Reply to Comment under AGG-A2016-MS-WTPA-00200a

No. Comment Reply


1) Please review the attached RC strengthening for the slab, It Checked and Updated; Remark that Placing boom for Tower 4 to be cancelled.
appears that there is a discrepancy between the provided
calculations and RC strengthening detail (area of steel
provided is less than the one required
2) Please provide the punching shear checking for the slab, Checked and Shown in Appendix F;
considering the presence of a point load acting on the slab.

3) The column and wall checking are missing from appendix E Updated;

4) The column and wall moment and loading input are missing Updated;
from appendix F

5) Please clarify the purpose of including the calculation for the As the slab is revised to cast insitu, it is not semi precast slab. No further checking on semi
precast slab, as all the supports of placing boom are acting on precast slab is required. This part of calculation to be cancelled.
the in situ slab.