Professional Documents
Culture Documents
Draft Faulty - Broken Report PTS010 - SEMITAU
Draft Faulty - Broken Report PTS010 - SEMITAU
INCIDENT CHRONOLOGY
TELKOMSEL (describe
MANAGE chronology
SERVICE incident based on
PROJECT
real condition)
FAULTY/BROKEN/STOLEN REPORT
I. SITE INFORMATION
A. Site ID :PTS010
B. SITE NAME :SEMITAU
C. REGION :R08_KALIMANTAN
D. NOP :PONTIANAK
Date/Time Description
Team Pengecekkan Genset ke Site PTS010_SEMITAU
1. Pengecekan Battery Starter
>> Battery starter tidak ada
>> photo taken
2. Pengecekan Radiator
>> Perlu penggantian air radiator
>> photo taken
3. Pengecekan Oli & Filter
>> Perlu dilakukan penggantian oli,filter oli,filter solar & filter udara
24-05-2024/10.00
19 >> photo taken
4. Pengecekan Elektrikal Genset
>> Perlu penggantian module genset,wiring elektrikal genset
>> photo taken
5. Pengecekan Engine
>> Test running genset ok,tegangan dan frekuensi normal hanya saja genset sudah lama tidak aktif apabila akan di
relokasi ke site dengan main power genset disarankan melakukan TOP Overhoul
6. Pengecekan ATS
>> ATS ok (New Panel ATS support AMF & CDC)
>> photo taken
19-04-2024/10:30 Team made faulty/broken report
22-04-2024/18.00 Team submit to RTS
V. EVIDENCE
1 Name Plate
3 Accu N/A
Page 2 of 5
5 Panel ATS
7 Module Genset
Page 3 of 5
N
Rectification Request Qty Remark
O
Page 4 of 5
N
Rectification Request Qty Remark
O
NOTE
Page 5 of 5