Professional Documents
Culture Documents
Capacitor Protection: © 2009 by Taylor & Francis Group, LLC
Capacitor Protection: © 2009 by Taylor & Francis Group, LLC
Capacitor Protection
9.96 KV × 4 = 39.84 KV
39.84 KV × √ 3 = 69 KV
When one CAN fuse opens, the impedance of, and the voltage across,
the remaining CANs in that parallel group increases. If additional fuses
in this same parallel group open, the voltage across remaining CANs will
continue to increase. The goal is to detect overvoltage before voltage
becomes high enough to cause additional CAN failures.
Several protection alternatives are available. One method is to connect
the phases to ground through a CT and to use the neutral current as an
indication that the bank should be tripped off-line. A second method is
to connect VTs to each phase and to use group voltage as an indicator
that the bank should be tripped off-line. The first method is commonly
used for protection of capacitor banks rated 138 KV and below. The second
method, which requires the installation of two VTs per phase, is com-
monly used for protection of capacitor banks rated above 138 KV.
299
© 2009 by Taylor & Francis Group, LLC
300 Protective Relay Principles
Figure 18.1
Typical three-phase capacitor bank.
The following equation can be used to determine the voltage on the remain-
ing CANs when fuses in the capacitor bank shown in Figure 18.1 open.
PG × E ϕ -N
E High =
N F + S × (PG − N F )
E ϕ -N − E G
E Other =
S −1
where
EHigh = the voltage across a parallel group of CANs with open fuses
EOther = t he voltage across other parallel groups of CANs, that is, the
groups that have no open fuses
Eφ-N = the phase-to-neutral voltage across series groups of CANs
NF = the number of failed CANs in a parallel group
PG = the number of CANs in a parallel group
S = the number of series groups
For the capacitor bank shown in Figure 18.1 with no CAN fuses open,
69, 000 V
6×
E High = 3 = 9959 V
0 + 4 × (6 − 0)
69, 000 V
6×
E High = 3 = 11, 382 V = 114.2%
1 + 4 × (6 − 1)
69, 000
V − 11, 382 V
EO = 3 = 9485 V = 95.2%
4 −1
For the capacitor shown in Figure 18.1 with two CAN fuses open in the
same group,
69, 000 V
6×
EG = 3 = 13, 279 V = 133.3%
2 + 4 × (6 − 2)
69, 000
V − 13, 279 V
EO = 3 = 8852 V = 88.9%
4 −1
Figure 18.2
Typical three-phase capacitor bank with one CAN removed neutral CT.
The trip value should be indicative of CAN failures that would lead to
overvoltage conditions. Very low trip settings should be applied in order
to minimize the possibility that a CAN fuse could open in Phase 1, fol-
lowed by a random fuse opening in Phase 2, followed by a random fuse
opening in Phase 3. In which case, the neutral current would return to
zero even though three of the twelve series-parallel groups are experienc-
ing increased voltage.
The unbalance current due to a CAN fuse opening is approximately
KVAR E ϕ -N PG × N F
I= × ×
KV S × V S × (PG − N F ) + N F
where
Eφ-N = the phase-to-neutral voltage across a series group of CANs
KV = the voltage rating of each CAN in the bank
KVAR = the var rating of each CAN in the bank
NF = the number of failed CANs in a parallel group
For the capacitor bank shown in Figure 18.2, the unbalance current due
to a CAN fuse opening is approximately
69, 000
V
200 KVAR 3 6×1
I= × × amps
9.96 KV 4 × 9960 V 4 × (6 − 1) + 1
I = 20.08 × 1 × 0.286 = 5.74 amps
The neutral CT should be sized to carry rated phase current in the event
that one phase of the 69-KV switching device fails (to open or close).
If a 100/5 amp CT is utilized, the CT secondary current for one CAN
fuse open would be 0.287 amps and a time overcurrent relay, which is
not sensitive to harmonic currents, could be utilized. The setting could be
0.2 amps with a 2-second time delay at ten multiples of pickup.
Another alternative is to install an adjustable resistor across the second-
ary of the CT (100/5, with 150-volt secondary voltage capability), as shown
in Figure 18.3, and to connect a time overvoltage relay across the terminals
of the resistor.
With a resistor setting of 25 Ωs, a time overvoltage relay, which is not
sensitive to harmonic currents, could be set to pick up at 5 volts (0.287 A ×
25 Ω = 7.175 V). The setting could be 5.0 volts with a 4-second time delay at
two multiples of pickup.
Figure 18.3
Typical three-phase capacitor bank with one CAN removed neutral CT and voltage relay.
and the voltage across the other half of the bank becomes
Figure 18.4
Typical three-phase capacitor bank voltage comparison relay phase-to-ground CCVTs.
Figure 18.5
Typical three-phase capacitor bank voltage comparison relay phase-to-midpoint and mid-
point-to-ground CCVTs.