Section 7

Index

Nuclear Products
HVAC Products for the Nuclear
and Defence Industries 2

Safechange® HEPA Filter Units 4

Dampers 8

Supply Air Handling Units 16

Extract Fan Skids 19

Mobile Filtration Units 22

Mini Mobile Filtration Units 24

Quick Mix Injectors 25

Track Record 26


Section 7
7 HVAC Products for the Nuclear and Defence Industries

HVAC Products for


the Nuclear and
Defence Industries
Introduction

Wozair (abbreviated in 2000 from


Waterloo-Ozonair Limited) has been
closely associated with the Nuclear
Nuclear Products

industry for many years. The word


“Safechange®” was first registered by
Ozonair in the 1960’s.

An extensive range of ventilation


products is available, both for C1 and
C2 supply systems and C3, C4 and C5
contaminated extract systems where
safety and reliability are of paramount
importance. The range of products
includes:

• Safechange® Filter Units (Radial


and Axial Flow)

• Mobile Filter Units (Radial and Axial


Flow)

• Mini Mobile Filter Units (Radial)

• Dampers including Fire, Control,


Isolation and Non Return types

• Fully Integrated Plant Rooms

• Air Handling Units

• Quickmix Injectors

• Other Products such as Louvres,


Moisture Eliminators and Grilles
available from the Wozair Offshore
and Marine range

• Ancillary equipment such as Filter


Change Trollies and Bag Sealing
machines

• Recommended spare parts such


as Safechange® Bags and HEPA
Filters


7 HVAC Products for the Nuclear and Defence Industries
Section 7

In house manufacturing systems and


procedures are in place to ensure
quality, safety and reliability including:

• Detailed design, engineering and


3D CAD drafting

• Full CAD/CAM laser cutting up to


12mm stainless steel and 20mm
carbon steel

Nuclear Products
• Synergic MIG welding and TIG
welding to BNFL approved
procedures

• Visual Weld inspection to EN970


and Dye Penetrant non destructive
testing to EN571-1

• Pressure containment testing –


positive and negative up to 10kPa

• Blade leakage testing

• AHU performance testing –


volumetric and pressure

• Full documentation service


including life time records, material
traceability etc

In addition X Ray and MPI non


destructive testing, structural
calculations and seismic evaluation
can be carried out using approved third
parties

Wozair is approved by all the licensed


UK Nuclear operators and has an
extensive track record of supplying
equipment to the following sites:

• Dounreay
• Sellafield
• Trawsfynydd
• Dungeness
• Aldermaston
• Winfrith
• Capenhurst
• Devonport
• Risley
• Porton Down
• Heysham
• Bradwell
• Harwell
• Burghfield


Section 7
7.1 Safechange® HEPA Filter Units

Safechange® HEPA
Filter Units
Introduction

A range of radial and axial flow


Safechange® HEPA Filter Units for
use with HVAC extract systems where
radioactive or other toxic effluents may
Nuclear Products

be present. The designs are such


that the High Efficiency Particulate Air
(HEPA) filter can be changed without
the risk of contamination to personnel
and the environment.

The range is available in either


stainless steel or painted carbon steel
with a Decontamination factor in excess
of 2000.

Range

• Radial flow single filter housings Single Filter Radial Flow The cover is sealed to casing with a
75l/s to 950l/s Housings chloroprene ‘O’ ring (55 IRHD).
Designed to accept a single radial flow
• Radial flow multiple filter housings filter to AESS 30/95100, the housing A standard 50mm welded socket
is designed to be in accordance with and plug is fitted for depression
• Axial flow single filter units including NF0153/1. relief connection, and also two 6mm
pre filters as required manometer connections.
Units are available as all welded
• Manifolds for radial flow single units stainless steel (304 or 316 grade) or Filter Housings can be supplied on
or axial flow housings painted carbon steel construction. support legs to typically raise the
centre line to 1500mm. However with a
• Butterfly dampers, Isolation valves, Inlet and outlet flanges shall be 950l/s HEPA Filter weighing 18kgs it is
depression relief valves and filters precision laser pierced for connection recommended that a scissor lift change
to clients ductwork, isolation valves trolley is used to assist with manual
• PVC Safechange® Bags or manifolds. Inlet/filter spigots are handling.
accurately machined and welded in
• HEPA Filters & Spark Arrestors position. HEPA Filters are available at 75, 160,
280, 470 and 950l/s. When combined
Casing and outlet spigots are rolled onto manifolds with individual housing
and welded from 2mm thick material inlet and outlet Isolation dampers the
complete with two swaged grooves for capacity of an extract system can be
attachment of filter bags. increased in multiples of 950l/s.

Removable access cover accurately It is normal for these arrangements to


spun from 2.5mm material and fixed include 2, 3, 4, or 6 housings although
to the casing flange by machined more can be accommodated. Forming
swing back handles and with 80mm a bank of HEPA filters with one 950l/s
cruciformed handwheels. spare capacity enables contaminated
filters to be individually isolated and
changed without shutting down the
extract fan system.


7.1 Safechange® HEPA Filter Units
Section 7

Multiple Filter Radial Flow


Housings

Designed for supply to BNFL these


units are suitable for multiples of 950l/s
radial flow filters to AESS 30/95100.

Units can be supplied for 2, 4, 6 or 8


filters with various horizontal or vertical
configurations to suit requirements and

Nuclear Products
are designed to be in accordance with
NF0153/1.

The units are available in either


stainless steel (304 or 316 grade) or
painted carbon steel construction.

The unique feature of the Wozair


range is the robust fully welded
construction which guarantees the
integrity of the housings without having
to rely on gasketted panels.

The range has been seismically The fully welded filter partition plate is a
evaluated by Alsthom for use single piece with accurately machined
at Sellafield site and has been 350mm diameter filter spigots welded
successfully leak tested at pressures of in position.
up to 20kPa.
The front plate consists of welded
Inlet and outlet flanges are arranged to spigotted openings with 625mm double
suit requirements and can be circular, bag grooves for access to the filters.
rectangular or square and positioned
on any of the two sides, top, bottom or Removable access covers accurately
back of the unit. spun from 2.5mm material are provided
for each opening. These are fixed to
the housing by machined swing back
handles with 80mm cruciformed
handwheels.

The covers are sealed to the casing


with chloroprene ‘O’ rings (55IRHD).

Flanged depression relief connections


are provided for either 470l/s (150mm
flange) or 25l/s filters (100mm flange)
as required.


Section 7
7.1 Safechange® HEPA Filter Units
Nuclear Products

Axial Flow Filter Housings


Axial flow Safechange® filter housings
are available in painted mild steel or
stainless steel grade 304L or 316L. The
housings are generally 2 mm thick, and
are of fully welded construction.

The mild steel option is supplied shot A removable cover allows access Each filter housing incorporates two
blasted and painted with a 2 pack to remove and replace the HEPA or stainless steel cam bars that are
epoxy system and stainless steel option pre-filter. The front face of the access manually rotated through approximately
acid pickled and passivated. cover is fitted with two ‘goal post’ type 90°. These force the filter cell against
handles. Access covers are fitted with its sealing lip in one position and allow
The housing incorporates inlet and out four slotted brackets and corresponding removal of the filter in the second
flange connections and a bag change pivoting hand wheels are provided with position. The removable cover can only
spigot, welded as an integral part of the the bracket welded to the front plate. be fitted when the filter is in the sealed
housing and incorporating two grooves position.
for filter bag retaining bands. Hand wheels are duraplast 80mm
diameter cruciform type, manufactured The filter housing is designed for
The HEPA filter housing is designed for with an extended steel boss. A vertical downward airflow although
a HEPA filter nominally 610 x 610 mm replaceable cover gasket manufactured other orientations can be considered.
square x 298 mm deep, with either a from 55 IRHD chloroprene is provided
maximum rated capacity 0.94 m3/s or for sealing the cover onto the housing Should multiple housings be required
0.47 m3/s. The inlet face of the filter is assembly. as determined by the duty inlet and
fitted with a gasket that seals against outlet manifold sections can be
an internal lip within the filter housing. provided in order that the housings
form part of a complete assembly.
Where required a pre-filter housing
can be provided which is designed for
a panel filter nominally 610 x 610 mm
square x 50 mm deep. The inlet face
of the filter is fitted with a gasket that
seals against an internal lip within the
filter housing.


7.1 Safechange® HEPA Filter Units
Section 7

Associated Equipment and Inlet and outlet Housing


Products Isolation Dampers
For details please refer to Section 7.2
Manifolds of this catalogue.
Inlet and outlet manifolds are designed
to bank together a number of filter Depression Relief Systems
housings where an increased design Nuclear extract systems normally
airflow rate is required. operate under negative pressure, so
that to permit a filter change bag in bag
Manifolds are available in painted mild out operation, it is necessary to provide

Nuclear Products
steel or stainless steel grade 304L or a depression relief system on the
316L. Design and construction is in clean side of the main HEPA filter. This
accordance with the nuclear ductwork facility comprises an isolation valve
specification normally NF0154/2 or 3 and a disposable HEPA filter to protect
(previously AESS 6008). operators and the environment from
any possible backflow
The mild steel option is supplied shot
blasted and painted with a 2 pack Each Wozair single filter Safechange®
epoxy system, and stainless steel housing is provided with a 50mm
option acid pickled and passivated or welded socket for connection to a
manually cleaned as size permits. 5l/s depression relief valve and filter
system. With Multiple Filter Housings
Inlet and outlet flanged connections the connection maybe increased to
are supplied for connection to clients 100mm flanged for 25l/s depression
ductwork. Complete filter banks will be relief valve and filter.
assembled with gaskets and fasteners
at works and pressure tested. Isolation valves will normally be
diaphragm type for 50mm and butterfly
Supports type for 100mm.
Either individual or manifolded
Safechange® housings can be supplied Depression relief HEPA filters are
with rigid mounting frames for ease of supplied manufactured in accordance
installation at site. with AESS30/93450

Individual Safechange® housings can Valves and filter can either be provided
be specified with welded support legs loose for client installation on site or
to raise the filter centre line to a suitable piped together and supplied fitted on
working height for example 1500mm. one side of the Safechange® housing.
The support legs will generally be
50mm angle either painted mild steel or
stainless steel as the housing. PVC Safechange® Bags
For the safe handling and disposable
Manifolded housings can be mounted of contaminated filters Wozair
on a rigid cantilever structure designed Safechange® housings are provided
to support the weight of housings, with a double sealing groove for fitting
manifolds, dampers and ancilliary a PVC bag.
equipment. The support structure will
be fabricated from welded and bolted Wozair Safechange® bags are
mild steel channel and angle sections, manufactured from 250 micron thick
hot dip galvanised to EN1461. PVC and feature a rubber sealing band
and hand glove pockets for ease of
Lifting lugs and bolting down points are removal of a contaminated filter
provided for installation on site.
HEPA Filters, Pre Filters and
Spark Arrestors
Please contact our sales office.


Section 7
7.2 Dampers

Dampers
Introduction

To supplement the comprehensive


range of offshore and marine dampers
detailed in Catalogue Section 3 Wozair
offer a full range of high integrity HVAC
dampers for the nuclear industry
Nuclear Products

consisting of isolation, balancing,


control, non return and smoke/fire
dampers.

Dampers are designed generally in


accordance with BNFL specification NF
0155/1 and AWSS 12023. They are
available to meet the requirements of
ductwork specification NF 0154/1, 2 & 3
(previously AESS 6008).

Range

Isolation Dampers Dampers can be supplied as opposed Non Return Dampers


Designed for tight shut off and will blade rectangular type. For circular These dampers are designed to allow
normally be fully open or fully closed. ductwork dampers can be supplied airflow in one direction only. Upon
Airflow through the damper can be in either as single blade butterfly type backflow the dampers will close and
either direction and the dampers can be up to 400mm diameter or above this isolate the system.
installed in any orientation. size square with transition plates and
flanged spigots. Smoke and Fire Control
Operation can be specified as manual, Dampers
electrical actuation or pneumatic Balancing Dampers Designed to prevent the spread of
actuation. Manual operation is not Designed to achieve the required air smoke or fire through an air distribution
recommended for inaccessible or distribution and can be set at any system, these dampers will normally be
hazardous areas. position between open and closed. located at fire wall or floor penetration
Balancing dampers are designed for points.
manual operation with the airflow in
either direction. They can be installed Fire dampers have been independently
in any orientation. Dampers incorporate tested with the furnace controlled to
an external quadrant, handle and the time - temperature curve published
locking arrangement to enable setting in BS476: Part 20. They have type
in position once commissioning and approval from Lloyd’s Register for both
balancing has been completed. horizontal and vertical positions.

Control Dampers Dampers are suitable for airflow in


Similar in function to a balancing either direction and will operate in any
damper although the damper can be orientation.
automatically adjusted to a required
position by the use of an electric Fire dampers shall operate to close by
or pneumatic actuator coupled to a operation of the thermal trigger, remote
positioner. sensor or failure of the electric or
pneumatic supply.


7.2 Dampers
Section 7

Ductwork Application
NF 0154 Part 1

For low integrity installations for non


active areas where the ductwork is
manufactured to DW144 galvanised
sheet.

Damper frames and blades are Ductwork Application


manufactured from galvanised sheet NF 0154 Part 2

Nuclear Products
steel with laser pierced and formed
flanges. Frames are welded across the For high integrity installations where
flanges and riveted and sealed along the ductwork is manufactured from
the duct. mild steel with all welded seams and
flanged joints, suitable for temperatures
Blades are fixed to steel spindles up to 100°C and working pressures
which rotate in oil impregnated sintered of 6000Pa and air velocities of up to
bronze bearings. 15m/s.

Spindles are linked together outside the Damper frames and blades are Ductwork Application
casing to give opposed or parallel blade manufactured from mild steel hot dip NF 0154 Part 3
motion as required. galvanised or stainless steel grade
304L or 316L with laser pierced and For high integrity installations where
As this construction does not provide formed flanges. Frames are fully the ductwork is manufactured from
for spindle seals the linkage is welded across the flanges and along stainless steel with all welded seams
permanently fixed by welding. the duct. and flanged joints, suitable for
temperatures up to 100°C and working
Blades are plug welded to continuous pressures of 6000Pa and air velocities
steel spindles which rotate in oil of up to 15m/s.
impregnated sintered bronze bearings.
Drive end bearings are through type Damper frames and blades are
with removable lip seals. Non drive end manufactured from stainless steel
bearings are sealed for life. Spindles grade 304L or 316L with laser pierced
are linked together outside the casing and formed flanges. Frames are fully
to give opposed or parallel blade welded across the flanges and along
motion as required. the duct.

Linkages and pins are manufactured Blades are fixed to stainless steel
from 316 grade stainless steel and are spindles which rotate in oil impregnated
pinned and removable for maintenance sintered bronze bearings. Drive
of the lip seals. end bearings are through type with
removable lip seals. Non drive end
Fabrication of the dampers will be bearings are sealed for life.
carried out in accordance with standard
in house procedures. Spindles are linked together outside the
casing to give opposed or parallel blade
motion as required.

Linkages and pins are manufactured


from 316 grade stainless steel and are
pinned and removable for maintenance
of the lip seals.

Fabrication of the dampers will


be carried out in accordance with
fabrication procedures in compliance
with Spec. Tech. A-0339_1 and _4.


Section 7
7.2 Dampers

Operating Modes

Manual Operation
Dampers are provided with a multiple
position lockable quadrant and a
handle connected to the drive shaft with
sufficient clearance for hand operation.

Spring Loaded Latching


Dampers are held in position by a
Nuclear Products

trigger arrangement which operates


at a preset temperature (68°C).
Alternatively the damper can be latched
open by an electrio magnet which
releases when a signal from a smoke
detector or sensor is received.

Electric Operation Each damper shall be provided with Blade Leakage


Operation shall be provided by a a switch box containing limit switches
quarter turn electric actuator, such to give remote indication of open or Rectangular Isolation Dampers
as Belimo, mounted on a plate and closed status. The switch box shall Less than 0.060 m³/s per m² damper
connected to the drive shaft. The be provided as part of the actuator face area at 2000 Pa differential
actuator can be specified as 24v dc, assembly for client connection via M20 pressure for dampers up to
110v ac or 240v ac. The actuator will ISO entries. It will also include local 1000x1000mm.
include integral status switches to visual indication of damper status.
provide remote indication of damper Butterfly Isolation Dampers
open/closed status and an external The actuator assembly shall also be Less than 1l/hr per m² damper face
pointer. Normally the actuator leads will provided with a close coupled solenoid area at max working pressure up to
be provided loose although if required valve which shall cause the damper 10000 Pa.
a termination box can be supplied to operate (open or closed) when
mounted on the damper casing. A energised. Failure of the electrical Fire Dampers
manual override will be provided as supply shall either cause the damper Less than 0.060 m³/s per m² damper
required. to return to the default position or stay face area at 2000 Pa differential
put as required. Solenoid valves can be pressure for dampers up to
Pneumatic Operation provided for 24v dc, 110v ac or 1000x1000mm.
Dampers shall be provided as spring 240v ac.
return or stay put type as required. Non Return Damper
Spring return actuators, such as Hytork, If required pneumatically operated Less than 0.1 m³/s per m² damper face
shall be suitable for 4 to 8 barg supply dampers can be provided with a back are at reverse differential pressure for
and shall return to the default position; up air reservoir and non return valve. dampers up to 1000x1000mm.
damper either open or closed in the
event of loss of supply. Performance and Testing Balancing dampers and control
dampers will not normally be specified
Alternatively a double acting actuator Casing Leakage with a blade leakage requirement.
can be supplied which will stay in Damper casing leakage will be in
position upon loss of supply. accordance with the applicable Pressure Drop
ductwork classification NF 0154/1, 2
or 3 (previously AESS 6008) at the Isolation dampers and fire dampers
specified duct pressure. As standard fully open at 10m/s cause a static
all Wozair dampers for NF0154/2 and pressure drop of 18Pa.
3 ductwork systems will be 100% case
leak tested at 3000Pa to demonstrate Balancing and control dampers fully
a maximum leakage of 0.5% enclosed open at 10m/s cause a static pressure
volume per hour. For additional security drop of 15Pa.
all case welds are dye penetrant non
destructive tested and certified.

10
7.2 Dampers
Section 7

Butterfly Isolation
Damper
Typical Applications Pneumatic and Electric
Options:
A range of high integrity dampers These are operated by actuators which
has been designed to meet the move the blade from the fully open to
requirements of the nuclear industry, fully closed position.
where low case leakage, corrosion

Nuclear Products
resistance and mechanical integrity are Micro-switches, indicating blade
of prime importance. position are also available. These units
are designed to be fully open or fully
The following design features have closed.
been included:
• Continuously welded construction Leakage Rates
• Single blade The isolation damper has been
• Low casing leakage designed to minimise leakage with the
• Low blade leakage blade in the closed position. Extensive
• Manual, pneumatic, testing on 350 diameter Nuclear HEPA
or electric operation filter Isolation Dampers has indicated
• Wide range of materials a mean leakage rate of 0.0001 m³/sec
• Excellent corrosion resistance at a differential pressure of 10,500Pa.
Specific requirements regarding
Description leakage should be discussed with
Wozair engineers.
Rolled casing manufactured from
1.5mm minimum thick material, with
welded seam, length over flanges
minimum 100mm. Welded flanges 25
x 6mm thick drilled to standard nuclear
specification pattern. A single 2mm Ordering
thick circular butterfly blade with a one
piece neoprene seal, bolted to 19mm Quantities, surface finish and other
diameter shaft that rotates in sealed special requirements to be stated
‘oilite’ bearings. The shaft is extended separately.
on one side for actuator mounting.
Type BID Duct Dia 356Ø
Control Mechanism Material 316L Case Depth 100D
Manual Isolating Damper: This is
Type Wozair: Butterfly Manual
operated by a robust adjusting handle Isolation Damper
with a locking device which moves
across a quadrant plate. Moving the Case Material:
Stainless Steel
handle through 90º moves the blade
Low Carbon 1.4307 (SS304L) = 304L
from the fully open to the fully closed Low Carbon 1.4404 (SS316L) = 316L
position, thereby enabling the unit to Mo>2.5% 1.4432 (SS316L) = 316L
be used for volume control purposes if
Case Thickness: 1.5mm
necessary.
Nominal Clear inside duct dimensions
Duct Size: ‘Quote’ inside Diameter

Order Code Example:


BID/316L/1.5/356Ø/100D

11
Section 7
7.2 Dampers

Ultra Low Leakage


Isolation Damper
Introduction

To supplement the existing


comprehensive range of nuclear
dampers, Wozair now offer an
Ultra Low Leakage Isolation Damper
Nuclear Products

(IDX) suited for safety critical


applications where there is the need
to maintain very low leakage rates
while maintaining extreme ductwork
pressures such as tie-in sections and
venting to atmosphere.

The following design features have


been included.

• Continually welded construction


• Parallel blade motion
• Ultra low case leakage
• Ultra low blade leakage
• Manual or electric operation
• Excellent corrosion resistance

Description

Casing Blades Control Mechanism


This is a continuously welded channel These are typically of stainless steel Manual Ultra Low Leakage
section construction and is available in grade 1.4404/1.4307. They are of Isolation Damper: This is
stainless steel and thickness. Typically: double skin aerofoil section, minimum operated by a hand wheel and
Stainless steel grade 1.4404 (316L) 1.5mm per skin. Blades are plug gearbox mechanism, this is available
and grade 1.4307 (304L) minimum of welded to continuous shafts and rotate in either cast iron or stainless steel
3mm thick. Angles are fitted at the top in self lubricating phosphor bronze oilite constructions.
and bottom as well as stainless steel bearings and are linked externally to
grade 1.4404 (316L) precision roll provide parallel blade motion. Reduced Electric Ultra Low Leakage
formed sprung side seals in order to blade leakage is achieved by a Wozair Isolation Damper: Please contact
achieve an effective seal between the unique metal blade edge seal which Wozair with your requirements.
damper case and the blades. does not rely on self adhesive rubber
type seals and therefore does not put Options
the dampers operational life at risk. The following options can be
incorporated if required.
• Increased case thickness
• Increased flange thickness
• Ceramic or PTFE bearings in place
of phosphor bronze oilite.
• Transition pieces for fitting into
circular ductwork
• Lifting lugs
• Earth bosses

12
7.2 Dampers
Section 7

Leakage rates
The damper has been designed
generally in accordance with the latest
BNG/BNFL and AWE specifications
NF0155/1 and /DSD01/A/S/2051/001.

The damper is available to meet the


requirements BNFL/BNG ductwork
specification NF0154/ 3 (previously
AESS6008).

Nuclear Products
The IDX has been successfully tested
at the BSRIA laboratories, Bracknell,
Berkshire, United Kingdom, to meet the
continual ever changing demands of
the nuclear industry.

The test was carried under stringent


conditions with the damper being
subjected to pressure in excess of
7kPa (7000Pa) and achieving 35l/s/m².
(BSRIA report 50937/1 July 2007).

In order to achieve this figure a


unique parallel blade design has been
developed and in line with NF0155 and
DSD01/A/2051/001 respectively.

Blade Leakage Graph Ordering

Quantities, surface finish and other


special requirements to be stated
separately.

Type IDX Duct Width 500W

Material 316L Duct Height 500H

Case Thickness 3.0 Case Depth 300D

Type Wozair: Ultra Low Leakage


Isolation Damper

Damper Types:
MIDX = Manual Ultra Low Leakage Isolation
Damper
EIDX = Electric Ultra Low Leakage Isolation
Damper

Case Material:
Stainless Steel
Low Carbon 1.4307 (SS304L) = 304L
Low Carbon 1.4404 (SS316L) = 316L
Mo>2.5% 1.4432 (SS316L) = 316L

Case Thickness: 3mm minimum

Nominal Clear inside duct dimensions


Duct Size: ‘Quote’ (Width x Height)

Order Code Example:


MIDX/316L/3.0/500W/500H/300D

13
Section 7
7.2 Dampers

Total Isolation
Damper
Introduction

To supplement the existing


comprehensive range of nuclear
dampers, Wozair now offer a Total
Isolation Damper (TID) suited for
Nuclear Products

extreme applications where there is the


need to maintain zero leakage rates
while operating within high ductwork
pressures.

The following design features have


been included.

• Continually welded construction


• Parallel blade motion
• Unique blade assembly
• Zero case leakage
• Zero blade leakage
• Manual or electric operation
• Excellent corrosion resistance

Description

Casing
This is a continuously welded channel
section construction and is available in
stainless steel and thickness. Typically:
Stainless steel grade 1.4404 (316L)
and grade 1.4307 (304L) minimum of
5mm thick.

Blades Control Mechanism


These are typically of stainless steel Manual Total Isolation Damper:
grade 1.4404/1.4307. They are of This is operated by a hand wheel and
single skin tray section, minimum 3mm gearbox mechanism, this is available
per skin and complete with gasket. in either cast iron or stainless steel
Blades are plug welded to continuous constructions.
shafts, incorporated into a linkage
arrangement, rotate in self lubricating Electric Total Isolation Damper:
phosphor bronze oilite bearings and Please contact Wozair with your
are linked externally to provide parallel requirements.
blade motion.
Options
The following options can be
incorporated if required.
• Increased case thickness
• Increased flange thickness
• Ceramic or EPDM bearings in place
of phosphor bronze oilite.
• Transition pieces for fitting into
circular ductwork
• Lifting lugs
• Earth bosses

14
7.2 Dampers
Section 7

Nuclear Products
Leakage rates Ordering
The damper has been designed
generally in accordance with the latest Quantities, surface finish and other
BNG/BNFL and AWE specifications special requirements to be stated
NF0155/1 and DSD01/A/S/2051/001. separately.

The damper is available to meet the Type TID Duct Width 500W
requirements BNFL/BNG ductwork
Material 316L Duct Height 500H
specification NF0154/ 3 (previously
Case Thickness 5.0 Case Depth 300D
AESS6008).
Type Wozair: Total Isolation Damper
In order to achieve this figure a
unique parallel blade design has been Damper Types:
MTID = Manual Total Isolation Damper
developed and accepted in line with
ETID = Electric Total Isolation Damper
NF0155/1 and DSD01/A/S/2051/001.
Case Material:
Stainless Steel
Low Carbon 1.4307 (SS304L) = 304L
Low Carbon 1.4404 (SS316L) = 316L
Mo>2.5% 1.4432 (SS316L) = 316L

Case Thickness: 5mm minimum

Nominal Clear inside duct dimensions


Duct Size: ‘Quote’ (Width x Height)

Order Code Example:


MTID/5.0/316L/500W/500H

15
Section 7
7.3 Supply Air Handling Units

Supply Air Handling


Units
Introduction

Wozair manufacture and supply high


integrity Air Handling Units for the
Nuclear Industry. Both draw through
and blow through units are available.
Nuclear Products

Units are designed for use in exposed


coastal areas typical of power station
locations with a 40 year life expectancy.
Units are manufactured to comply
with NF specifications and specific
site requirements making most units Standards Casing
unique. In addition to designing the Air
Handling Unit as the main supply plant Wozair design and manufacturer Air The casing consists of a rigid
it can also perform the function of a Handling Units to comply with NF and construction framework with lagged
pressurisation unit. AWE specifications and EC directives. infill panels for thermal insulation and
noise attenuation.
Units incorporating centrifugal fans are Units comply with Directives and any
designed with the fans contained within amending Directives: The frame work is continuously welded
a panelled crate. Machinery Directive 2006/42/EC and manufactured from stainless steel
Low Voltage Directive 2006/95/EC grade 1.4404 (316L) or 1.4307 (304L).
Units are generally designed to be ATEX Directive 94/9/EC The frame work is 1.5 mm, 2.0 mm or
lifted and positioned as one complete EMC Directive 2004/108/EC 3.0 mm dependant upon the size and
assembly so as to minimise installation Pressure Equipment 97/23/EC application. If required the frame work
time. However if required they can Directive can be insulated with a closed cell
be supplied in modular format for re- elastomeric material or mineral wool to
assembly on site. Wozair units have been in-house eliminate a heat bridge.
tested to EN1886 meeting T2 thermal
The main features and components transmittance and TB1 thermal bridging Infill panels are double skinned
of an Air Handling Unit are presented requirements. and flush mounted. Infill can be 25
herein. mm or 50 mm thick and is used to
Skid provide thermal insulation and noise
attenuation. Infill material can be
The Air Handling Unit is supplied extruded polystyrene rigid board
as a skid mounted assembly with bonded to the panel skin or mineral
the skid fabricated from hot rolled wool. Panel skins are manufactured
structural steel sections. The skid from the same material as the frame
can be designed to BS 449 and with work with a range of sheet thicknesses
consideration for transportation forces available from 0.9 mm to 2.0 mm.
and any seismic conditions. Skids Hinged access panels are provided
are welded by coded welders and for inspection and maintenance of
hot dip galvanized to EN 1461 after equipment.
manufacture. If required main welds
can be subject to NDT. Lifting lugs and A baseplate manufactured from the
earthing points are provided. same material as the frame work is
sandwiched between the frame work
and the skid and is insulated if required.

Externally mounted units can be


provided with a pitched roof to shed rain.

16
7.3 Supply Air Handling Units
Section 7

Nuclear Products
Air Handling Units can be designed As a general rule where the face
with 100% run and standby fan sets or velocity on the cooling coil exceeds
2 x 50% fan sets or run and standby 2.5 m/s a vane eliminator should be
motors on a single fan. With dual installed to prevent moisture carry-
fan arrangements fans are installed over. Vane eliminators can be supplied
Fans in separate chambers to enable in stainless steel 316, marine grade
maintenance on one fan to be carried aluminium or polymers.
Fans are typically of the DIDW out whilst the other is in operation.
centrifugal type to NF0152/1 with These chambers can be configured The cooling coil section of the Air
non-stalling and non-overloading side-by-side or one above the other Handling Unit is provided with a drain
characteristics. Fans are generally belt subject to practical transportation limits. tray to drain to the edge of the skid.
driven although direct drive fans can Inlet guide vane, manual or automatic
be provided for operation with variable isolation and non-return dampers can Temperature control valves can be
speed drives. be provided to control the airflow and supplied as required.
isolate the fan chamber.
The fan casing can be gas tight Heating Coils
to the requirements of NF0152/2 Motors
manufactured from mild steel (type B) These shall generally be as described
or stainless steel (type D). Impellers These are in accordance with above but suitable for operation with
can be mild steel painted or stainless NF0004/1, NF0004/2, NF0004/2, steam, hot water or a heating medium.
steel as appropriate. NF0032/1, BS 4999 and BS 5000 Some applications may demand the
suitable for direct on line starting and use of stainless steel tube.
Fans are driven by LV motors. Where operating on 415V. If required we
belt drive is employed, belts are an can supply motor to operate on any Electric Heaters
anti-static, vee design. The motor is common 3 phase low voltage supplies
mounted on a frame integral to the fan of 50 Hz and 60 Hz. Electric heaters are designed for
set. The fan is isolated from the Air thyristor or step control. Generally
Handling Unit by anti-vibration mounts If required Wozair can supply motors elements are 80/20 nickel/chrome
and flexible connections. rated suitable for use in a potentially resistance wire insulated with
hazardous area as required and compacted magnesium oxide and
If required Wozair can supply fans compliant with project specifications ceramic beads in Incoloy 800 sheaths.
suitable for operating within a zone 1 or and standards where stipulated. Thermocouples, RTD’s or thermostats
zone 2 motors hazardous area and as are installed to detect element and
such the fans shall incorporate anti- Cooling Coils air over temperature. Element
spark features. temperature is normally restricted to
Cooling coils can be selected to 150 - 200ºC.
Fans can be provided with the following operate with refrigerant or chilled water.
accessories: speed sensor, bearing Tubes are typically seamless copper If required heaters can be supplied
monitoring, extended lubricators, and are expanded on to copper fins suitable for operation in a potentially
automatic grease lubricators, drain although aluminium fins are available. hazardous area but any manual or auto
plug, access door, inlet and discharge Copper fins may be pre-tinned or reset device operated in conjunction
guards and belt guards. copper tube and fin coils electro-tinned with the over temperature sensor
after manufacture. Alternatively with should be located in a control panel in
copper tube and fin coils or copper a non-hazardous area. The elements
tube and aluminium fins a PolyAl anti- are terminated in a stainless steel
corrosion treatment can be provided. enclosure.

17
Section 7
7.3 Supply Air Handling Units

Filters Control Dampers Safety Features

A wide selection of panel and bag In addition to the dampers previously The units are provided with an EC
filters is available to suit a range described in the fan section control Declaration of Incorporation. Where
of application such as removal of dampers at the Air Handling Unit personnel can gain internal access
dust or coalescing filters for the inlet or discharge can be supplied. to maintain filters, dampers, fan sets
removal of particulate salt to reduce Dampers can be used to isolate the or other equipment then lights of
the concentration to less than 0.05 unit, regulate the airflow or in the the filament or fluorescent type are
ppm. If required HEPA filters can be case of a unit drawing in a mixture of provided operated from a common
incorporated within the Air Handling Unit. fresh and re-circulated air, modulating switch. For the fan motor a push
Nuclear Products

control dampers to vary the mix ratio. button emergency stop can be fitted.
Filters are arranged on mounting Modulating dampers can be provided As required any electrical components
frames within the unit to suit side or with pneumatic, electro-pneumatic shall be suitable for use in a hazardous
front withdrawal. Instrumentation or electric positioners suitable for a area.
can be provided to monitor the filter hazardous or non-hazardous area.
condition during operation such as a Ancillary Components
differential pressure gauge, switch or Controls/Wiring
transmitter. The following features can be provided:
Control panels can be provided • Temperature, pressure and
With coalescing filters vane eliminators installed on the unit skid or supplied humidity instrumentation
can also be provided to prevent loose. The design and features of • Test points
moisture carry-over. Vane eliminators each panel is dependant upon the • Interface junction boxes
can be supplied in stainless steel 316 application and requirements. Control • Maintenance beams to lift and
or marine grade aluminium. panels can be provided for installation move motors, typically 15 kW and
in a hazardous area though it is above
Humidification recommended that wherever possible • Spreader beams with shackles for
they are located in non-hazardous lifting and positioning the units on
Electrically operated fresh steam area. site
humidifiers may be installed if required. • Access platforms and ladders for
Alternative humidifier types can Wozair can provide heater thyristor equipment at high level
be considered upon request. The control panels, variable speed drives • Drain traps and pipes
humidifier, including its water tank and HVAC control panels to suit • Trace heating of drains
and steaming chamber form part of customer requirements.
the unit package, space permitting. A Testing
matrix of injection tubes is installed Electrical components on the Air
within the unit case as they provide Handling Unit shall generally be cabled Various testing options are available
the best solution for achieving the to a terminal box mounted external to on the completed Air Handling Unit
minimum absorption distance. The the unit. including:
humidifiers are supplied with a control Running motors on project specified
panel and can be suitable for thyristor Cabling shall as minimum be flame voltage and frequency 50Hz/60Hz
or step control. It is preferable to locate retardant PVC with options to provide Volume/pressure testing based on BS
humidifiers within a non-hazardous area. low smoke, zero halogen cable both 6583
unarmoured and armoured. Cabling Case deflection and leakage based on
Weather Louvres can be run in cable tray as required. EN 1886
Earthing continuity is achieved by Case leakage testing up to 3000 Pa
For an exposed fresh air intake a cabling equipment to a common Indicative noise breakout testing
weather louvre can be provided, if earthing point on the unit skid base. Measurement of the fan running speed
required, to prevent the ingress of rain Cable penetrations into the unit are by Recording motor running current
water into the Air Handling Unit inlet. way of gland plates or transit frames.
Leakage performance of Wozair Air
Handling Units meets DW143 Class B
where the leakage from the casing is
calculated as:
Leakage (l/s/m²) = 0.009 x test
pressure0.65

18
7.3 Extract Fan Skids
Section 7

Extract Fan Skids


Introduction Standards

Wozair manufacture and supply high Wozair design and manufacturer its
quality Extract Fan Skids to the Nuclear Fan Extract Skids to comply with EC
Industry. Units are designed for use in directives, NF and AWE specifications.
exposed coastal site locations typical
of Power Station locations with a 40 Units comply with Directives and any

Nuclear Products
year life expectancy. Fan Skids are amending Directives:
manufactured to comply with specific Machinery Directive 2006/42/EC
client and site requirements. Low Voltage Directive 2006/95/EC
ATEX Directive 94/9/EC
Fan Skids Units are typically designed EMC Directive 2004/108/EC
with centrifugal fans. Units can be
designed with: a single fan, 100% run
and standby fan sets, 2 x 50% fan sets
or run and standby motors on a single
fan.

For low integrity systems with dual


DIDW the fans are contained within
a panelled crate and are installed
in separate chambers to enable
maintenance on one fan to be carried
out whilst the other is in operation. For
low integrity systems with dual SISW
centrifugal fans the fans are “ducted
mounted” with each fan installed in a
separate duct branch and a manifold
duct connection piece at the inlet to
connect to the extract ductwork.

For high integrity systems gas tight


SISW fans shall be used and with dual
fan arrangements the fans are “ducted
mounted” with each fan installed in a
separate duct branch and a manifold
duct connection piece at the inlet to
connect to the extract ductwork.

Units are generally designed to be


lifted and positioned as one complete
assembly so as to minimise installation
time.

The main features and components


of an Extract Fan Skid are presented
herein.

19
Section 7
7.3 Extract Fan Skids

Skid

The Extract Fan Skid is supplied


as a skid mounted assembly with
the skid fabricated from hot rolled
structural steel sections. The skid
can be designed to BS 449 and with
consideration for transportation forces
and any seismic conditions. Skids
are welded by coded welders and
Nuclear Products

hot dip galvanized to EN 1461 after


manufacture. If required main welds
can be subject to NDT. Lifting lugs and
earthing points are provided.

Casing (Low Integrity


Systems)

A crated unit is provided when using


DIDW centrifugal fans. The casing
consists of a rigid construction
framework with lagged infill panels available from 0.9 mm to 2.0 mm. Fans are driven by LV motors. Where
for thermal insulation and noise Hinged access panels are provided belt drive is employed, belts are an
attenuation. for inspection and maintenance of anti-static, vee design. The motor is
equipment. mounted on a frame integral to the fan
The frame work is continuously welded set. The fan is isolated from the Air
and manufactured from stainless steel A baseplate manufactured from the Handling Unit by anti-vibration mounts
grade 1.4404 (316L) or 1.4307 (304L). same material as the frame work is and flexible connections.
The frame work is 1.5 mm, 2.0 mm or sandwiched between the frame work
3.0 mm dependant upon the size and and the skid and is insulated if required. If required Wozair can supply fans
application. If required the frame work suitable for operating within a zone 1
can be insulated with a closed cell Externally mounted units can be or zone 2 hazardous area and as such
elastomeric material or mineral wool to provided with a pitched roof to shed the fans shall incorporate anti-spark
eliminate a heat bridge. rain. features.

Infill panels are double skinned Fans (High Integrity Fans can be provided with the following
and flush mounted. Infill can be 25 Systems) accessories: speed sensor, bearing
mm or 50 mm thick and is used to monitoring, extended lubricators,
provide thermal insulation and noise Fans are typically of the high integrity automatic grease lubricators, drain
attenuation. Infill material can be SISW centrifugal type to NF0152/2 plug, access door, inlet and discharge
extruded polystyrene rigid board with non-stalling and non-overloading guards and belt guards.
bonded to the panel skin or mineral characteristics. Fans are generally
wool. Panel skins are manufactured belt driven although direct drive fans With dual fan arrangements fans are
from the same material as the frame can be provided for operation with installed in separate duct branches
work with a range of sheet thicknesses variable speed drives. The fan casing complete with shut-off damper to
shall be gas tight to the requirements enable maintenance on one fan to
of NF0152/2 manufactured from mild be carried out whilst the other is in
steel (type B) or stainless steel (type operation. Dual fans can be configured
D). Impellers can be mild steel painted side-by-side or one above the other
or stainless steel as appropriate. subject to practical transportation limits.

Inlet guide vane, manual or automatic


isolation and non-return dampers can
be provided to control the airflow and
isolate the fan.

20
7.3 Extract Fan Skids
Section 7

Nuclear Products
Motors

These are in accordance with


NF0004/1, NF0004/2, NF0004/2,
NF0032/1, BS 4999 and BS 5000
suitable for direct on line starting and
operating on 415V. If required we
can supply motor to operate on any
common 3 phase low voltage supplies
of 50 Hz and 60 Hz.

If required Wozair can supply motors Testing


rated suitable for use in a potentially
hazardous area as required and Various testing options are available
compliant with project specifications on the completed Extract Unit and gas
and standards where stipulated. tight fans including:

Weather Louvres For low integrity cased fans in a crated


unit:
Refer to section 7.3 • Volume/pressure testing based on
BS 6583
Controls/Wiring • Case deflection and leakage based
on EN 1886
Refer to section 7.3 • Case leakage testing up to 3000 Pa
• Indicative noise breakout testing
Safety Features • Measurement of the fan running
speed
The units are provided with an EC • Recording motor running current
Declaration of Incorporation. Where
personnel can gain internal access For high integrity gas tight fans:
to maintain dampers or fan sets then • Pneumatic pressure test of fan
lights of the filament or fluorescent type casing prior to painting or
are provided operated from a common galvanising
switch. For the fan motor a push • Pneumatic pressure test of fan
button emergency stop can be fitted. casing following assembly to twice
As required any electrical components the working differential pressure
shall be suitable for use in a hazardous • Static and dynamic balancing of
area. impeller
• Vibration measurements to the
Ancillary Components requirements of BS 6581 grade G6.3
• Mechanical run test
Refer to section 7.3 • Performance test to BS 848 Part 1
• Measurement of the fan running
speed
• Recording motor running current/
power input

21
Section 7
7.4 Mobile Filtration Units

Mobile Filtration
Units
Introduction

Wozair manufactures a range of


Mobile Filtration Units to compliment
their radial and axial type safe change
HEPA filter systems.
Nuclear Products

Wozair are able to offer flexible


solutions to extract ventilation problems
where it is not always possible to
introduce the conventional static HEPA
filter banks to assist in waste operations.

Primarily the Wozair Mobile Filtration


Unit is used in the decommissioning
process in conjunction with some sort
of temporary ventilation enclosure. The
emphasis is very much on a “Plug and
Play” scenario.

As the name “Mobile” suggests the


Filtration Unit is an economical solution
to decommissioning projects.

Legislation Unit Specification Technical Specifications


Materials
Wozair Mobile Filtration Units shall Wozair Mobile Filtration Units shall be
be fully compliant with EC Legislation tailored to suit a range of client specific Wozair Mobile Filtration Units shall be
and shall be supplied with EMC testing requirements when dealing with waste available in Epoxy coated carbon steel
certification. and shall include as required. or Stainless steel grades 1.4307 (304L)
or 1.4404 (316L)
Client Specifications • Rigid mounting frame (skid based)
or with braked castors for mobility. • Depression Relief systems to assist
Wozair Mobile Filtration Units shall be • Lifting Lugs with bag change
fully compliant with the requirements of • Pre-Filters with safe change facility • Pressure and Flow monitoring
NF or AWE specifications with all Mobile • Spark arrestors with safe change systems
components being compliant with he facility • DOP testing and sampling points
relative standards too and tailored to • Primary HEPA Filters with safe • Quick Mix Injector
suit specific applications on site. change facility • Pre-Heater
• Secondary HEPA Filters with safe • Fans: Two stage or single stage
Custom built and designed for change facility contra rotating axial or Centrifugal
specified SIL (Safety Integrity Level) • Isolation Dampers for Inlet and outlet type to suit client requirements
substantiation. • Local Control Panels to suit client
requirements and shall include as
required:
• Local/Remote audible and visual
alarms
• Emergency Stop Button
• Programmable Logic Control
• Thyristor Control
• Invertor Speed Control
• Thermal/Thermistor cut outs

22
7.4 Mobile Filtration Units
Section 7

Testing

Wozair Mobile Filtration Units shall


be fully factory function tested for
performance and leakage. Witness
and stage inspection points to client
requirements.

Environmental - Applications

Nuclear Products
Levels of Waste Contamination
Low Level Waste (LLW)

Waste that, because of its low


radionuclide content does no require
shielding during normal handling and
transportation, i.e wastes other than
those suitable for disposal with ordinary
refuse but not exceeding specified
levels of radioactivity.

Intermediate Level Waste (ILW)

Wastes exceeding the upper


boundaries for LLW, but which do not
need heat to be taken into account
in the design of storage or disposal
facilities. Major components are metal
items such as nuclear fuel casing and
reactor components as well as sludge
from treatment of radioactive effluents. Ordering

High Level Waste (HLW)


Type MFU Capacity 950L

Wastes in which there is a significant Material 316L

temperature rise as a result of their Case Thickness 2.0


radioactivity. Major components are liquids Type Wozair: Mobile Filtration Unit
containing fission products, nitric acid
Case Material:
solutions. Spent reactor fuel if declared
Stainless Steel
waste can be included in the level. Low Carbon 1.4307 (SS304L) = 304L
Low Carbon 1.4404 (SS316L) = 316L
Mo>2.5% 1.4432 (SS316L) = 316L

Case Thickness: 2mm minimum

Order Code Example:


MMFU/316L/2.0/950L

23
Section 7
7.4 Mini Mobile Filtration Unit

Mini Mobile
Filtration Unit
Introduction

Wozair manufactures Mini Mobile


Filtration Units to compliment their
existing range of Mobile Filtration Units.
Nuclear Products

The Mini Mobile Filtration Units offer


flexible solutions to temporary extract
ventilation problems where it is not
always possible to introduce the
conventional static HEPA filter banks or
Mobile Filtration Units to assist in waste
operations.

The Wozair Mini Mobile Filtration


Unit is used in the decommissioning
process in conjunction with some sort
of temporary ventilation enclosure. The
emphasis is very much on a “Plug and
Play” scenario.

Technical Specifications
Materials

Wozair Mini Mobile Filtration Units


shall be available in Epoxy coated
carbon steel or Stainless steel grades
1.4307 (304L) or 1.4404 (316L) Ordering

Unit Specifications Type MMFU Capacity 470L

Material 316L
• Fans: single stage axial type to suit
Case Thickness 2.0
client requirements
Type Wozair: Mini-Mobile Filtration Unit
• Local Control Panels to suit client
requirements and shall include as Case Material:
required: Stainless Steel
• Local/Remote audible and visual Low Carbon 1.4307 (SS304L) = 304L
Low Carbon 1.4404 (SS316L) = 316L
alarms
• Emergency Stop Button
Mo>2.5% 1.4432 (SS316L) = 316L

• Programmable Logic Control Case Thickness: 2mm minimum

• Thyristor Control Order Code Example:


• Invertor Speed Control MMFU/316L/2.0/470L
• Thermal/Thermistor cut outs
• Braked castors for mobility
• HEPA Filters with safe change facility
• Isolation Dampers for Inlet and outlet
(optional)

24
7.5 Quick Mix Injectors
Section 7

Quick Mix Injectors


Introduction

Wozair own the patent rights for the The QUICKMIX Injector is a
QUICKMIX Injector , a product that breakthrough for plant designers
was designed, developed and tested providing a simple low cost method of
by the Atomic Energy Authority to injecting and thoroughly mixing active
provide a solution to challenge HEPA aerosol upstream of the HEPA filter.
filter systems where space constraints

Nuclear Products
restrict ductwork systems to tight Duct lengths can be reduced to
configurations precluding the use of between 2 – 6 duct diameters
conventional methods of DOP testing. depending on the system parameters.

Operation The QUICKMIX Injector allows


for a sampling to be conducted using
The QUICKMIX Injector has been a single sampling probe providing
developed to confirm the efficiency negligible pressure drop to the
and effectiveness of HEPA filtration installed system.
systems within Nuclear plants, meeting
the standards demanded by the The QUICKMIX Injector system
Nuclear Industry and it’s regulators, only requires a conventional DOP
ensuring the safety and environmental generator and a compressed air supply
acceptability of its operations. to ensure satisfactory operation. The Product

The conventional way to generate a The QUICKMIX Injector is


well mixed aerosol mist is to use long manufactured from stainless steel
straight lengths of ducting to allow grade 1.4404 (316L) and is mounted to
‘natural’ mixing (creating expensive and the duct using a BS4504 PN6 Flange
bulky process plants) or to introduce such that the injector nozzle sits on the
mixing baffles into the duct system. centre line of the duct system to ensure
a uniform distribution of the aerosol
The inherent pressure drop introduced mix.
by methods such as this necessitates
the use of larger fans which in turn The QUICKMIX Injector requires a
means increased capital and plant compressed air supply of 10 to 15 L/S
running costs. at variable pressures of 2 to 3.5 bar
The standard unit is supplied with
Hansen quick release couplings.
However a range of isolation valve
options are available on request.

25
Section 7
7.6 Track Record

• AWE Burghfield – Building Project

• AWE Aldermaston – Building A89.2,


U1 Chambers HEPA Safechange
Filters, Gauge Boxes, Drum Store
Nuclear Products

and Building A91

• Bradwell – HEPA Safechange Filters

• Capenhurst – Spark Arrestor Facility

• Chemical Defense Est. Porton Down


– Design & Supply of Safechange
Filter System, Air Handling Units &
Site Services

• Devonport Dockyards – Steam • Risley Laboratories – HEPA


Barge and N102 Project Safechange Filters

• Dounreay – D2001 Project, ETP • Sellafield – B215 Facility, BTC Project,


Project, D1215 Vent Upgrade, Encapsulated Product Store, Sludge
D1208 Project, D1209 Project, Packaging Plant, B229 Facility,
D1209 Tie In, Breeder Fuel Removal, SAV Tie-In, B204 Facility, SPRS,
DN060 Conversion, D1231 Project, WVP Residue Export, B38 Caves,
D2580 Project, Dounreay Fast BTC Facility, B205 Project, EDS2
Reactor, DFR Phase 1, DFR Phase 2, Project, Wet Inlet Facility, B13
D1203 Project, Building D9867, Amber Extract, BNFL B215 Caustic
Fan 6 Project and D2670 Project Scrubber, DryPac Facility, Thermal
Oxide Reprocessing Plant (THORP)
• Dungeness B Power Station – and Southern Store
Luggs Retrieval and HV1C Facility
• Trawsfynydd Power Station –
• GE Healthcare, Amersham – Hydrogen Extract Package Unit Air
Building 22 Phase 2 and Building 22 Handling Unit, Ducting & Installation
Phase 3 and ILW Project

• Hartlepool Power Station – • Winfrith – WOMAD East


NF Spec Dampers
• Winscale – PIE Cave
• Harwell – Package, B482 Facility

• Heysham Power Station – ILW Project

• Hunterston A – Pond and ILW Vault

• Oldbury Powers Station –


Battery Room

• PAKS – HEPA Safechange Filters

26