Msa 18 VDK 1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

Revision C:

• Another type of the electronic control P.C.


board (TYPE 2) has been added to the
SPLIT-TYPE AIR CONDITIONERS original one (TYPE 1). They are both com-
patible with MS-A18/24/30VD- K .
Please void OB400, REVISED EDITION-B.

INDOOR UNIT
No. OB400
SERVICE MANUAL REVISED EDITION-C

Models

MS-A18VD- K1

MS-A18VD- K2

MS-A24VD- K1

MS-A24VD- K2

MS-A30VD- K1

MS-A30VD- K2

Outdoor unit service manual


MU-A·VD Series (OB401)

CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. OUTLINES AND DIMENSIONS ·························6
MS-A18VD
MS-A24VD 5. WIRING DIAGRAM ············································7
MS-A30VD 6. REFRIGERANT SYSTEM DIAGRAM ················9
7. SERVICE FUNCTIONS ····································10
8. TROUBLESHOOTING······································12
9. DISASSEMBLY INSTRUCTIONS ····················21
10. PARTS LIST······················································23
11. RoHS PARTS LIST···········································26
NOTE:
• This service manual describes technical data of the indoor units.
• RoHS compliant products have <G> mark on the spec name plate.
For servicing of RoHS compliant products, refer to the RoHS Parts List.
TM

Downloaded from www.Manualslib.com manuals search engine


Use the specified refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by
failure to follow the instructions.

Revision A:
• MS-A18VD- K2 , MS-A24VD- K2 and MS-A30VD- K2 have been added.

Revision B:
• Remote controller model “KM04B” has been added.
There are two remote controller models for “ K1 ” and “ K2 ”. (KP0B, KM04B)
You can use the remote controller model “KP0B” and “KM04B”.
The remote controller model “KM04B” is supplied as service parts for “ K1 ” and “ K2 ”.

Revision C:
• Another type of the electronic control P.C. board (TYPE 2) has been added to the original one (TYPE 1). They are both com-
patible with MS-A18/24/30VD- K .

1 TECHNICAL CHANGES
w : change
Frequency 50Hz
New Model MS-A18VD - K1
Old Model MS-18NV - KB MS-18UV - P1 MS-18RV - R1
Indoor unit:Unit size:W1,015mmoH320mmoD190mm ➞ W1,100mmoH325mmoD258mm w w w
Electricity receiving unit: Indoor unit ➞ Outdoor unit w w
Rated voltage : 220/240V ➞ 220-230-240V w

Frequency 50Hz
New Model MS-A24VD - K1
Old Model MS-24NV - K1 MS-24UV - P1 MS-24RV - R1
Indoor unit:Unit size:W1,015mmoH320mmoD190mm ➞ W1,100mmoH325mmoD258mm w w w
Electricity receiving unit: Indoor unit ➞ Outdoor unit w w
Rated voltage : 220/240V ➞ 220-230-240V w

Frequency 50Hz
New Model MS-A30VD - K1
Old Model MS-30SV - K1 MS-30SV - P1
Indoor unit:Unit size:W1,100mmoH325mmoD227mm ➞ W1,100mmoH325mmoD258mm w w
Rated voltage : 220/240V ➞ 220-230-240V w

MS-A18VD - K1 ➔ MS-A18VD - K2
MS-A24VD - K1 ➔ MS-A24VD - K2
MS-A30VD - K1 ➔ MS-A30VD - K2

1. Fan guard has been added.


2. Fan speed has been changed.
3. Wiring diagram has been changed.
4. FUSE (F12) has been removed. (MS-A18/24VD- K2 )
5. “8-5.C Check of indoor electronic control P.C. board” has been changed.

OB400C 2

Downloaded from www.Manualslib.com manuals search engine


2 PART NAMES AND FUNCTIONS

INDOOR UNIT
MS-A18VD
MS-A24VD
MS-A30VD
Air cleaning filter Grille
(White bellows type)
Air inlet

Front Panel

Catechin air filter


Remote control
receiving section
Vertical vanes
Horizontal vane

Remote controller

Operation section Display section


(When the grille is opened) Operation indicator lamp

Emergency operation switch


Remote control
receiving section

OB400C 3

Downloaded from www.Manualslib.com manuals search engine


ACCESSORIES

1 Installation plate 1
2 Installation plate fixing screw 4 x 25 mm 7
3 Remote controller holder 1
4 Fixing screw for 3 3.5 x 16 mm (Black) 2
5 Battery (AAA) for remote controller 2
6 Wireless remote controller 1
7 Felt tape (Used for left or left-rear piping) 1
8 Air cleaning filter 2
9 Pipe cover

REMOTE CONTROLLER

MS-A18VD
MS-A24VD
Signal transmitting section
MS-A30VD

Operation display section PM

AM
OPERATE/ STOP
(ON/ OFF)button TOO
ON/OFF WARM TOO
COOL

TEMPERATURE buttons

Open the front lid.


Indication of remote controller
model is on back.

CLOCK
PM

AM

TOO
ON/OFF WARM TOO
COOL

VANE button FAN SPEED CONTROL button


(Horizontal vane button) FAN STOP
I FEEL COOL
OFF-TIMER button
VANE START
FAN DRY
ON-TIMER button
MODE WIDE VANE HR.
HR. button
OPERATION SELECT button
ECONO COOL LONG MIN. MIN. button
ECONO COOL button (TIME SET button)
RESET CLOCK

WIDE VANE button CLOCK SET button


(Vertical vane button) LONG button
RESET button

OB400C 4

Downloaded from www.Manualslib.com manuals search engine


3 SPECIFICATION

Indoor model MS-A18VD - K1 MS-A18VD - K2 MS-A24VD - K1 MS-A24VD - K2 MS-A30VD - K1 MS-A30VD - K2

Function Cooling
Single phase
Power supply
220-230-240V, 50Hz
Capacity Air flow (High/Med./Low) K /h 774/660/552 972/828/684
Running current A 0.30-0.30-0.31 0.33-0.34-0.35
Electrical

Power input W 60-60-64 67-69-75


Auxiliary heater A(kW) — —
data

Power factor % 91-87-86 92-88-89


Fan motor current A 0.30-0.30-0.31 0.33-0.34-0.35
Model RC4V32-AA RC4V40-AA
motor
Fan

Winding WHT-BLK 293.0 WHT-BLK 138.2


"
resistance(at 20:) RED-BLK 146.0 RED-BLK 159.0
Dimensions WOHOD mm 1,100O325O258
Weight kg 16
Air direction 5
Sound level (High/Med./Low) dB 42/37/33 45/41/37
remarks
Special

Fan speed (High/Med./Low) rpm 1,010/880/760 1,070/920/780 1,220/1,070/910 1,280/1,130/970 1,220/1,070/910 1,280/1,130/970
Fan speed regulator 3
Thermistor RT11(at 25:) k" 10
Thermistor RT12(at 25:) k" 10
Thermistor RT13(at 25:) k" — 10
Remote controller model KP0B / KM04B
NOTE:Test conditions are based on ISO 5151.
Cooling : Indoor Dry-bulb temperature 27: Wet-bulb temperature 19:
Outdoor Dry-bulb temperature 35: Wet-bulb temperature 24:
Indoor-Outdoor piping length : 5 m

OB400C 5

Downloaded from www.Manualslib.com manuals search engine


4 OUTLINES AND DIMENSIONS

MS-A18VD MS-A24VD MS-A30VD


Unit: mm
INDOOR UNIT

Installation plate Indoor unit


98 173

7.5
1068

255.5
315
47

2.5
47
98 414.5 414.5 173

Wall hole [75


{
Liquid line [ 6.35- 0.5m
258 5 Gas line [ 12-0.43m
Insulation [ 50 O.D
1100 Air in [ 32 I.D
Installation plate
for MS-A18VD
for MS-A24VD

{
Liquid line [ 9.52- 0.5m
325

Gas line [ 16-0.43m


Insulation [ 50 O.D
[ 32 I.D
for MS-A30VD
56 791 253 Drain hose [16
Air out (Connected part O.D)
58 19 Insulation [28
162

Wireless remote controller

OB400C 6

Downloaded from www.Manualslib.com manuals search engine


5 WIRING DIAGRAM

MS-A18VD - K1 MS-A24VD - K1
INDOOR UNIT
CN
112 RT12
TO OUTDOOR
UNIT HIC1 CN
CONNECTING CN201 111 RT11
TB 3 3
2 WHT F12 BLU BLK
2 52C/
220-230-240V~ 1 X11 CN 3 GRY
BLU BLU NR11
2 1 4 121
N YLW
BLU
220-230-240V~ 1 BRN MF
C11
WHT
L BRN F11 SR141 3
RED
4
CN211
CN CN CN
ELECTRONIC CONTROL P.C. BOARD
GRN/YLW

151 102 101

15
3 3

MV2 MV2 MV1 DISPLAY RECEIVER


P.C. BOARD P.C. BOARD

REMOTE
CONTROLLER

SYMBOL NAME SYMBOL NAME SYMBOL NAME


C11 INDOOR FAN CAPACITOR MV1 HORIZONTAL VANE MOTOR SR141 SOLID STATE RELAY
F11 FUSE(3.15A) MV2 VERTICAL VANE MOTOR TB TERMINAL BLOCK
F12 THERMAL FUSE (93:) NR11 VARISTOR 52C/X11 COMPRESSOR CONTACTOR
HIC1 DC/DC CONVERTER RT11 ROOM TEMPERATURE THERMISTOR
MF INDOOR FAN MOTOR(INNER PROTECTOR) RT12 INDOOR COIL THERMISTOR
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector

MS-A18VD - K2 MS-A24VD - K2
INDOOR UNIT
CN
112 RT12
TO OUTDOOR
UNIT HIC1 CN
CONNECTING 111 RT11
TB CN201 3
2 WHT BLK
220-230-240V~ 3 X11 CN 3 GRY
NR11
2 4 121
N YLW
BLU
220-230-240V~ 1
1 BRN MF
C11
WHT
L BRN F11 SR141 3
RED
4
CN211
CN CN CN
ELECTRONIC CONTROL P.C. BOARD
GRN/YLW

151 102 101

15
3 3

MV2 MV2 MV1 DISPLAY RECEIVER


P.C. BOARD P.C. BOARD

REMOTE
CONTROLLER

SYMBOL NAME SYMBOL NAME SYMBOL NAME


C11 INDOOR FAN CAPACITOR MV2 VERTICAL VANE MOTOR TB TERMINAL BLOCK
F11 FUSE(T3.15AL250V) NR11 VARISTOR X11 CONTACTOR
HIC1 DC/DC CONVERTER RT11 ROOM TEMPERATURE THERMISTOR
MF INDOOR FAN MOTOR(INNER PROTECTOR) RT12 INDOOR COIL THERMISTOR
MV1 HORIZONTAL VANE MOTOR SR141 SOLID STATE RELAY
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector

OB400C 7

Downloaded from www.Manualslib.com manuals search engine


MS-A30VD
INDOOR UNIT
4
RT13
3
TO OUTDOOR HIC1 2
UNIT RT12
CONNECTING 1
TB CN201 CN112 BLK
12V 3 RED
3 NR11 CN 3 GRY
121 YLW
2
N BLU BRN MF
1 1
C11
WHT
220-230-240V~ 2 TAB12 F11 SR141 3
BRN RED
4
CN211
CN CN CN CN
151 102 101 ELECTRONIC CONTROL P.C. BOARD 111 RT11
GRN/YLW

15
3 3

MV2 MV2 MV1 DISPLAY RECEIVER


P.C. BOARD P.C. BOARD

REMOTE
CONTROLLER

SYMBOL NAME SYMBOL NAME SYMBOL NAME


C11 INDOOR FAN CAPACITOR MV2 VERTICAL VANE MOTOR SR141 SOLID STATE RELAY
F11 FUSE (T3.15AL250V) NR11 VARISTOR TB TERMINAL BLOCK
HIC1 DC/DC CONVERTER RT11 ROOM TEMPERATURE THERMISTOR
MF INDOOR FAN MOTOR (INNER PROTECTOR) RT12 INDOOR COIL THERMISTOR (MAIN)
MV1 HORIZONTAL VANE MOTOR RT13 INDOOR COIL THERMISTOR (SUB)
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector

OB400C 8

Downloaded from www.Manualslib.com manuals search engine


6 REFRIGERANT SYSTEM DIAGRAM

MS-A18VD Unit : mm

INDOOR UNIT
Refrigerant pipe
[12.7
(with heat insulator)

Indoor Indoor coil


heat thermistor
exchanger RT12 Flared connection

Distributor
RT11
Room
temperature
thermistor

Strainer
#50 Flared connection

Refrigerant pipe
[6.35
(with heat insulator)

MS-A24VD MS-A30VD
INDOOR UNIT Refrigerant pipe
INDOOR UNIT Refrigerant pipe
[15.88 [15.88
(with heat insulator) (with heat insulator)

Indoor Indoor coil Indoor Indoor coil


heat thermistor heat thermistor
exchanger RT12 Flared connection exchanger RT12 (main) Flared connection

Indoor coil
thermistor
RT13 (sub)

Room temperature Room temperature


thermistor thermistor
RT11 RT11

Strainer Strainer
#50 #50
Flared connection Flared connection

Refrigerant pipe Refrigerant pipe


[6.35 [9.52
(with heat insulator) (with heat insulator)

Refrigerant flow in cooling

OB400C 9

Downloaded from www.Manualslib.com manuals search engine


7 SERVICE FUNCTIONS

MS-A18VD
MS-A24VD
MS-A30VD
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board.
The time will be shortened as follows. (Refer to 8-6.)
Set time : 1-minute ➔ 1-second
Set time : 3-minute ➔ 3-second
It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short
circuit of JPG and JPS.
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :

Remote controller model : KP0B


J2
NOTE : For modification, take out the
batteries and press the
OPERATE/STOP(ON/OFF)
button twice or 3 times at first.
After finish modification, put
back the batteries then press
the RESET button.

J1

Remote controller model : KM04B

J1 J2
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.

OB400C 10

Downloaded from www.Manualslib.com manuals search engine


Table 1
1 unit operation 2 units operation 3 units operation 4 units operation
No. 1 unit No modification Same as at left Same as at left Same as at left
No. 2 unit – Solder J1 Same as at left Same as at left
No. 3 unit – – Solder J2 Same as at left
No. 4 unit – – – Solder both J1 and J2
How to set the remote controller exclusively for particular indoor unit.
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote
controller for the indoor unit.
The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are
set.
The setting will be cancelled if the breaker has turned off, or the power supply has shut down.
Please conduct the above setting once again after the power has restored.
7-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are
memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment
power has restored after power failure. Then, the unit will restart automatically. However if the unit is operated in “I FEEL
CONTROL” mode before power failure, the operation is not memorized. In “I FEEL CONTROL” mode, the operation is
decided by the initial room temperature.
How to disable “AUTO RESTART FUNCTION”
1Turn off the main power for the unit.
2Pull out the indoor electronic control P.C. board and the display P.C. board.(Refer to 9-1.2.)
3Solder the Jumper wire or the RESISTOR 220" to the RESISTOR JR07 on the indoor electronic control P.C.board.
(Refer to 8-6.)

Operation
1If the main power has been cut, the operation settings remain.
2After the power is restored, the unit automatically resumes the same operation as the memory has recorded.
However, it takes the compressor at least 3 minutes to get started.
NOTE:
•The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
•If the main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
•If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
•To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same
time.
•When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.

OB400C 11

Downloaded from www.Manualslib.com manuals search engine


8 TROUBLESHOOTING

MS-A18VD
MS-A24VD
MS-A30VD
8-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after confirm-
ing the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel and the electronic
control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.

<Incorrect> <Correct>

Lead wiring Housing point

3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service
work.
2) Before servicing that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discolouration.
4) When troubleshooting, refer to 8-2. and 8-3.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries. 2 Press the RESET button with a thin instrument,
Then reattach the front lid. and then use the remote controller.

Insert the negative pole


of the batteries first.
Check if the polarity of
the batteries is correct.
RESET button

NOTE: 1. If the RESET button is not pressed, the remote controller may not operate correctly.
2. Do not use the leaking batteries.

OB400C 12

Downloaded from www.Manualslib.com manuals search engine


8-2. Instruction of troubleshooting

Start

Indoor unit Indoor unit


operates. Indoor unit
operates. OPERATION INDICATOR
Outdoor unit does not receive
Outdoor unit lamp on the indoor unit is
does not operate the signal from
does not flashing on and off.
normally. remote controller.
operate.

Outdoor unit MU-A30VD MU-A24VD-K2 MU-A30VD


operates Outdoor unit MU-A30VD Outdoor unit Indoor unit Indoor unit
in only Test does not operate Outdoor unit repeats start operates when does not operate
Run operation. even in Test does not and stop. EMERGENCY when
w Run operation. stop even OPERATION EMERGENCY
w if indoor unit switch is pressed. OPERATION
stop. switch is pressed.

1. Check indoor /
Check room outdoor
temperature Refer to 8-5. B connecting wire.
thermistor. Refer to Refer to Refer to "Check of 2. Check of outdoor
Refer to 8-6. "Check of "Check of "Check of remote controller fuse.
outdoor unit". solenoid (MU-A18/A24VD )
"Test point outdoor unit". and receiver 3. Refer to 8-5. C
diagram and valve coil". P.C. board". "Check of indoor
voltage". electronic control
P.C. board".

MS-A30VD 2-time flash 3-time flash 4-time flash MU-A30VD MU-A30VD MU-A30VD
Flash on and Cause: Cause: Cause: 6-time flash 7-time flash 10-time flash
off at 0.5-second Indoor unit Indoor unit Indoor unit Cause: Cause: Cause:
intervals • Trouble of • Trouble of • Trouble of Outdoor unit Outdoor unit Outdoor unit
Cause: room temp- indoor fan indoor • Trouble of • Trouble of • Trouble of
erature/
Indoor/ motor control thermistor outdoor low discharge
indoor coil
Outdoor unit thermistor system in outdoor control temperature
• Mis-wiring unit system protection

Check room
Refer to temperature
8-5. D thermistor
"How to and indoor Refer to Replace the
Refer to
check coil thermis- 8-5. A indoor Replace the Refer to
tor. "Check of
mis-wiring "Check of electronic deicer "Check of
Refer to 8-6. outdoor
(When indoor fan control P.C. board. LEV".
"Test point thermistor".
outdoor unit motor". P.C. board.
does not work)". diagram and
voltage".

Refer to outdoor unit service manual.


w "Test Run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.

OB400C 13

Downloaded from www.Manualslib.com manuals search engine


8-3. Troubleshooting check table
• Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and the following detection method has detected an abnormality
(the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor
with the OPERATION INDICATOR lamp flashing.
· Flashing of the OPERATION INDICATOR lamp (the left-hand side lamp) indicates
Operation Indicator Lighted possible abnormalities.
· The OPERATION INDICATOR lamp (the left-hand side lamp) is lighting during
Not lighted normal operation.

Abnormal
No. Indication Symptom Condition Remedy
point
0.5-second ON 3 minutes after power supply turns ON, when • Refer to 8-5. D "How to check
Outdoor unit serial signal is not received. mis-wiring ".
1 Mis-Wiring does not
operate.
MS-A30VD 0.5-second OFF

• Refer to the characteristics of


Detect Indoor coil/room temperature indoor coil thermistor,
Indoor coil
2-time flash thermistor short or open circuit every 8 sub indoor coil thermistor,
thermistor
Outdoor unit seconds during operation. and room temperature
2 does not thermistor on 8-6.
Room operate.
tempera- 2.5-second OFF
ture
thermistor
Indoor fan • Refer to 8-5. A "Check of
motor repeats Rotational frequency feedback signal is not indoor fan motor".
12 seconds emitting during 12-second indoor fan
ON and 3 operation.
3-time flash
Indoor fan minutes OFF.
3 motor. When the
indoor fan
2.5-second OFF motor breaks,
the fan keeps
stopping.

4-time flash Nonvolatile memory data cannot be read • Replace the indoor electronic
Indoor Outdoor unit properly on indoor electronic control P.C. control P.C. board.
4 control does not board.
system operate.
2.5-second OFF

<Thermistor short> • Shortage of refrigerant


Thermistors are abnormal when they short • Replace the deicer P.C.
6-time flash after compressor start-up. board.
<Thermistor open> Refer to "Check of outdoor
Outdoor Outdoor unit
5 Thermistors are abnormal when they open thermistor".
thermistors does not
after compressor start-up. Refer to outdoor unit service
operate.
MU-A30VD 2.5-second OFF However, discharge temperature thermistor is manual.
abnormal when open circuit is detected more
than 10 minutes after compressor start-up.

7-time flash Nonvolatile memory data cannot be read • Replace the deicer P.C.
Outdoor Outdoor unit properly on deicer P.C. board. board.
6 control does not Refer to outdoor unit service
system operate. manual.
MU-A30VD 2.5-second OFF

10-time flash Discharge temperature has been 50: or less • Refer to "Check of LEV".
for 20 minutes. • Check refrigerant circuit and
Low
Outdoor unit refrigerant amount.
discharge
7 temperature does not Refer to outdoor unit service
operate. manual.
protection
MU-A30VD 2.5-second OFF

OB400C 14

Downloaded from www.Manualslib.com manuals search engine


8-4. Trouble criterion of main parts
MS-A18VD
MS-A24VD
MS-A30VD

Part name Check method and criterion Figure


Room
temperature Measure the resistance with a tester.
thermistor (RT11) (Part temperature 10°C ~ 30°C)
Indoor coil Refer to 8-6. “Test point diagram and voltage”, “Indoor electronic control P.C.
thermistor board”, for the chart of thermistor.
(RT12(main), RT13(sub))
Measure the resistance between the terminals with a tester.
(Coil wiring temperature10°C ~ 30°C)
Motor part

Indoor fan Normal


Color of lead wire
motor (MF) MS-A18VD MS-A24/30VD
WHT - BLK 282 ~ 304 " 132 ~ 144 " MAIN

INNER AUX.
BLK - RED 141 ~ 152 " 152 ~ 166 "
PROTECTOR
135i 5: OPEN Measure the voltage Power ON.
86i15: CLOSE
Sensor part

Color of lead wire Normal BLK REDWHT

BRN - YLW 4.5 ~ 5.5 V


(When fan revolved one time)
YLW - GRY 0V➔5V➔0V
(Approx.)

Measure the resistance between the RED terminals and other ones.
PNK
Horizontal vane (Winding temperature10°C ~ 30°C) ROTOR

motor(MV1)
Vertical vane Normal ORN
RED
motor(MV2) 282 ~ 306 "
YLW BLU

P:INNER PROTECTOR

OB400C 15

Downloaded from www.Manualslib.com manuals search engine


8-5. Troubleshooting flow
When OPERATION INDICATOR lamp flashes 3-time.
Indoor fan motor does not operate.
Turn OFF the power supply.
A Check of indoor fan motor Check connector CN211 visually.

No No
Yes Is soldered point of the connector
Are lead wires connected?
correctly soldered?

Yes
Reconnect the lead wires. Resolder it.

Disconnect lead wires from connector CN211 on the indoor electronic control P.C. board.
Measure resistance between lead wires No.1 and No.4 and then No.3 and No.4.

Turn ON the power supply.


Stop it if the unit operate. Insert screwdriver into
Is resistance 0 (short circuit) or ∞ (open circuit)? air outlet to rotate indoor fan motor slowly for 1
No revolution or over, and measure voltage No.2(+)
Yes ( 0 or ∞ ) (others) and No.3(-) on CN121.

Repair the indoor fan motor. No


Does voltage repeat 0 VDC and 5 VDC?

Yes

Replace the indoor electronic control P.C. board.

Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote controller.

B Check of remote controller and receiver P.C. board


w Check if the remote controller is exclusive for this air conditioner.
Switch on the remote controller.

Is LCD display on the remote con- No Replace the batteries


troller visible? (Refer to 8-1.4.).
(not clear)
Yes

Remove batteries, then set them back and


press the RESET button.
Check if the unit operates with remote con-
troller.

No
Does the unit operate with remote Turn on a radio to AM and press switch on
controller? the remote controller.

Yes
No
Is noise heard from radio? Replace the remote controller.
OK

Yes

Are there any fluorescent lights of Yes ● Reinstall the unit away from lights.
inverter or rapid-start type within the ● Attach a filter on receiving part.
range of 1m?
No

Measure the voltage between receiver P.C. board connector CN301 No.1(+) and No.3(-) when
the remote controller button is pressed (Refer to 8-6.).

Yes Replace the indoor electronic control


Is the voltage approximately 4 VDC?
P.C. board

No (5V or 0 VDC)

Replace the receiver P.C.board.

OB400C 16

Downloaded from www.Manualslib.com manuals search engine


The unit does not operate with the remote controller.
Also, the OPERATION INDICATOR lamp does not light up by pressing the EMERGENCY OPERATION switch.

C Check of indoor electronic control P.C. board

Check both “parts side” and “pattern


side” of the indoor electronic control P.C.
board visually.

Turn OFF the power supply.


Remove indoor fan motor connector CN211 and
vane motor connector CN151 from the indoor electronic
control P.C. board and turn ON the power supply.

Does the unit operate with the remote controller?


No
Does the OPERATION INDICATOR lamp light up by
pressing the EMERGENCY OPERATION switch?

Yes Varistor (NR11)


Terminal
Turn OFF the Replace the vane Turn OFF the Indoor electronic block
power supply. power supply. control P.C. board
motor. 2
N
Yes 3 L
F12
Is the winding 2 1
Fuse (F11)
resistance of 1 2
vane motor 0 "? Replace the fuse. CN201
Indoor electronic
No control P.C. board
Yes
Is the winding
resistance of Is fuse(F11) blown?
fan motor 0 "? No MS-A18/24VD - K2 Replace the indoor
No MS-A30VD
Yes electronic control
P.C. board.
MS-A18/24VD - K1
Replace the fan Measure the
No
motor. Is varistor(NR11) burnt? resistance Yes
between
CN201 1 on Is resistance
Yes
the indoor approximately 0"?
electronic control
No (∞)
Replace the varistor. P.C. board and N
on the terminal
block with a tester. Replace the fuse (F12).

OB400C 17

Downloaded from www.Manualslib.com manuals search engine


When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
Outdoor unit does not operate.

D How to check mis-wiring MS-A30VD

w Short circuit of JPG and JPS on the indoor electronic control


P.C. board enables self-check to be displayed in 3 seconds.

Start

• Turn ON the power supply.


• Press EMERGENCY OPERATION switch once.

When the unit has mis-wiring, in 3 minutes,


OPERATION INDICATOR lamp on indoor unit
flash on and off at 0.5 second intervals. w

Yes Is this mis-wiring, poor contact,


Make them sure.
or wire disconnection?
No

1. Turn OFF the power supply and disconnect only terminal block 3 of indoor/ outdoor
connecting wire on indoor side.
2. Short-circuit terminal block N-3 by lead wire.
3. Turn ON the power supply and press EMERGENCY OPERATION switch once.

Is there 1V DC detected between both ends


of PS132 on the indoor electronic control P.C. No Replace the indoor electronic
board ?
However, the stylus of a tester would be control P.C. board.
between 0 and 20V.
Yes
• Turn OFF the power supply.
• Disconnect the lead wire that terminal
block N-3 is short-circuited.
• Connect ON indoor/ outdoor connecting wire.

Turn ON the power supply.

Is there 220-230-240V AC between L-N No Check the outdoor power supply


on the outdoor terminal block? and connection of wiring.
Yes
No
Is there 5V DC between J101 + -J401 - ? Replace the deicer P.C. board.

Yes

When EMERGENCY OPERATION


is operated, is there 10V DC between both No Make the wiring between CN730
ends of R601 on the deicer P.C. board? on the deicer P.C. board and
However the stylus of a tester would be outdoor terminal block correct.
between 5 ~10V.
Yes

Replace the deicer P.C. board.

Refer to outdoor unit service manual .

OB400C 18

Downloaded from www.Manualslib.com manuals search engine


8-6. Test point diagram and voltage
w There are 2 types of electronic control P.C. boards
MS-A18VD MS-A24VD MS-A30VD (TYPE1/TYPE2).
Indoor electronic control P.C.board They are both compatible with MS-A18/24/30VD.
Varistor (NR11)
TYPE 1

Fan motor power supply


220-230-240 VAC(CN211)

} Power supply input


220-230-240 VAC

+
} 5 VDC
Room temperature
Fuse (F11) thermistor (RT11)
T3.5AL250V Indoor coil
thermistor (RT12 (main))
MS-A30VD
Indoor coil
PS132 thermistor (RT13 (sub))
MS-A30VD
CN121

Vane motor
power supply
(CN151)

Emergency operation
switch
Timer short mode point
(JPS, JPG)
(Refer to 7-1.)

Receiver P.C. board


+
}

12 VDC
Indoor coil thermistor
(RT12 (main), RT13 (sub))
Room temperature thermistor (RT11)

CN301 To disable “Auto restart function”,


solder the Jumper wire or the
Resistance (k")

Resistor 220" to the Resistor


JR07. (Refer to 7-3.)

Temperature (:)
OB400C 19

Downloaded from www.Manualslib.com manuals search engine


MS-A18VD MS-A24VD MS-A30VD
Indoor electronic control P.C.board

TYPE 2

Fan motor power supply


(CN211)

} Power supply input


220-230-240 VAC

Fuse (F11) +
T3.15AL250V } 5 VDC
PS132
MS-A30VD
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12 (main))
MS-A30VD
Indoor coil thermistor
+ (RT13 (sub))
12 VDC {
CN121

Vane motor
power supply
To disable “Auto restart (CN151)
function”, solder jumper
wire to JR07. Emergency
(Refer to 7-3.) operation
switch
Timer short
mode point
(JPS, JPG)
(Refer to 7-1.)

Indoor coil thermistor


(RT12 (main), RT13 (sub))
Room temperature thermistor (RT11)
Receiver P.C. board
Resistance (k )

CN301

OB400C 20

Downloaded from www.Manualslib.com manuals search engine


9 DISASSEMBLY INSTRUCTIONS

<"Terminal with locking mechanism" Detaching points>


The terminal which has the locking mechanism can be detached as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.

(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
Sleeve

1Slide the sleeve. 1Hold the sleeve, and


2Pull the terminal while pull out the terminal
Locking lever pushing the locking slowly.
lever.
Connector

9-1. MS-A18VD MS-A24VD MS-A30VD


NOTE: Turn OFF power supply before disassembly.

OPERATING PROCEDURE PHOTOS


1. Removing the front panel Photo 1
(1) Remove the screws caps of the front panel.
Front panel
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.

Screws

2. Removing the electronic control P.C. board, the receiver Photo 2


P.C. board and the display P.C. board Screws of the ground wire
(1) Remove the front panel. (Refer to 1.)
(2) Remove the screw of the electrical cover.
Remove the electrical cover.
(3) Remove the screw of the V.A. clamp.
Remove the V.A. clamp. Fan motor
(4) Remove the screw of the terminal block. connectors
(5) Remove the screw of the ground wire.
(6) Disconnect all the connectors and all the lead wires on the Vane motor
electronic control P.C. board. connector
(7) Remove the R.L holder. Indoor
(8) Remove the electronic control P.C. board. electronic
(9) Open the R.L holder, remove the receiver P.C. board and control
the display P.C. board. P.C.board
Screw of
the electrical
cover
Screw of R.L Receiver Screw of the
the terminal holder P.C. V.A. clamp
block board

OB400C 21

Downloaded from www.Manualslib.com manuals search engine


OPERATING PROCEDURE PHOTOS
3. Removing the electrical box Photo 3 Screws of the ground wire
(1) Remove the front panel. (Refer to 1.)
(2) Remove the electrical cover. (Refer to 2.)
(3) Disconnect the connector of the indoor coil thermistor.
(4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic
control P.C. board. Screw of the
(5) Remove the screw of ground wire. electrical cover
(6) Remove the fan motor lead wire and indoor coil thermistor Screw of the
from the electrical box. electrical box
(7) Remove the lead wire of vane motor from the bottom of
electrical box.
(8) Remove the screw fixing the electrical box, remove the
electrical box.

4. Removing the vane motor Photo 4


(1) Remove the front panel. (Refer to 1.)
Vane motors Screws
(2) Remove the electrical cover. (Refer to 2.)
(3) Remove the lead wire of vane motor.(Refer to 3.) of the
(4) Remove the R.L. holder. vane
(5) Pull out the drain hose from the nozzle assembly, remove motor
the nozzle assembly.
(6) Remove the screws of the vane motor, disconnect the con-
nector.
(7) Remove the vane motor.
Photo 5 Screws of the
vane motor

Vane motor

5. Removing the line flow fan and the indoor fan motor
Photo 6
(1) Remove the front panel. (Refer to 1.)
(2) Remove the electrical box. (Refer to 3.)
(3) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly.
(4) Remove the water cut. Screws fixing
(5) Slide the hole cover, remove the hole cover. the left side
(6) Remove the hexagon socket set screw from the line flow of the heat
fan. exchanger
(7) Remove the fan motor after removing screws, which fasten
the motor, but be careful not to drop it because of its heavy
weight. Photo 7
(8) Remove the screws fixing the left side of the heat Indoor
exchanger. coil
(9) Lifting the left side of the heat exchanger. thermistor
(10) Remove the line flow fan.

Photo 8
Water cut
Hole
cover

Screws fixing the fan motor

OB400C 22

Downloaded from www.Manualslib.com manuals search engine


10 PARTS LIST (non-RoHS compliant)

MS-A18VD MS-A24VD MS-A30VD


10-1. INDOOR UNIT STRUCTURAL PARTS 10-2. INDOOR UNIT HEAT EXCHANGER

2
11
3

4
CATCH 12
7 9
5
SCREW
(See 10-5.)
CAP
13

10-1. INDOOR UNIT STRUCTURAL PARTS


Part number that is circled is not shown in the illustration.
Symbol Q'ty/unit
No. Part No. Part name in WiringMS-A18 MS-A18 MS-A24 MS-A24 MS-A30 MS-A30 Remarks
Diagram VD- K1 VD- K2 VD- K1 VD- K2 VD- K1 VD- K2
1 E02 527 970 INSTALLATION PLATE 1 1 1 1 1 1
2 E02 685 234 BOX 1 1 1 1 1 1
3 E02 888 000 FRONT PANEL ASSEMBLY 1 1 1 1 1 1 Including No.4,5,6
4 E02 408 142 CATCH 4 4 4 4 4 4 4PCS/SET
5 E02 685 067 SCREW CAP 3 3 3 3 3 3 3PCS/SET
6 E02 888 010 GRILLE 1 1 1 1 1 1
7 E02 685 975 CORNER BOX RIGHT 1 1 1 1 1 1
8 E02 534 100 CATECHIN AIR FILTER 2 2 2 2 2 2 1PCE/SET
9 AIR CLEANING FILTER 2 2 2 2 2 2 MAC-1700FT
10 E02 888 007 LAMP PANEL 1 1 1 1 1 1

10-2. INDOOR UNIT HEAT EXCHANGER


E02 817 620 INDOOR HEAT EXCHANGER 1 1
11 E02 947 620 INDOOR HEAT EXCHANGER 1 1
E02 890 620 INDOOR HEAT EXCHANGER 1 1
E02 179 667 UNION(GAS) 1 1 {12.7
12 E02 138 666 UNION(GAS) 1 1 {15.88
E02 A16 666 UNION(GAS) 1 1 {15.88
E02 151 667 UNION(LIQUID) 1 1 1 1 {6.35
13
E02 527 667 UNION(LIQUID) 1 1 {9.52

OB400C 23

Downloaded from www.Manualslib.com manuals search engine


PARTS LIST (non-RoHS compliant)

MS-A18VD MS-A24VD MS-A30VD


10-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS

1 20 19
2
3

4
12
11
5
18
6 17
10
7 13

14 15 16
8
9

10-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS


Part numbers that are circled are not shown in the illustration.

Symbol Q'ty/unit
No. Part No. Part name in Wiring MS-A18 MS-A18 MS-A24 MS-A24 MS-A30 MS-A30 Remarks
Diagram VD- K1 VD- K2 VD- K1 VD- K2 VD- K1 VD- K2
1 E02 527 302 LINE FLOW FAN 1 1 1 1 1 1
2 E02 408 509 BEARING MOUNT 1 1 1 1 1 1
3 E02 001 504 SLEEVE BEARING 1 1 1 1 1 1
4 E02 408 702 DRAIN HOSE 1 1 1 1 1 1
E02 527 235 NOZZLE 1 1 1
5
E02 996 235 NOZZLE 1 1 1
6 E02 685 040 VANE UPPER 1 1 1 1 1 1
7 E02 685 041 VANE LOWER 1 1 1 1 1 1
8 E02 A49 382 FUSE F11 1 1 1 1 1 1 T3.15AL250V
9 E02 817 385 VARISTOR NR11 1 1 1 1 1 1
10 E02 527 034 VANE CRANK SET 1 1 1 1 1 1
RC4V32-
E02 817 300 INDOOR FAN MOTOR ASSEMBLY MF 1 1 Including RUBBER MOUNT
11 RC4V40-
E02 527 300 INDOOR FAN MOTOR ASSEMBLY MF 1 1 1 1 Including RUBBER MOUNT
12 E02 448 303 VERTICAL VANE MOTOR MV2 2 2 2 2 2 2 RIGHT&LEFT
13 E02 408 303 HORIZONTAL VANE MOTOR MV1 1 1 1 1 1 1 UP&DOWN
14 E02 528 329 DISPLAY P.C. BOARD 1 1 1 1 1 1
15 E02 527 468 RECEIVER P.C. BOARD 1 1 1 1 1 1
E02 946 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
E02 A14 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
E02 947 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
16
E02 A15 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
E02 948 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
E02 A16 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
17 E02 527 308 ROOM TEMPERATURE THERMISTOR RT11 1 1 1 1 1 1
E02 817 333 MOTOR BAND 1 1
18
E02 527 333 MOTOR BAND 1 1 1 1
E02 888 375 TERMINAL BLOCK TB 1 1 1 1
19
E02 814 375 TERMINAL BLOCK TB 1 1
E02 408 311 INDOOR COIL THERMISTOR RT12 1 1
20 E02 947 311 INDOOR COIL THERMISTOR RT12 1 1
E02 527 311 INDOOR COIL THERMISTOR RT12, RT13 1 1
21 E02 528 034 VANE MOTOR SUPPORT SET (RIGHT) 1 1 1 1 1 1
22 E02 529 034 VANE MOTOR SUPPORT SET (LEFT) 1 1 1 1 1 1
23 E02 408 381 THERMAL FUSE F12 1 1
w1 Refer to 8-6.
OB400C 24

Downloaded from www.Manualslib.com manuals search engine


PARTS LIST (non-RoHS compliant)

MS-A18VD MS-A24VD MS-A30VD


10-4. ACCESSORY AND REMOTE CONTROLLER
1 2

10-4. ACCESSORY AND REMOTE CONTROLLER


Symbol Q'ty/unit
No. Part No. Part name in Wiring MS-A18 MS-A18 MS-A24 MS-A24 MS-A30 MS-A30 Remarks
Diagram VD- K1 VD- K2 VD- K1 VD- K2 VD- K1 VD- K2
1 E02 527 426 REMOTE CONTROLLER 1 1 1 1 1 1 KM04B
2 E02 527 083 REMOTE CONTROLLER HOLDER 1 1 1 1 1 1

10-5. AIR CLEANING FILTER


● Normal life of AIR CLEANING FILTER is 4 months. However, when it becomes dirty, replace it as soon as possible.
● Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
● DO NOT reuse AIR CLEANING FILTER even if it is washed.
● DO NOT remove or attach AIR CLEANING FILTER during unit operation.

Model Part No.


MS-A18VD - K1
MS-A18VD - K2
MS-A24VD - K1 MAC-1700FT
MS-A24VD - K2
MS-A30VD - K1 Air cleaning filter (White bellows type)
MS-A30VD - K2

OB400C 25

Downloaded from www.Manualslib.com manuals search engine


11 RoHS PARTS LIST (RoHS compliant)

MS-A18VD MS-A24VD MS-A30VD


11-1. INDOOR UNIT STRUCTURAL PARTS 11-2. INDOOR UNIT HEAT EXCHANGER

2
11
3

4
CATCH 12
7 9
5
SCREW
(See 11-5.)
CAP
13

11-1. INDOOR UNIT STRUCTURAL PARTS


Part number that is circled is not shown in the illustration.
Symbol Q'ty/unit
RoHS

No. Part No. Part name in WiringMS-A18 MS-A18 MS-A24 MS-A24 MS-A30 MS-A30 Remarks
Diagram VD- K1 VD- K2 VD- K1 VD- K2 VD- K1 VD- K2
1 G E12 527 970 INSTALLATION PLATE 1 1 1 1 1 1
2 G E12 685 234 BOX 1 1 1 1 1 1
3 G E12 888 000 FRONT PANEL ASSEMBLY 1 1 1 1 1 1 Including No.4,5,6
4 G E12 408 142 CATCH 4 4 4 4 4 4 4PCS/SET
5 G E12 685 067 SCREW CAP 3 3 3 3 3 3 3PCS/SET
6 G E12 888 010 GRILLE 1 1 1 1 1 1
7 G E12 685 975 CORNER BOX RIGHT 1 1 1 1 1 1
8 G E12 534 100 CATECHIN AIR FILTER 2 2 2 2 2 2 1PCE/SET
9 G AIR CLEANING FILTER 2 2 2 2 2 2 MAC-1700FT
10 G E12 888 007 LAMP PANEL 1 1 1 1 1 1

11-2. INDOOR UNIT HEAT EXCHANGER


G E12 817 620 INDOOR HEAT EXCHANGER 1 1
11 G E12 947 620 INDOOR HEAT EXCHANGER 1 1
G E12 890 620 INDOOR HEAT EXCHANGER 1 1
G E12 179 667 UNION(GAS) 1 1 {12.7
12 G E12 138 666 UNION(GAS) 1 1 {15.88
G E12 A16 666 UNION(GAS) 1 1 {15.88
G E12 151 667 UNION(LIQUID) 1 1 1 1 {6.35
13
G E12 527 667 UNION(LIQUID) 1 1 {9.52

OB400C 26

Downloaded from www.Manualslib.com manuals search engine


RoHS PARTS LIST (RoHS compliant)

MS-A18VD MS-A24VD MS-A30VD


11-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS

1 20 19
2
3

4
12
11
5
18
6 17
10
7 13

14 15 16
8
9

11-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS


Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
RoHS

No. Part No. Part name in Wiring MS-A18 MS-A18 MS-A24 MS-A24 MS-A30 MS-A30 Remarks
Diagram VD- K1 VD- K2 VD- K1 VD- K2 VD- K1 VD- K2
1 G E12 527 302 LINE FLOW FAN 1 1 1 1 1 1
2 G E12 408 509 BEARING MOUNT 1 1 1 1 1 1
3 G E12 001 504 SLEEVE BEARING 1 1 1 1 1 1
4 G E12 408 702 DRAIN HOSE 1 1 1 1 1 1
G E12 527 235 NOZZLE 1 1 1
5
G E12 996 235 NOZZLE 1 1 1
6 G E12 685 040 VANE UPPER 1 1 1 1 1 1
7 G E12 685 041 VANE LOWER 1 1 1 1 1 1
8 G E12 A49 382 FUSE F11 1 1 1 1 1 1 T3.15AL250V
9 G E12 817 385 VARISTOR NR11 1 1 1 1 1 1
10 G E12 527 034 VANE CRANK SET 1 1 1 1 1 1
RC4V32-
G E12 817 300 INDOOR FAN MOTOR ASSEMBLY MF 1 1 Including RUBBER MOUNT
11 RC4V40-
G E12 527 300 INDOOR FAN MOTOR ASSEMBLY MF 1 1 1 1 Including RUBBER MOUNT
12 G E12 448 303 VERTICAL VANE MOTOR MV2 2 2 2 2 2 2 RIGHT&LEFT
13 G E12 408 303 HORIZONTAL VANE MOTOR MV1 1 1 1 1 1 1 UP&DOWN
14 G E12 528 329 DISPLAY P.C. BOARD 1 1 1 1 1 1
15 G E12 527 468 RECEIVER P.C. BOARD 1 1 1 1 1 1
G E12 946 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
G E12 A14 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
G E12 947 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
16
G E12 A15 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
G E12 948 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
G E12 A16 452 ELECTRONIC CONTROL P.C. BOARD w1 1 AUTO RESTART
Including No.15
17 G E12 527 308 ROOM TEMPERATURE THERMISTOR RT11 1 1 1 1 1 1
G E12 817 333 MOTOR BAND 1 1
18
G E12 527 333 MOTOR BAND 1 1 1 1
G E12 888 375 TERMINAL BLOCK TB 1 1 1 1
19
G E12 814 375 TERMINAL BLOCK TB 1 1
G E12 408 311 INDOOR COIL THERMISTOR RT12 1 1
20 G E12 947 311 INDOOR COIL THERMISTOR RT12 1 1
G E12 527 311 INDOOR COIL THERMISTOR RT12, RT13 1 1
21 G E12 528 034 VANE MOTOR SUPPORT SET (RIGHT) 1 1 1 1 1 1
22 G E12 529 034 VANE MOTOR SUPPORT SET (LEFT) 1 1 1 1 1 1
23 G E12 408 381 THERMAL FUSE F12 1 1
w1 Refer to 8-6.

OB400C 27

Downloaded from www.Manualslib.com manuals search engine


RoHS PARTS LIST (RoHS compliant)

MS-A18VD MS-A24VD MS-A30VD


11-4. ACCESSORY AND REMOTE CONTROLLER

1 2

11-4. ACCESSORY AND REMOTE CONTROLLER


Symbol Q'ty/unit
RoHS

No. Part No. Part name in Wiring MS-A18 MS-A18 MS-A24 MS-A24 MS-A30 MS-A30 Remarks
Diagram VD- K1 VD- K2 VD- K1 VD- K2 VD- K1 VD- K2
1 G E12 527 426 REMOTE CONTROLLER 1 1 1 1 1 1 KM04B
2 G E12 527 083 REMOTE CONTROLLER HOLDER 1 1 1 1 1 1

11-5. AIR CLEANING FILTER


● Normal life of AIR CLEANING FILTER is 4 months. However, when it becomes dirty, replace it as soon as possible.
● Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
● DO NOT reuse AIR CLEANING FILTER even if it is washed.
● DO NOT remove or attach AIR CLEANING FILTER during unit operation.

Model Part No.


MS-A18VD - K1
MS-A18VD - K2
MS-A24VD - K1 MAC-1700FT
MS-A24VD - K2
MS-A30VD - K1 Air cleaning filter (White bellows type)
MS-A30VD - K2

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

C Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD


Distributed in Aug. 2011. No.OB400 REVISED EDITION-C
Distributed in May 2006. No.OB400 REVISED EDITION-B 6
Distributed in Nov. 2005. No.OB400 REVISED EDITION-A 6
Distributed in Mar. 2005. No.OB400 106 New publication, effective Aug. 2011
Made in Japan Specifications subject to change without notice.

Downloaded from www.Manualslib.com manuals search engine

You might also like