Professional Documents
Culture Documents
Technical Specifications
Technical Specifications
Technical Specifications
APFC Controller 3CT Sensing Microprocessor based PFC Controller with 8 Steps, LCD
display, in-built data logger and RS-485 communication
Operation Auto
Shunt Reactor 3 Phase Copper wound low loss shunt reactor with thermal cut-off
switch as per bank rating.
Switching
Thyristor Switching Modules consisting of 2200 PIV thyristors,snubber
firing cards and other accessories mounted on heat sink
Bank Protection HRC Fuse with Base
APFC Controller 3CT Sensing Microprocessor based PFC Controller with 8 Steps, LCD
display, in-built data logger and RS-485 communication
Operation Auto
Shunt Reactor 3 Phase Copper wound low loss shunt reactor with thermal cut off
swtich as per bank rating.
Switching
Thyristor Switching Modules consisting of 2200 PIV thyristors,snubber
firing cards and other accessories mounted on heat sink
Bank Protection HRC Fuse with Base
Incomer 2000A TP 50KA MDO type ACB with Microprocessor Based LSIG
release for O/L, S/C and E/F
Indication R,Y,B, On,Off,Trip
APFC Controller 3CT Sensing Microprocessor based PFC Controller with 15/16 Steps,
LCD display, in-built data logger and RS-485 communication
Operation Auto
Capacitor MPP Dry Type Power Capacitor rated at 525 VAC with over pressure
disconnector
Reactor 7% De-tuned Harmonic Block Reactor, Cu wound, Class H insulation,
with thermal cutoff switch
Switching Thyristor Switching Modules consisting of 2200 PIV thyristors,snubber
firing cards and other accessories mounted on heat sink
Bank Protection HRC Fuse with Base
Cooling Forced cooling with heavy duty thermostat operated fans
Other Accessories AC Industrial Outlet, Panel Illumination Light for Control Compartment
Enclosure The Non-Compartmental, Floor Mounting Free Standing type
Enclosure shall be fabricated using 2/mm thick CRCA sheet duly
powder coated. Gland plate shall be fabricated using 3 mm thick
CRCA Sheet.
Tentative Dimensions: H: 2275 mm L/W: 2300 D: 900 mm
Wiring Power wiring shall be done using Univyn cable. Sleeving shall be
done using high temperature imported sleeves ( withstanding
temperatures up to 135 deg C)
Control wiring shall be done using suitably color coded Cu flexible
wires - 1.5 sq mm (control) / 2.5 sq mm (CT circuit) Cu flexible
cables of reputed makes.