recessed Frame
HDFG(F) = Heavy Duty Floor Grille Angle Frame
HDFG(R) = Heavy Duty Floor Grille Recessed Frame
SGC = Security Grille Concealed Fixing
SGT = Security Grille Tamperproof Fixing
Add “/VCD” to product code where an opposed blade damper is required
(not usually specified for transfer, floor and security grilles.)
*Special finish requirements to be specified separately.


Section 4

Performance Data for


Adjustable Grilles

Air Terminal Devices


Section 4

Performance Data for


Fixed Grilles
Air Terminal Devices


Section 4

Diffusers
Description Core Style Configurations

Wozair manufacture a range of all


stainless steel diffusers designed to
produce 1-, 2-, 3- or 4-way directional
air patterns. Available in either 304
(1.4301) or 316 (1.4404) stainless

Air Terminal Devices


steel.

Frames are flared angle section with


welded corners. Diffuser blades
are welded into the frame, although
removable cores are available.
Optional integral opposed blade
dampers are available with single skin
blades adjustable through the front face
of the diffuser. The gear ratio ensures Note: Full performance data available upon request.
that airflow cannot move the blade
setting.

Minimum duct size 150 x 150mm


Maximum duct size 600 x 600mm
Width and height dimensions available
in 75mm increments

Diffuser Ordering

DF/VCD / 304 / 1.5 / 300W / 300H / 41

Core Pattern

Nom. Duct Width (mm) Nom. Duct Height(mm)

Frame Material Thickness


1.5 = 1.5mm
Grade of Stainless Steel 2.0 = 2.0mm
304 = 1.4301 3.0 = 3.0mm
316 = 1.4404

Diffuser Code
DF = Diffuser
DF/VCD = Diffuser with Opposed Blade Damper


Section 4

Drum Louvres
Introduction Description

Wozair manufacture a range of all The frame is an angle section, with Deflector blades are double skin
stainless steel drum louvres designed integral flanges and welded spigot. aerofoil section and are welded onto
to provide long throws with jet spread spindles. They are independently
and directional control. Available in The drum is a formed construction with adjustable and are prevented from
either 304 (1.4301) or 316 (1.4404) welded end plates. It is held in position rattling and movement by the airflow,
by self locking nuts so that once set, it
Air Terminal Devices

stainless steel. using self locking nuts.


cannot be moved by the airflow. A felt
The following design features have seal is provided to ensure that there is Optional integral blade dampers are
been included: no leakage between the drum and the available on all drum louvres in the
frame. range. Blades are single skin linked to
• Welded construction provide opposed motion and adjustable
• 60o Inclusive angle of rotation The drum may be rotated by up to 30o through the front face of the drum
• Volume control dampers (optional) either side of the centre line. louvre. The gear ratio ensures that
airflow through the drum louvre cannot
move the blade setting.

Drum Louvre Ordering

DL/VCD / 316 / 2.0 / 600W / 300H

Nom. Duct Height(mm)

Nom. Duct Width(mm)

Frame Material Thickness


1.5 = 1.5mm
Grade of Stainless Steel
2.0 = 2.0mm
304 = 1.4301
3.0 = 3.0mm
316 = 1.4404

Drum Louvre Code


DL = Drum Louvre
DL/VCD = Drum Louvre with Opposed Blade Damper


Section 4

Dimensions and types

• Nominal Duct Sizes (NDW and


NDH) = Clear inside duct
dimensions (width and height)
• Flange 32mm typ with 8mm Ø plain
holes on 20mm backmark.

Air Terminal Devices



Nominal Duct Height (NDH)

150 200 250 300 400

Protrusion (X) 30 55 80 100 145

Insertion (Y) 75 95 115 135 180

The table details preferred duct heights,


other dimensions can be considered
upon request.
Nominal duct width minimum 300mm,
maximum 1000mm.


Section 4

Performance Data for


Drum Louvre

Example

Louvre size 500mm W x 200mm H


Passing 300 l/s

Throw = 8.5m
NC = 33
Air Terminal Devices

Pressure loss = 40 Pa

Note: For Drum Louvre with VCD use


NC addition and PS multipliers as
page 5.

10
Section 4

Air Supply Nozzles


Introduction Description

Wozair manufacture a range of Frames are welded construction and The damper is an integral part of the air
stainless steel air supply nozzles are suitable for duct insertion or flange supply nozzle. It is comprised of two
designed to provide long throws with mounting. semicircular blades linked to provide
directional control. opposed motion. The linkage and
The core assembly comprises of a operating mechanism are constructed

Air Terminal Devices


The range is available in either 304 series of concentric stainless steel from stainless steel. The gear ratio of
(1.4301) or 316 (1.4404) stainless tubes supported by studding and the screw operator ensures that airflow
steel. spacer system. The core is capable of through the nozzle cannot move the
rotation through a 60o inclusive angle blades.
Design features include a robust about its centre.
welded construction, 60o inclusive
angle of rotation and the option of
including an integral blade damper.

Air Supply Nozzle Ordering

ASN / A / 304 / 1.5 / 250O

Nom. Duct Diameter (mm)

Grade of Stainless Steel Frame Material Thickness


304 = 1.4301 1.5 = 1.5mm
316 = 1.4404 2.0 = 2.0mm
3.0 = 3.0mm

Frame
A = Angle (duct insertion)
C = Channel (end of duct)

Air Supply Nozzle Code


ASN = Air Supply Nozzle
ASN/OBD = Air Supply Nozzle with Opposed Blade Damper

11
Section 4

Dimensions (mm) and types

Nominal Duct Size (NDS)

150 200 250 315 380

Protrusion (X) 35 58 80 115 140


ASN
Insertion (Y) 70 95 120 155 180

Protrusion (X) 55 80 105 140 170


ASN/OBD
Insertion (Y)
Air Terminal Devices

155 205 255 323 385

TYPE DESCRIPTION

ASN Air Supply Nozzle

ASN/OBD Air Supply Nozzle with Opposed Blade Damper

Nominal Duct Size (NDS) = Clear Inside Duct Diameter


All dimensions in mm.

12
Section 4

Performance Data

All data is for the nozzle set at 0o


deflection and operating under
isothermal conditions.
Correction factors for 15o deflection are
also given below.

NR level = Peak NR level based on


octave band sound power

Air Terminal Devices


levels.

Throw = Forward distance to the


point where the jet velocity
has retarded to a terminal
velocity of 0.5 ms.
Corrections for other
terminal velocities are
also listed.

Ps = Static pressure loss of the


nozzle when mounted in a
plenum.

AIR FLOW RATE (l/s)

UNIT SIZE PARAMETER 50 75 100 125 150 200 250 300 400 500 600 800 1000

150 THROW (m) 3.0 4.5 6.0 7.5 9.0

NRLW 25 34 41 48

Ps (Pa) 18 30 45 64

200 THROW (m) 5.5 7.0 9.0 11.3 13.5

NRLW 25 30 39 46 51

Ps (Pa) 20 27 50 75 105

250 THROW (m) 4.5 5.5 7.0 9.0 10.5 14.5

NRLW 18 27 34 39 48

Ps (Pa) 9 12 20 32 44 75

315 THROW (m) 4.5 6.0 7.0 8.5 11.5 14 17

NRLW 21 27 36 43 49

Ps (Pa) 5 9 14 19 33 50 73

380 THROW (m) 7.0 9.5 12.0 14.0 19.0 24.0

NRLW 17 26 32 39 48 57

Ps (Pa) 9 16 20 36 60 88

Corrections for 15o Setting

NR Level Addition + 11 dB

Pressure Loss Multiplier 1.25

Corrections for other Terminal Velocities

Terminal Velocity (m/s) 0.2 0.3 0.4 0.5 1.0 1.5

Throw Multiplier 2.5 1.7 1.2 1.0 0.5 0.3

13
Section 4

Terminal Units
Introduction Description

Wozair offer a range of constant and • Volume Control Damper • Attenuators


variable volume control units designed For a full description of volume Acoustic media is non-hygroscopic,
to client requirements. These are control dampers please refer to rot and vermin proof, 40 – 45 kg/m³
available in mechanical or electrical Catalogue Section 3. Typically for a mineral wool flame retardant and
control options. They comprise a flow terminal unit the volume control woven glass fibre cloth faced.
control valve or damper and where
Air Terminal Devices

damper shall be fabricated from


required attenuator or acoustically lined galvanised sheet steel although Attenuators are typically
plenum and electric heater. stainless steel is available. manufactured from galvanized
sheet steel, although stainless
Mechanical units can be supplied with • Electric Heater steel is available.
a factory set control valve to provide Single phase heaters up to 3kw are
constant volume flow. Alternatively a typically used for terminal units The infill is an inorganic non-
manually operated damper can be fitted being supplied with a local wall hygroscopic, flame, moisture and
which is set during commissioning to mounted room thermostat and auto vermin proof mineral fibre. Where
give the desired flow to the area being reset over temperature cut out. the attenuator is installed in
served. moisture or grease laden
The duct case will be either environments the infill is covered in
With the electrical control type an galvanized steel, painted steel or Melinex or glass cloth.
airflow sensing device and a control stainless steel.
system to modulate the valve or Please contact Wozair sales office
damper actuator can be supplied. Heater elements will be black heat to discuss specific requirements. Full
type comprising 80/20 nickel performance figures giving static and
Wall mounted thermostats can be chrome wire centred in 8/11mm dynamic insertion losses and static
provided for heaters to give the diameter (depending on duty) pressure drop are available on request.
occupant of the room a degree of Incoloy 800 sheaths insulated with
comfort control. Electric heaters shall compacted magnesium oxide.
be fitted with an automatic cut-out in
the event of high element or airway Element temperature is restricted
temperatures being encountered. The subject to the application but would
cut-out can be either a manual or typically be limited to 150ºC for T3
automatic reset type. applications or 400ºC. Elements
will be terminated in a flush
mounted or stand off enclosure
rated IP42 to IP56.

14