Technical Specifications

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Technical Specifications

Item 1: Stepped Inductive Compensator 350 KVAr Qty : 5 Nos.

Design System Specification 480 AC +/-10% Frequency: 60 Hz 3P3W Supply

Rated Output 350 KVAr at 480 VAC


Rated Current : 421 A at full load
Proposed Banking: 50 KVAR x 1, 100 KVAR x 3
Incomer 630A TP 50KA MCCB with Microprocessor Based LSIG release

Indication R,Y,B, On,Off,Trip

Metering 3 Phase Digital Ammeter, Class 1, 96x96

Control Transformer 480/220 VAC control transformer of 1KVA with MPCB/MCB


protection

APFC Controller 3CT Sensing Microprocessor based PFC Controller with 8 Steps, LCD
display, in-built data logger and RS-485 communication

Operation Auto

Shunt Reactor 3 Phase Copper wound low loss shunt reactor with thermal cut-off
switch as per bank rating.
Switching
Thyristor Switching Modules consisting of 2200 PIV thyristors,snubber
firing cards and other accessories mounted on heat sink
Bank Protection HRC Fuse with Base

Cooling Forced cooling with heavy duty thermostat operated fans

Enclosure The Non-Compartmental, Floor Miounting Free Standing type


Enclosure shall be fabricated using 2/mm thick CRCA sheet duly
powder coated. Gland plate shall be fabricated using 3 mm thick
CRCA Sheet.
Tentative Dimensions : TBD
Wiring Power wiring shall be done using Univyn cable. Sleeving shall be
done using high temperature imported sleeves ( withstanding
temperatures upto 135 deg C)
Control wiring shall bedone using suitably color coded Cu flexible
wires - 1.5 sq mm (control) / 2.5 sq mm ( CT circuit) Cu flexible
cables of reputed makes.
Item 2: Stepped Inductive Compensator 180 KVAr Qty : 3 Nos.

Design System Specification 480 AC +/-10% Frequency: 60 Hz 3P3W Supply

Rated Output 180 KVAr at 480 VAC


Rated Current : 216.5 A at full load
Proposed Banking:
Auto: 90 KVAR x 1, 45 KVAR x 2

Incomer 400A TP 50KA MCCB with Microprocessor Based LSIG release

Indication R,Y,B, On,Off,Trip

Metering 3 Phase Digital Ammeter, Class 1, 96x96

Control Transformer 480/220 VAC control transformer of 1KVA with MPCB/MCB


protection

APFC Controller 3CT Sensing Microprocessor based PFC Controller with 8 Steps, LCD
display, in-built data logger and RS-485 communication

Operation Auto

Shunt Reactor 3 Phase Copper wound low loss shunt reactor with thermal cut off
swtich as per bank rating.
Switching
Thyristor Switching Modules consisting of 2200 PIV thyristors,snubber
firing cards and other accessories mounted on heat sink
Bank Protection HRC Fuse with Base

Cooling Forced cooling with heavy duty thermostat operated fans

Enclosure The Non-Compartmental, Floor Mounting Free Standing type


Enclosure shall be fabricated using 2/mm thick CRCA sheet duly
powder coated. Gland plate shall be fabricated using 3 mm thick
CRCA Sheet.
Tentative Dimensions : TBD
Wiring Power wiring shall be done using Univyn cable. Sleeving shall be
done using high temperature imported sleeves ( withstanding
temperatures upto 135 deg C)
Control wiring shall bedone using suitably color coded Cu flexible
wires - 1.5 sq mm (control) / 2.5 sq mm ( CT circuit) Cu flexible
cables of reputed makes.
Item 3: 1000 KVAr 480 VAC RTPFC Panel Qty: 2 Nos.

Design System Specification 480 AC +/-10% Frequency: 60 Hz 3P3W Supply

Rated Output 1000 KVAr at 480 VAC


Rated Current : 1202.80 A at full load
Proposed Banking: 100 KVAR x 9, 50 KVAR x 2

Incomer 2000A TP 50KA MDO type ACB with Microprocessor Based LSIG
release for O/L, S/C and E/F
Indication R,Y,B, On,Off,Trip

Metering 3 Phase Digital Ammeter, Class 1, 96x96

Control Transformer 480/220 VAC control transformer of 2 KVA with MPCB/MCB


protection

APFC Controller 3CT Sensing Microprocessor based PFC Controller with 15/16 Steps,
LCD display, in-built data logger and RS-485 communication

Operation Auto

Capacitor MPP Dry Type Power Capacitor rated at 525 VAC with over pressure
disconnector
Reactor 7% De-tuned Harmonic Block Reactor, Cu wound, Class H insulation,
with thermal cutoff switch
Switching Thyristor Switching Modules consisting of 2200 PIV thyristors,snubber
firing cards and other accessories mounted on heat sink
Bank Protection HRC Fuse with Base
Cooling Forced cooling with heavy duty thermostat operated fans
Other Accessories AC Industrial Outlet, Panel Illumination Light for Control Compartment
Enclosure The Non-Compartmental, Floor Mounting Free Standing type
Enclosure shall be fabricated using 2/mm thick CRCA sheet duly
powder coated. Gland plate shall be fabricated using 3 mm thick
CRCA Sheet.
Tentative Dimensions: H: 2275 mm L/W: 2300 D: 900 mm
Wiring Power wiring shall be done using Univyn cable. Sleeving shall be
done using high temperature imported sleeves ( withstanding
temperatures up to 135 deg C)
Control wiring shall be done using suitably color coded Cu flexible
wires - 1.5 sq mm (control) / 2.5 sq mm (CT circuit) Cu flexible
cables of reputed makes.

You might also like