Drive Lecture 4 Slip Power

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 25

Advanced Electric Drives

Ass. Prof. Dr. Mohamed El-Kourfouly


Dr. Magdi A. Mosa
Electrical Power and Machine Department
Faculty of Engineering – Helwan University
Speed Control of 3phase I. M.

The speed and the torque of I.M can be varied by one of the following means:
1. Stator Voltage Control
2. Stator Frequency Control
3. Stator Voltage /Frequency Control
4. Rotor resistance control.
5. Slip Power Recovery
6. Rotor Voltage Control
7. Stator Current Control
8. Stator Current, and Frequency Control
9. Pole changing
Speed Control by adding Resistance in rotor circuit
This method is applied only for slip ring induction motors
Accomplished by adding three phase resistance in rotor circuit

n 𝑇𝐿
𝑅𝑥 = 0
𝑛𝑠

𝑅𝑥 1

𝑅𝑥 2

T
120𝑓
𝑛𝑠 = = 𝐶𝑜𝑛𝑠𝑡𝑎𝑛𝑡
𝑃
𝑅𝑥 2 > 𝑅𝑥 1
2
3𝑉𝑝ℎ
𝑇𝑚 = 2 = 𝐶𝑜𝑠𝑛𝑡𝑎𝑛𝑡
2ω𝑠 𝑋1 + 𝑋′2
𝑅′2
𝑆𝑐𝑟 = ∝ 𝑅𝑎𝑑𝑑
𝑋1 + 𝑋′2
Speed Control by adding Resistance in rotor circuit
n 𝑇𝐿
𝑅𝑥 = 0
Advantages 𝑛𝑠

1. Increases the starting torque 𝑅𝑥 1

2. constant maximum torque


𝑅𝑥 2
3. reduces the starting current
4. no additional losses in side the motor losses are outside
5. constant flux operation T

6. Improves the system power factor therefore reduces the required reactive power
compensator
7. Doesn’t produces harmonics such as power electronic devices
8. The machine is not derated due to absence of harmonics in rotor circuit
Speed Control by adding Resistance in rotor circuit
Limitations
1. Needs to three phase balanced resistance, since un balance resistance produces
unbalanced current in rotor circuit which
2. High power losses, but this losses is dissipated outside the motor therefore this losses not
overheat the motor, the losses is called slip power losses
3. Less range of speed control
4. Needs variable resistance which is usually designed in steps to ensure good contacts,
therefore speed control is performed in steps not smoothly
5. Doesn’t applied to squirrel cage induction motor
6. The resistance needs for cooling system specially for large motors
7. Mechanically Manual controlled or mechanically motorized control
8. Sparks generation specially in high power applications
9. Needs periodic maintenance due to movable parts and bad contact generated from
sparks
Speed Control by adding Resistance in rotor circuit
The three-phase resistor may be replaced by a three-phase diode rectifier and a dc converter,
as shown in Figure, where the gate-turn-off thyristor (GTO) or an insulated-gate bipolar
transistor (IGBT) operates as switch. Id

Id

is iR
is t

Id

i2 iR t
i2

Id
2π/3 Id
Rotor Current 2π/3 π 2π ωt
Ton Ts t
Id

1. The slip frequency AC rotor voltages are converted into DC by a 3-phase diode bridge and
applied across an enteral resistance R. The semiconductor switch is operated periodically
with a period T𝑠 and remains on for an interval ton in each period.
2. The effective value of resistance R changes from R to 0 as ton changes from 0 to T𝑠
3. The filter inductor L𝑑 , is provided to minimize the ripple in current Id
Speed Control by adding Resistance in rotor circuit
𝑡𝑜𝑛 = D𝑇𝑠
The average value of switch current
𝑡𝑜𝑛 𝑡𝑜𝑓𝑓 = 1 − D 𝑇𝑠
Is = 𝐼 = 𝐷𝐼𝑑 Id
𝑇𝑠 𝑑
t
The average value of Resistor current is

𝑡𝑜𝑓𝑓
IR = 𝐼 = 1 − 𝐷 𝐼𝑑
𝑇𝑠 𝑑 Id

iR t
Energy Dissipated in the resistance
𝐸𝑅 = 𝐼𝑑2 R𝑡𝑜𝑓𝑓 = 𝐼𝑑2 R 1 − D T
Id

t on Ts t
Average power in the resistance
𝐸𝑅 𝐼𝑑2 R 1 − D T
𝑃𝑅 = = = 𝐼𝑑2 R 1 − D = 𝐼𝑑2 𝑅𝑒𝑓𝑓
𝑇 𝑇

The effective value of the resistance


𝑹𝒆𝒇𝒇 = 𝐑 𝟏 − 𝑫
Speed Control by adding Resistance in rotor circuit
Note
The effective value of the resistance is proportional inversely with the duty cycle D.
𝑅𝑒𝑓𝑓 = R 1 − D n 𝑇𝐿
𝐷1 = 1
𝑛𝑠

If the switch is completely open during the switching periods 𝐷2

D=0 𝑅𝑒𝑓𝑓 = R

𝐷3

If the switch is completely close during the switching periods


D=1 𝑅𝑒𝑓𝑓 = 0
T

The effective value of the resistance is changed smoothly by varying 𝐷3 < 𝐷2 < 𝐷1
the duty ratio from 1 to 0 i2

Id
2π/3 2π/3
1
I2,rms = 𝐼𝑑2 𝑑𝑡 = 2/3 𝐼𝑑 2π/3 π 2π ωt
π 0 Id
Speed Control by adding Resistance in rotor circuit
The effective AC resistance seen by rotor circuit
2
𝑃𝑅 = 𝐼𝑑2 R 1 − D =3𝐼2,𝑟𝑚𝑠
2
𝑅𝑎𝑐 = 3 3 𝐼𝑑2 𝑅𝑎𝑐

𝑅𝑎𝑐 = 0.5 1 − D R

The total resistance in rotor circuit is the summation of 𝑅𝑎𝑐 and rotor windings resistance per
phase
𝑅𝑡𝑜𝑡𝑎𝑙 = 𝑅𝑎𝑐 + 𝑅2

the torque is produced only by the fundamental. The harmonics produce only
pulsating torques.
i2

Fourier analysis Id
2π/3
The waveform is quarter odd
2π/3 π 2π ωt
Therefore even harmonics is zero
Average value is zero Id
The fundamental component is given by
Speed Control by adding Resistance in rotor circuit
π/2
4 4 π π 2 3
𝑏1 = 𝐼𝑑 sin ω𝑡 𝑑ω𝑡 = − 𝐼𝑑 cos − cos = 𝐼
π π/6 π 2 6 π 𝑑

𝑎1 6 6 3 3
𝐼𝑟1 = = 𝐼𝑑 = I2,rms = I2,rms
2 π π 2 π

This means the motor developed torque due to 𝐼𝑟1 while heat is generated is I2,rms therefore
for maximum current I2,rms the machine useful current is 𝐼𝑟1 the difference between this
values is called machine derating factor due to harmonics
𝐼𝑟1 3
Motor current derating = = = 0.95
I2,rms π

If the ripple in the Id, commutation overlap in the diode bridge, skin effect, and –the reduction
in full-load speed due to losses in diode bridge, inverter, transformer, and semiconductor
switch are considered, the derating of the motor will be much higher.
Speed Control by adding Resistance in rotor circuit
Motor equivalent circuit
The total power in rotor circuit is given by
2
2 𝑅
π 2
2
π 2
𝑃𝑔 = 𝑃𝑚 + 3𝐼𝑟𝑚𝑠 𝑡𝑜𝑡𝑎𝑙 = 𝑃𝑚 + 3 𝐼𝑟1 𝑅𝑡𝑜𝑡𝑎𝑙 = 𝑃𝑚 + 3 𝐼𝑟1 𝑅𝑡𝑜𝑡𝑎𝑙
3 9
The fundamental power in rotor circuit comes through air gap is given by
π2 2
𝑃𝑔1 = 𝑃𝑔 = 𝑃𝑚 + 3 𝐼𝑟1 𝑅𝑡𝑜𝑡𝑎𝑙
9
π2 2
𝑃𝑚 = (1 − 𝑠)𝑃𝑔1 = (1 − 𝑠)𝑃𝑚 + 3 𝐼𝑟1 𝑅𝑡𝑜𝑡𝑎𝑙 (1 − 𝑠)
9
π 2 2 (1 − 𝑠)
𝑃𝑚 = 3 𝐼𝑟1 𝑅𝑡𝑜𝑡𝑎𝑙
3 𝑠
π2 2 π2 2 (1 − 𝑠) π2 2
𝑃𝑔 = 𝑃𝑚 + 3 𝐼𝑟1 𝑅𝑡𝑜𝑡𝑎𝑙 = 3 𝐼𝑟1 𝑅𝑡𝑜𝑡𝑎𝑙 + 3 𝐼𝑟1 𝑅𝑡𝑜𝑡𝑎𝑙
9 9 𝑠 9

2
π2 𝑅𝑡𝑜𝑡𝑎𝑙 2
𝑃𝑔 = 3𝐼𝑟1 − 1 𝑅𝑡𝑜𝑡𝑎𝑙 + = 3𝐼𝑟1 𝑅𝑒
9 𝑠
Speed Control by adding Resistance in rotor circuit
The effective rotor resistance
π2 𝑅𝑡𝑜𝑡𝑎𝑙 𝑅𝑓
𝑅𝑒 = − 1 𝑅𝑡𝑜𝑡𝑎𝑙 + = 𝑅ℎ +
9 𝑠 𝑠
π2 π2
𝑅ℎ = − 1 𝑅𝑡𝑜𝑡𝑎𝑙 = −1 0.5 1 − D 𝑅 + 𝑅2
9 9
𝑅𝑓 = 𝑅𝑡𝑜𝑡𝑎𝑙 = 0.5 1 − D 𝑅 + 𝑅2

𝑅ℎ is the resistance equivalent to harmonic losses


𝑅𝑓 is the resistance corresponding to fundamental components losses
Speed Control by adding Resistance in rotor circuit
DC-Coil
1. The filter inductor L, is provided to minimize the ripple in current Id‘. A high ripple in Id
produces high harmonic content in the rotor, increasing copper losses and causing
derating of the motor.
2. The filter inductor also helps in eliminating discontinuous conduction at light loads.
3. As in the case of a DC motor, discontinuous conduction makes the speed regulation poor.
4. The main contributor to the ripple is the diode bridge and not the semiconductor switch,
because it operates at a sufficiently high frequency.
Speed Control by adding Resistance in rotor circuit
Advantages
n 𝑇𝐿
1. Increases the starting torque 𝑅𝑥 = 0
𝑛𝑠
2. constant maximum torque
𝑅𝑥 1
3. reduces the starting current
4. no additional losses in side the motor
𝑅𝑥 2
5. constant flux operation
6. Smooth speed control
7. Simple in control
T
8. No mechanical or movable parts
9. can be controlled remotely
10. Improves the system power factor therefore reduces the required reactive power
compensator
11. Only single resistance element
12. Assured balance of rotor circuit
13. Fast response
Speed Control by adding Resistance in rotor circuit
Limitations
1. High power losses, but this losses is dissipated outside the motor therefore this losses not
overheat the motor, the losses is called slip power losses
2. Less range of speed control
3. Doesn’t applied to squirrel cage induction motor
4. The resistance needs for cooling system specially for large motors
5. Produces harmonics in rotor circuit therefore the motor should be oversized or derated
6. Needs DC coil to avoid discontinues current operation specially at light loads
Speed Control by adding Resistance in rotor circuit
Example
A 3-phase, 460 V, 60 Hz, 1164 rpm, Y-connected, wound-rotor induction motor has the
following parameters:
R1 = 0.4 Ω, R’2 = 0.6 Ω, X1 = X’2 = 1.8 Ω, Xm = 40 Ω, Stator to rotor turns ratio is 2.5.
The motor speed is controlled by static rotor resistance control. Fi1ter resistance is neglected
and the external resistance is chosen such that at D=0, the breakdown torque is obtained at
standstill.
1. Ca1cu1ate the va1ue of the external resistance.
2. Ca1culate D for a speed of 960 rpm at 1.5 times the rated torque.
3. Ca1culate the speed for D=0.6 and l.5 times the rated torque.
Neglect friction and windage.
Note:
𝑁𝑠 2
R’= R
𝑁𝑟
Speed Control by adding Resistance in rotor circuit
Example:
A three-phase, 460-V, 60-Hz, six-pole Y-connected wound-rotor induction motor whose
speed is controlled by slip power, using resistance and switch, has the following parameters:
Rs = 0.041 Ω, R’r = 0.044 Ω, Xs = 0.29 Ω, X’r = 0.44 Ω, and Xm = 6.1 Ω.
The turns ratio of the rotor to stator windings is nm = Nr/Ns = 0.9. The inductance Ld is very
large and its current Id has negligible ripple. The values of Rs , Rr , Xs , and Xr for the
equivalent circuit in Figure 15.2 can be considered negligible compared with the effective
impedance of Ld. The no-load loss of the motor is negligible. The losses in the rectifier,
inductor Ld, and the GTO dc converter are also negligible. The load torque, which is
proportional to speed squared, is 750 N.m at 1175 rpm.
(a) If the motor has to operate with a minimum speed of 800 rpm, determine the resistance
R. With this value of R, if the desired speed is 1050 rpm, calculate
(b) the inductor current Id
(c) the duty cycle of the dc converter D
(d) the dc voltage Vd
(e) the efficiency
(f) the input PFs of the drive.
Speed Control using slip Power Recovery
Instead of wasting the slip power in the rotor circuit resistance, it can be fed back to the ac
mains using the approach suggested by krammer ans is called static krammer.
It is also known as the slip power recovery scheme or subsynchronous converter cascade
because it is capable of providing speed control only in the subsynchronous speed range.
However for regenerative can operate supper synchronous speed.

A diode bridge converts a portion of slip power into DC which in turn is converted into line
frequency by a 3-phase line commutated inverter and fed back to the ac mains through a
transformer.
Speed Control using slip Power Recovery
Power Flow diagram of Slip Power Recover 𝑃𝑠𝑢𝑝𝑝𝑙𝑦

𝑃𝑠𝑡𝑎𝑡𝑜𝑟

𝑃𝑐𝑢𝑝 + 𝑃𝑐𝑜𝑟𝑒 𝑃𝑔

𝑃𝑠 = 𝑠𝑃𝑔 𝑃𝑑 = (1 − 𝑠)𝑃𝑔

𝑃𝑟 𝑃𝑐𝑢𝑝2 𝑃𝑟𝑜𝑡𝑎𝑡𝑖𝑜𝑛𝑎𝑙 𝑃𝐿
Speed Control using slip Power Recovery
Firing angle to achieve certain speed
𝑁
Assuming 𝑎𝑚 is the effective turns ratio (𝑁𝑠 )of the stator and the rotor windings, the rotor
𝑟
voltage is related to the stator (and line voltage VL) by
𝑠𝑉𝐿
𝑉𝑟 =
𝑎𝑚
The dc output voltage of the three-phase rectifier is
3 2 3 2 𝑠𝑉𝐿 𝑠1.35𝑉𝐿
𝑉𝑑 = 𝑉𝑟 = =
π π 𝑎𝑚 𝑎𝑚

The converter is controller in the inversion mode then the DC voltage is negative
𝑠1.35𝑉𝐿
𝑉𝑑𝑐 = −𝑉𝑑 = −
𝑎𝑚
Also the converter related to the transformer output 𝑉𝑡 and transformer turns ratio of 𝑎𝑡
𝑉𝐿 𝑠1.35𝑉𝐿 𝑉𝐿
𝑉𝑑𝑐 = 1.35𝑉𝑡 cos 𝛼 = 1.35 cos 𝛼 ∴ 𝑉𝑑𝑐 = − = 1.35 cos 𝛼
𝑎𝑡 𝑎𝑚 𝑎𝑡
𝑠 cos 𝛼 −𝒔𝒂𝒕
− = ∴ 𝜶 = 𝒄𝒐𝒔−𝟏
𝑎𝑚 𝑎𝑡 𝒂𝒎
Speed Control using slip Power Recovery

 To avoid failure of thyristor commutation the firing angle should be less than 180
by an angle 𝛾 which is called extinction angle
 The practical values of 𝛾 is 15 to 18 degrees
π 𝑎𝑚
≤𝛼 ≤ π−𝛾 0≤𝑠≤ cos π − 𝛾
2 𝑎𝑡

2π/3
1
I2,rms = 𝐼𝑑2 𝑑𝑡 = 2/3 𝐼𝑑
π 0

If losses in R2 is neglected, the returned power to the stator is given by


Pr = 𝑉𝑑 𝐼𝑑 = 𝑠Pg

1−𝑠 𝑠1.35𝑉𝐿
Pd = 1 − 𝑠 Pg = 𝑉𝑑 𝐼𝑑 = 𝑇𝑑 ω𝑟 = 𝑇𝑑 ω𝑠 1 − 𝑠 𝑉𝑑 =
𝑠 𝑎𝑚
𝑉𝑑 𝐼𝑑 1.35𝑉𝐿 𝐼𝑑
𝑇𝑑 = =
𝑠ω𝑠 𝑎 𝑚 ω𝑠
Speed Control using slip Power Recovery
Example:
A three-phase, 460-V, 60-Hz, six-pole Y-connected wound-rotor induction motor whose
speed is controlled by a static schurbius drive, has the following parameters:
Rs = 0.041 Ω, R’r = 0.044 Ω, Xs = 0.29 Ω, X’r = 0.44 Ω, and Xm = 6.1 Ω.
The turns ratio of the rotor to stator windings is am = Ns /Nr= 1.1. The inductance Ld is very
large and its current Id has negligible ripple. The turns ratio of the converter ac voltage to
supply voltage is at =Np/Ns = 0.40. The load torque, which is proportional to speed squared
.The load torque is 750 N.m at 1175 rpm. If the motor is required to operate at a speed of
1050 rpm, calculate
(a) The inductor current Id
(b) the dc voltage Vd
(c) the delay angle of the converter
(d) the efficiency
(e) the input PF of the drive, PFs.
The losses in the diode rectifier, converter, transformer, and inductor Ld are negligible.
Speed Control using slip Power Recovery
Example:
A 3-phase, 460 V, 60 Hz, 1164 rpm, Y-connected, wound-rotor induction motor has the
following parameters:
R1 = 0.4 Ω, R’2 = 0.6 Ω, X1 = X’2 = 1.8 Ω, Xm = 40 Ω, Stator to rotor turns ratio is 2.5.
The motor speed is controlled by a static Scherbius drive. The drive has
been designed to provide speed control up to 50 percent of the synchronous speed. The
maximum value of the firing angle is 170°.
1. Calculate "at".
2. Calculate the torque and power factor for α= 120° and 720 rpm.
3. Calculate α for the rated torque and 720 rpm.
Speed Control using slip Power Recovery
EXAMPLE
A three-phase, six-pole, Y-connected, 480 V induction motor is driving a 300 Nm constant-
torque load. The motor has the following parameters:N1/N2=1, Protational = 1 kW.
The motor is driven by a slip energy recovery system. The triggering angle of the dc/ac
converter is adjusted to 1200. Ignore all core and copper losses and calculate the following:
a) Motor speed
b) Current in the dc link
c) Rotor rms current
d) Stator rms current
e) Power returned back to the source
f) Assume that the motor is not driven by an SER system. If a resistance is
added in the rotor circuit to reduce the speed to that calculated in part a.,
compute the additional losses.
Dr. Magdi A. Mosa
magdimosa@yahoo.com
01282969241