AH

KK HVAC LEGENDS:
MA
PACU: PACKAGED AIR CONDITIONING UNIT SD: SUPPLY DIFFUSER
EF: EXHAUST FAN RD: RETURN DIFFUSER
VCD: VOLUME CONTROL DAMPER SG: SUPPLY GRILL
CRAC: COMPUTER ROOM AIR CONDITIONING EF: EXHAUST FAN
ACCU: AIR-COOLED CONDENSING UNITS ED: EXHAUST DIFFUSER
MD: MOTORIZED DAMPER HS: HUMIDITY SENSOR
FSD: FIRE SMOKE DAMPER WO: WALL OPENING
MFSD: MOTORIZED FIRE SMOKE DAMPER TS: TEMPERATURE SENSOR
1 2 3 AD:
BOD:
ACCESS DOOR
BOTTOM OF DUCT
EL:
BOP:
ELEVATION LEVEL
BUTTOM OF PIPE
8000 8000
SYMBOLOGY
RG REFRIGERANT GAS PIPE
EXHAUST DUCT
B SUPPLY DUCT
RL REFRIGERANT LIQUID PIPE

CDP
HV-A1-0025 HV-A1-0026 RETURN DUCT CONDENSATE PIPE

A HVAC PENTHOUSE
WO WALL OPENINGS HP HUMIDIFIER WATER SUPPLY PIPE

700(L)x550(W)x1100(H) T THERMOSTAT T/H TEMPERATURE / HUMIDIFIER


SENSOR
550x400 EA F/B GIS &

FD-17 TRANSFORMER
BUILDING
AD-5 EA 550x400
4650

1030 L/s
AD-5 BDD BOD:13832

I-2007-GT-EF-003
KEY PLAN
B NOTES:
THE PRESSURE RELAY PROVIDED FOR THE I-2007-GT-SCRU-001
1. ALL DRAWINGS MUST BE READ IN CONJUNCTION WITH OTHER RELEVANT
GAS MONITORING SHALL HAVE POTENTIAL- DRAWINGS AND SPECIFICATIONS.
FREE AUXILIARY CONTACTS FOR TWO STAGE 2. FOR DIMENSIONS OF STRUCTURAL ELEMENTS REFER TO STRUCTURAL DRAWINGS.
3. THIS DRAWING EXTRACTED FROM BIM MODEL : I-2007-HV-A1-0919.rvt
ALARM INITIATION THAT WILL FURTHER BE
4700

4. FOR GENERAL NOTES, ABBREVIATIONS, LEGENDS REFER TO


WIRED TO THE SCRUBBER SYSTEM DRAWINGS I-2007-HV-A1-0001 & I-2007-HV-A1-0002.
PROVIDED BY CONTRACTOR, WHICH SHALL 5. FOR STANDARD DETAILS REFER TO DRAWINGS I-2007-HV-A1-0003-01 TO
I-2007-HV-A1-0003-04.
SWITCH ON WHEN THERE IS A LEAKAGE OF 6. DRAIN PAN SHOULD BE PROVIDED UNDER ALL CONDENSATE PIPES OR WET
SF6 GAS INSIDE THE GIS ROOM. CROSSING / SERVING ANY ELECTRICAL OR TELECOM ROOM.
7. EQUIPMENT ARE PROVIDED WITH NORMAL POWER FEEDERS (PROTECTED
MCB/MCCB) , FURTHER REQUIREMENT OF STARTERS (IF ANY) SHALL BE PROVIDED
C 8.
BY VENDOR FOR SUCCESSFUL OPERATION OF THE EQUIPMENT .
BATTERY ROOM DUCTWORK MATERIAL SHOULD BE STAINLESS STEEL
WELDED DUCT/ FLANGES OR USE STAINLESS STEEL RIVETS /STAINLESS STEEL
2375

FASTENERS (CORROSIVE RESISTANCE).


9. ALL THE MOTORS SHOULD BE HIGH EFFICIENCY MOTORS.
10. MOTORS WITH POWER OF 3.75 KW AND LARGER SHOULD BE VFD TYPE.
11. GIS EXHAUST DUCTWORK MATERIAL SHOULD BE STAINLESS STEEL WELDED
DUCT/FLANGES OR USE STAINLESS STEEL RIVETS/STAINLESS STEEL
C.1 12.
FASTENERS (CORROSIVE RESISTANCE).
CRAC UNIT HAVE FOLLOWING ITEMS IN SELF-CONTAINED, FACTORY
ASSEMBLED PREWIRED AND PREPIPE, CONSISTING OF CABINET, FAN,
2325

FILTERS,CONTROL PANEL,LOCKING DISCONNECT, SIGHT GLASS WITH


MOISTURE INDICATOR, SERVICE SHUTOFF VALVES , DRIER.
13. DUCT WORK OUTSIDE THE BUILDING SHALL BE INSULATED WITH 50MM
THICK FIBERGLASS WITH A DENSITY OF 48 KG/M³ WITH ALUMINUM CLADDING.
D 14. DUCT WORK INSIDE THE BUILDING SHALL BE INSULATED WITH 50MM THICK
FIBERGLASS WITH A DENSITY OF 24KG/M³ WITH VAPOUR BARRIER.
15. THE BATTERY ROOM EXHAUST FANS ARE EXPLOSION PROOF.
16. CRAC UNIT ACCU HAVE BUILT-IN SIGHT GLASS, SHUTT OFF VALVES AND FILTER/DRYER.

SHOP DRAWING
5650

REFERENCE NUMBER DRAWING TITLE

I-2007-HV-A1-0001 GENERAL NOTES, ABBREVIATIONS, LEGENDS - SHEET 01


E I-2007-HV-A1-0002 GENERAL NOTES, ABBREVIATIONS, LEGENDS - SHEET 02
HV-A1-0025 HV-A1-0026
I-2007-HV-A1-0003-001 HVAC - INSTALLATION DETAILS - SHEET 01
EXHAUST DUCT DISCHARGE COMPLETE
E WITH GOOSE-NECK AND MESH SCREEN. I-2007-HV-A1-0003-002 HVAC - INSTALLATION DETAILS - SHEET 02
EXHAUST LOUVER AREA 0.065M2
I-2007-HV-A1-0003-003 HVAC - INSTALLATION DETAILS - SHEET 03
FOR CONTINUATION REFER RA 1000x700
4920 L/s I-2007-HV-A1-0003-004 HVAC - INSTALLATION DETAILS - SHEET 04
DWG.NO I-2007-HV-A1-0024
4800

BOD:800
RG-5/8" BOP:5550 FOR CONTINUATION REFER I-2007-HV-A1-0023-SD-001 HVAC - BASEMENT FLOOR PLAN LAYOUT
RL-1/2" BOP:5550 TEMPERATURE SENSOR
DWG.NO I-2007-HV-A1-0024
I-2007-HV-A1-0024-SD-001 HVAC - GROUND FLOOR PLAN LAYOUT
DISCONNECT HUMIDITY SENSOR
SL-01 I-2007-HV-A1-0024-SD-002 HVAC - CONDENSATE DRAIN LAYOUT
SWITCH 75x120x75 AD-9
FD-15 600x600 FD-16
F I-2007-HV-A1-0024-SD-003 HVAC - WALL OPENING AND FOUNDATION LAYOUT - SHEET 02
SA 1000x750
5540 L/s
CONTROL PANEL BOD:2400
F SA 1000x750 TS

I-2007-GT-EF-001
CONTROL PANEL 5540 L/s BDD HS
5100

HV-A1-0025 HV-A1-0026 EA 250x200 I-2007-GT-SAT-002


BOD:2400 FD-6
125 L/s This drawing and the design it covers are the property of the
I-2007-GT-IFL-001
BOD:597 M
Royal Commission for Jubail and Yanbu, Royal Commission
HVAC PENTHOUSE STL-1 at Yanbu. These drawings are loaned on the borrower's
MD-5

express agreement that they will not be reproduced, copied,


400(L)x600(W)x1000(H) 620 L/s loaned, exhibited or used except in the limited way, if any,
permitted by written consent of the Royal Commission.
SA PLENUM SAND TRAP LOUVER WITH CONTRACTORS SIGNATURE
G W1000xH900xL6755 BIRD SCREEN AND FILTER
MD-1 MD-3 AREA 0.64m2 @620 L/s 0 5 10m
M M

M M

RA PLENUM MD-2 MD-4 OA 400x350


W1000xH1650xL7480
620 L/s SCALE = 1 :100 METERS
4100

DISCONNECT
SWITCH 3D VIEW HVAC EQUIPMENT
CENTRIFUGAL UTILITY FAN I-2007-GT-PACU-001A
WITH UPWARD DISCHARGE SHOP DRAWING
I-2007-GT-EF-002A CONTROL PANEL

H I-2007-GT-EF-002B
BDD BDD
EA PLENUM
W200XH350XL1500 AD-4 AD-4 EA 250x250
4000

175 L/s DISCONNECT SWITCH


MSFD
AD-3 BOD:600
HVAC PENTHOUSE MSFD-3 00 06-Jun-24 MI SHOP DRAWING MA
CONNECTED TO WATER NO. DATE BY DESCRIPTION APPROVED BY
550(L)x400(W)x1100(H)
SUPPLY CONNECTION REVISIONS
CONTROL PANEL
J
D I-2007-GT-PACU-001B
HV-A1-0025 HV-A1-0026

A
HV-A1-0025 HV-A1-0026
PROJECT TITLE
JAZAN CITY FOR PRIMARY AND
DOWNSTREAM INDUSTRIES (JCPDI)
SEA WATER COOLING (SWC) SYSTEM - PHASE 1
DRAWING TITLE

GIS AND TRANSFORMER BUILDING -


HVAC - ROOF PLAN LAYOUT
GIS AND TRANSFORMER BUILDING - HVAC - ROOF PLAN LAYOUT DESIGNED BY: AK CONTRACTOR
1 : 100
DRAWN BY: MI

CHECKED BY: MA

PROJ. MGR.: IA

QA/QC MGR:

A/E APPROVAL: WBS NO. DRAWING NO.

R.C. APPROVAL: CONT. NO. JCPDI I-2007 I-2007-HV-A1-0025-SD-001


DATE: 06-Jun-24 SCALE 1:100 REV NO. 00