Professional Documents
Culture Documents
Shunt and Series Reactor Protection: © 2009 by Taylor & Francis Group, LLC
Shunt and Series Reactor Protection: © 2009 by Taylor & Francis Group, LLC
When selecting protective relaying schemes for series and shunt reactors, it
is important to recognize the potential impact of a failure. If the reactor is
an oil-filled unit, there is the possibility of tank rupture with an oil spill and
fire that spreads to the surrounding area. If the reactor is an air-core unit,
the impact of a reactor failure would be an arc flash similar to a line fault.
Shunt reactors are used to control VAR loading. Series reactors are used
to reduce short-circuit current by increasing impedance or to control
power flow by changing transmission-line impedance.
Differential relays are used to detect failures quickly and to initiate iso-
lation of failed oil-filled reactors and air-core shunt reactors. Tank sudden
pressure relays may be used to provide an alternate means of detecting
failures. Overcurrent or impedance relays can be used to provide backup
protection. Air-core series reactors are usually considered to be in the
zone of protection provided for the associated transmission line, distribu-
tion line, or transformer.
A one-line diagram for a shunt reactor tapped off a transmission line is
illustrated in Figure 19.1. When protective relays operate, tripping of the
reactor circuit breaker would be initiated. If the switching device is a cir-
cuit switcher rather than a circuit breaker, a circuit switcher block tripping
scheme may be required. Separate zones of protection are established for
the shunt reactor and for the transmission line. CT connections for one set
of line relays, one set of differential relays, and backup overcurrent relays
for a shunt reactor are shown in Figure 19.2.
A typical shunt reactor would be a three-phase, 100-MVA, 345-KV reac-
tor that has an impedance of j1190 ohms per phase and rated current of
167 amps. Since shunt reactor current is proportional to system voltage,
maximum shunt reactor current should be less than 110% of rated as sys-
tem voltage should not exceed 110% of rated voltage.
A one-line diagram for a switchable, oil-filled series reactor (used to
change apparent line impedance) of a transmission line is illustrated in
Figure 19.3. The bypass switch—a circuit switcher or a circuit breaker—
functions as a switching device; that is, the bypass switch is not opened by
protective relays. The zone of protection for the transmission line includes
the series reactor. Reactor differential relaying is provided to detect faults
within the reactor tank. When the reactor differential relay operates, trip-
ping of the associated line circuit breakers at Bus 1 and Bus 2 would be ini-
tiated. In series reactor applications, switchable protective relay settings
307
© 2009 by Taylor & Francis Group, LLC
308 Protective Relay Principles
Line CB Line CB
Bus 1 Bus 2
Reactor CB
Shunt Reactor
Figure 19.1
Shunt reactor tapped off transmission line.
Bus 1 Bus 2
Reactor Overcurrent Relay
Line Relay
Reactor
Differential
Line Relay Relay
Figure 19.2
CT connections for shunt reactor tapped off transmission line.
Bus 1 Bus 2
Bypass CB
Figure 19.3
Switchable, series reactor installation.
(or switchable protective relays) are required if phase distance relays are
used for line protection. Otherwise, it may not be possible to develop prac-
tical Zone-1 and Zone-2 relay settings.
Bypass circuit-breaker position disagreement protection should be
considered if failure of one bypass circuit breaker (to open) can result in
transmission-line failure. Consider, for example, four parallel transmis-
sion lines equipped with switchable series reactors. If the self impedance
of each transmission line is 10 ohms and the impedance of each series
reactor is 10 ohms, each line would carry 25% (1/4) of the total current
when all reactors are in or out of service. If, however, three series reactors
are in service and the bypass circuit breaker for the fourth series reactor
fails to open, the three lines with series reactors in service would each
carry 20% and the fourth line with the series reactor bypassed would
carry 40% of total current.
Pole disagreement protection should be considered for each bypass cir-
cuit breaker if failure of one pole (to open) can result in transmission-line
failure. The difference between bypass circuit-breaker position disagree-
ment protection and pole disagreement protection is that pole dis
agreement checks current flow through the three phases of each bypass
circuit breaker whereas circuit-breaker position disagreement checks cur-
rent flow through parallel transmission lines.
CT connections for one set of line relays and one set of differential relays
for a switchable, oil-filled series reactor are shown in Figure 19.4.
A typical switchable, oil-filled series reactor would be a three-phase,
345-KV reactor that has an impedance of j35 ohms per phase and rated
current of 2000 amps. Since series reactor current is affected by transmis-
sion-line impedance and parallel paths, maximum reactor current should
be calculated using load flow methodology. Generally if the impedance
of a series reactor is less than one-half of the transmission-line reactance,
the maximum series reactor current can approach maximum, short-time
transmission-line current (that is, maximum transmission line current
when the series reactor is bypassed). If, however, the impedance of a series
CB Pole CB Position
Disagreement Disagreement
Protection Protection
Bus 1 Bus 2
Reactor
Differential Relay
Bypass CB Bypass CB
Open/Close Open/Close
Position Position
Input Input
Figure 19.4
CT connections for switchable series reactor.
4
Operate Current
Operate Region
1
Restraint Region
0
0 2 4 6 8 10 12 14 16 18 20
Restraint Current
Minimum Operate Current = 0.25 Amps
Series Order
20% Restraint 15% Restraint 10% Restraint
Figure 19.5
Reactor differential relay operate-restrain characteristic.
Example 19.1
Determine CT ratios and protective relay settings for a switchable series reactor
with the following parameters:
• Three phase
• 230-KV reactor
• Z = j12 ohms per phase
• Rated current = 2000 amps
• Short time current = 2400 amps
Western Line 1
Eastern
Dispatch
Dispatch
Area
Area
Line 2
Line 3
Figure 19.6
One line diagram showing a series reactor installation.
Table 19.1
Load Flow Study Results
System Line 2, Line 2, Out of Service
Normal Out of Service Series Reactor Switched In
Line 1 1600 A 2100 A 1800 A
Line 2 1000 A 0
Line 3 1000 A 1500A 1800 A
Example 19.2
Determine CT ratios and protective relay settings for a shunt reactor with the
following parameters:
• Three phase
• 230-KV reactor
• 50 MVA
• Z = j1050 ohms per phase
• Rated current = 126 amps
The associated transmission line has a summer short-time rating of 1800 amps
and a winter short-time rating of 2400 amps. A section of the power system is
illustrated in Figure 19.7.
Assuming current transformers for the reactor differential are matched, 2000/5 CTs,
the CTs should be set on the 300/5-amp tap and the differential relay should be set with
10% restraint. Minimum fault current to actuate the differential would be 0.25 relay
amps × 300/5 = 15 amps.
Assuming current transformers for the backup relays are 2000/5 CTs, the CTs should
be set on the 2000/5-amp tap. The time overcurrent relays should be set on the 0.5-amp
tap, 200 reactor amps, using #1 time dial. The instantaneous overcurrent relays should
be set on the 5.0-amp tap, 2000 reactor amps. (Minimum setting would be twice rated
current with 250% margin 2 × 126 amps × 250% = 630 amps.)
Line 1
Western Easter
Dispatch Dispatch
Area Area
Line 2
Line 3
Figure 19.7
One line diagram showing a shunt reactor installation.