Professional Documents
Culture Documents
Risk Assessment Sheet
Risk Assessment Sheet
Abbreviations:
Building Dimensions:
Length(L) (m): 30.0 Width(W) (m): 40.0 Height(H) (m): 6.0
Rectangular structure
Ae = LW + 6H(L+W) + π 9 H2
Ae = 4737.4 m2
C1 = 0.50
Reference : http://www.nasa.gov/centers/goddard/news/topstory/2004/0621lightning_prt.htm
Nd = 0.0118 event/year .
Roof Material
(ECG) ENGINEERING CONSULTANTS GROUP Rev. 0
C2 = 1.0
C3 Structure Contents
0.5 Low value and noncombustible.
1.0 Standard value and noncombustible.
2.0 High value, moderate combustibility.
3.0 Exceptional value, flammable liquids, computer or electronics.
4.0 Exceptional value, irreplaceable cultural items.
C3 = 3.0
C4 Structure Occupancy
0.5 Unoccupied.
1.0 Normally Occupied.
3.0 Difficult to evacuate or risk of panic.
C4 = 1.0
C5 Lightning Consequence
1.0 Continuity of facility services not required, no environmental impact.
5.0 Continuity of facility services required, no environmental impact.
(ECG) ENGINEERING CONSULTANTS GROUP Rev. 0
C5 = 5.0
1.5 x 10 -3
Nc =
(C2)(C3)(C4)(C5)
Nc = 0.0001 event/year
Risk Calculation:
Accordingly,
Should Be Installed
(ECG) ENGINEERING CONSULTANTS GROUP Rev. 0