05B 1 OF2 ND-648703 P 462 14580

WORKING CONDITIONS AND REQUIREMENTS NOTES:

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
a) To operate in a desert areaambiant temperature up to 35 ^C

Enquiry/Order No. Item No. Quentity


b) Derating the thermal elements of Breakers and Contactors, based on calibration at
KEY TOP 5 FB-462-16-9004 3 1
40/50^C and for a max. BREAKER ambient, taken as 50 ^C
A Space Desription
MOTOR CONTROL CENTER, type
B Unit has been done buyer
is to be done by Supplier
ELECTRICAL DATA
C Space
NEMA wiring, class and type
c) Indoor service NEMA enclosure type 1

SECTION UNDER BI-3712


D Unit 2FD 3FD 4FD ^C
Power leads CLASS 1 TYPE C Control leads CLASS 1 TYPE C

NEW MCC VERTICAL


Provide ventilatig solts in top and bottom of each unit section.
E Space
System Voltes Phase Wires Cycles
F Unit Outdoor service NEMA enclosure type
480 3 3 60
G Space No ventilatig solts to be provided
Short circuit capacity 22000 Amps
H Unit 2FH 3FH 4FH
NOTE: For both, indoor and outdoor service, each unit section shall contain a space Horizontal Main bus rated 1200 Amps braced for
J Space
heater with individual control switch and fuses
22000 Amps short circuit capacity.
K Unit

L Space d) All surface to be provided with a tropical finish resistance to a highly corrosive Copper Aluminum
atmosphere and high humidity.
M Unit 1FM 2FM 4FM 4FM Ground bus yes/no Neutral bus yes/no

BOTTOM e) Back to back arrangement required. yes/no


Incoming cable bus-duct cable per phase, size 1200AMP

f) Cubical depth 20 inch entering at top/bottom of section 1

FRONT VIEW Outgoing Leads: Terminal Board Compartment at top/bottom

NONE
Arrangement of starting units, future space units, incoming line devices,and feeder

devices, Vertical sections of above sketches are key-numbered by letter assignment

and units by number assignment, and are detailed in table below.

SERVICE DESIGNATION MOTOR DATA BUILT-IN COMBINATION STARTER


Ref Locked OUT GOING Full Voltage
Key Full STARTER CIRCUIT BREAKER
To Nameplates Phase Roter CABLE Reversing
Nos. Load NEMA
AUX.CONT. OVERLOAD RELAY MAGN. TRIP INTERRUPT.
Lamacoid or Similar Current SEE NOTE 1 Or Non- FRAME TRIP
Current Size CAPACITY
HP AMPS AMPS POWER CONTR. Reversing No. TYPE RANGE SETTING CAT. NO. AMPS AMPS RANGE SETTING AMPS.

1FM REACTOR

2FD COOLING WATER PUMP-GM-208C 100 3 125 381 4 3/C #4/0 4/C #12 FVNR 4 2NO / 2NC 400 200 1200-4000 1880 22,000
2FH COOLING WATER PUMP-GM-211M 50 3 60 363 3 3/C #1 4/C #12 FVNR 4 2NO / 2NC 100 100 480-1000 792 22,000

2FM COOLING WATER PUMP-GM-211N 50 3 60 363 3 3/C #1 4/C #12 FVNR 4 2NO / 2NC 100 100 480-1000 792 22,000
SCALE:

REVISION VALIDATION
3FD REFRIDGE COND. EM-211P 50 3 60 363 3 3/C #1 4/C #12 FVNR 4 2NO / 2NC 100 100 480-1000 792 22,000
3FH 60 363 3/C #1 THIS REVISION NO. 06 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
REFRIDGE COND. EM-211Q 50 3 3 4/C #12 FVNR 4 2NO / 2NC 100 100 480-1000 792 22,000
REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
3FM REFRIDGE COND. EM-211R 50 3 60 363 3 3/C #1 4/C #12 FVNR 4 2NO / 2NC 100 100 480-1000 792 22,000
532220-0811-004

DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER


(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
4RD INTERSTAGE COOLER EM-201B-J 50 3 60 363 3 3/C #1 4/C #12 FVNR 4 2NO / 2NC 100 100 480-1000 792 22,000 ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE
AOO MSA MSA MSA
4RH INTERSTAGE COOLER EM-201B-K 50 3 60 363 3 3/C #1 4/C #12 FVNR 4 2NO / 2NC 100 100 480-1000 792 22,000 08/28/11 08/28/11 08/28/11 08/28/11

4RM INTERSTAGE COOLER EM-201B-L 50 3 60 363 3 3/C #1 4/C #12 FVNR 4 2NO / 2NC 100 100 480-1000 792 22,000 REV.NO. DATE REVISION DESCRIPTION

06 08/28/11 REVISED AS BUILT

JOB ORDER/EWO NO.


THIS REVISION IS NOT TO BE USED FOR
532220 CONSTRUCTION UNTIL CERTIFIED AND DATED

NOTES: Additional Requirements:


SAUDI ARABIAN OIL COMPANY
3) THERMINAL TRIPS ELEMENTS IN CIRCUIT BREAKERS SHALL BE DRAWING TYPE
1) VENDOR TO PROVIDE ALL CONTROL TERMINALS & PROVISIONS VERTICAL BUSSES RATED AMPS, BRACED FOR KA.
TO CONNECT POWER CABLE. LUGS PROVIDED BY OTHERS.
AMBIENT COMPENSATED.
1. PROVISIONS FOR BLOCKING OF ALL BREAKERS IN "OFF" POSITION.
MOTOR CONTROL CENTER #3(FRONT) CBL
2) ALL COMBINATION STARTERS SHALL BE PROVIDED WITH 4) ALL COMBINATION STARTERS SHALL BE PROVIDED WITH A C.P. 2. FLANGE FOR BUYERS THROAT CONNECTED BUS DUCT
OVERLOAD RELAYS HAVING 3 AMBIENT COMPENSATED ELEMENTS. TRANSFORMER 460-120V, HAVING NEC FUSES IN SECONDARY CIRCUIT
SUBSTATION #24
COMPRESSION & DEETH’ING PLANT ABQ
Amp. rating to be provided by Suppliers. AUX. CONTACTS No. = Number per contactor
* In accordance with Dwg. Fig. ABQAIQ SAUDI ARABIA
Type= N.O., N.C., SPDT, etc.
X Amp. rating to be provided by later. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.
** In accordance with Dwg. Fig.

CONFIDENTIAL - downloaded by dekockgs on 2/20/2024


***
462 P ND-648703 001 06
Saudi Aramco 2636 ENG. (09/03)

RESTRICTED VECTOR CADD-04