1. APPLICATION: ASH LEVEL MEASUREMENT IN SILO AND BUFFER HOPPERS.
2. TANK/VESSEL DETAILS: MATERIAL-MS(BUFFER HOPPER) & CONCRETE(SILO),SHAPE WHERE TRANSMITTER WOULD BE MOUNTED-CYLINDRICAL, HEIGHT OF TANK:8.3 MTR.(BUFFER HOPPER) & 17.7 MTR.(SILO),DIAMETER:3 MTR.(BUFFER HOPPER) & 12 MTR.(SILO) 3. DRAWING FOR SILO & BUFFER HOPPER IS ATTACHED. 4. MEASURING PRINCIPLE:PULSED RADAR / FMCW 5. OUTPUT:4-20mA,HART 6. MEASUREMENT DISTANCE: UP TO 20 MTRS. 7. ACCURACY: (+/-)2 MM OR (+/-) 0.1% OF MEASURED VALUE, WHICHEVER IS BETTER 8. RESOLUTION:2 MM OR BETTER 9. DEAD BAND(ZONE BELOW TOP REFERENCE POINT WITHIN WHICH MEASUREMENT CAN'T BE DONE): <= 400 MM 10. POWER SUPPLY:24 VDC 11. PROCESS TEMP:0 to 200 DEG C 12. PROCESS PRESSURE:(-)1 to 5 KG/CM2 13. PROCESS CONNECTION:THREADED 1.5 BSP 14. SLIP ON FLANGE:AIMING DEVICE DN 150/PP 15. SEAL:VITON 16. CABLE ENTRY:1/2" NPT 17. ANTENA TYPE & MATERIALS:HORN TYPE,SS 18. HOUSING MATERIAL:ALUMINIUM POLYURETHAN PAINTED 19. PROTECTION:IP 67 OR BETTER 20. DISPLAY:INTEGRAL,ALPHANUMERIC LCD,BACKLIGHT FOR READOUT 21. VOLTAGE SUPPLY AND DATA TRANSMISSION THROUGH THE SENSOR 22. PROGRAMMING (THROUGH KEYS OF TRANSMITTER)- INTEGRATED (ALL THE PARAMETERS SHALL BE COMPLETELY FIELD PROGRAMMABLE). NECESSARY PROVISION SHOULD BE INTEGRAL PART OF THE TRANSMITTER. 23. COUNTER FLANGE:1 ½” thread 25. REMOTE INDICATOR: ONE NO. WITH EACH TRANSMITTER. 26.SENSOR MEASURING SURFACE CLEANING: CLEANING PROVISION, WITHOUT DISTURBING THE MEASUREMENT, TO BE PROVIDED BY VENDOR 27. RETRANSMISSION OUTPUT-1:4-20 mA DC 28. RETRANSMISSION OUTPUT-2:4-20 mA DC 29. INDICATION ACCURACY:+/- 0.25% OF FSD 30. DISPLAY:S DIGIT 7 SEGMENT.25 MM HIGH