25 MIN. TYP.

25mm MINIMUM OVERLAP


OVERLAP ON ALL 6mm CLEAEANCE
TO ALL SIDES OF DAMPER
SIDES OF DAMPER MINIMUM
3
WALL DUCT 7 4 6 9
WALL DUCT 10 DUCT

.
.
.

.
‍15mm
MAX.
. 8

.
TO CLEARANCE 6mm CLEAEANCE

‍75
2 1 3
6 7 MINIMUM
5
TO

MAX. CC
‍300mm
CLEARANCE 5 FLOOR
FLOOR FLOOR 4
1 SLAB
1 ‍300mm ‍300mm ‍75
10

406 MAX.
MAX. CC 2

150 MIN.
. .

‍300mm

TYP.
2 25mm MINIMUM OVERLAP 25 MIN. TYP.

‍150mm
OVERLAP ON ALL

MAX.
TO ALL SIDES OF DAMPER
6 SIDES OF DAMPER
4 5 DUCT GIS &
4 TRANSFORMER
5 BUILDING

6 3
6 3 9 1
‍150mm ‍150mm
MAX. MAX.
1‍ 52 MIN.
2 9
406 MAX. 8
KEY PLAN
VERTICAL INSTALLATION HORIZONTAL INSTALLATION
TYP. VERTICAL INSTALLATION HORIZONTAL INSTALLATION

ITEM ITEM DESCRIPTION ITEM ITEM DESCRIPTION


1 FIRE DAMPER 1 ACTUATOR
2 SLEEVE 2 FIRE STAT
3 MOUNTING ANGLES 3 AUXILIARY OPERATING JACK SHAFT
4 FASTENER (SCREWS OR STEEL POP RIVET) 4 FIRE/SMOKE DAMPER
5 S-JOINT 5 OVER-CENTER LINK
6 STEEL DUCT 6 SLEEVE

NOTE: 7 CAULKING MATERIAL


INSTALL FIRE,DAMPER AS PER 8 MOUNTING ANGLES
MANUFACTURER'S INSTALLATION INSTRUCTION.
9 S-JOINT
10 FASTENERS (SCREWS OR STEEL POP RIVETS)

NOTE:
INSTALL COMBINATION FIRE/SMOKE DAMPER AS PER MANUFACTURERS INSTRUCTION.

1 FIRE DAMPER INSTALLATION DETAIL 2 COMBINATION FIRE / SMOKE DAMPER INSTALLATION DETAIL
NTS NTS

DUCTWORK
CLINCH LOCK
SHAFT EXTENSION FRAME: 51mm OR SCHEDULE DOOR SIZES
(38.1x12.7x3.2mm) STRUCTURAL
DOOR ‍30 HOLE OPENING ‍30
CHANNEL FRAME OR FORMED CHANNEL
ASSEMBLY (SEE SCHEDULED SIZES) WIDTH
DUCT SIZE
HEIGHT
9.5mm OR 12.7mm GASKET
DIA. SHAFTS 300
BOLT & WING 200 TO 300
180
NUT OR

‍30
DAMPER REGULATOR SET
SASH LOCK 350 TO 450 350
250
OPPOSED BLADE VOLUME
CONTROL DAMPER (SEE HANDLE, RIVETED 400
500 TO 600 400
FLOOR PLAN) ‍25
400
W/O INSULATION 650 UP
400
DUCTWORK
CLINCH LOCK
GASKET
ANGLE STOP
"x1/2" BAR INSULATION HOLE OPENING ‍50

(SEE SCHEDULED
18 GA. (1.31mm) MIN. BLADES
NOTES : 150mm)TO 225mm WIDE SIZES)

‍20
‍25
1. BACKDRAFT DAMPER SIMILAR INSTALLATION BUT LESS REGULATOR SET.
2. MULTI-BLADE DAMPERS SHALL BE USED FOR WIDTHS MORE THAN 1500. BOLT & WING
3. DAMPERS WITH BLADE LENGTHS OVER 1200 SHOULD BE MADE IN NUT OR
MULTIPLE SECTIONS OF BLADE. SASH LOCK This drawing and the design it covers are the property of the
4. FRAME NET AREA SHOULD BE EQUL TO DUCT AREA. Royal Commission for Jubail and Yanbu, Royal Commission
DOOR ASSEMBLY at Yanbu. These drawings are loaned on the borrower's
express agreement that they will not be reproduced, copied,
INSULATION loaned, exhibited or used except in the limited way, if any,
W/ INSULATION permitted by written consent of the Royal Commission.
DETAIL - DAMPER MOUNTING ACCESS DOORS IN DUCTS DETAIL CONTRACTORS SIGNATURE
3 4
NTS NTS
0 5 10m

SCALE = 1 :100 METERS

50mm THICK PRECAST SLAB MIN. 300


LARGER THAN ROOF OPENING ALL SIDES
SHOP DRAWING
CONCRETE SLAB (AS PER ARCHITECTURAL DETAIL)
SEALANT
BLOCK WORK
PLASTER
25mm THK. WOODEN
FRAME
ALUMINIUM SHEET
HEIGHT
VARIES

00 06-Jun-24 MI SHOP DRAWING MA


FLASHING NO. DATE BY DESCRIPTION APPROVED BY
REVISIONS
SEALANT

HANGER ROD AIR DUCT FIRE DAMPER


10mm AS PER LAYOUT

INSULATION INSULATION &


FINISHES AS PER

MIN.
‍150
ROOF F.F.L SPECS.
PROJECT TITLE
JAZAN CITY FOR PRIMARY AND
DOWNSTREAM INDUSTRIES (JCPDI)
DUCT
FIXTURE CLIPS SEA WATER COOLING (SWC) SYSTEM - PHASE 1
DOUBLE NUTS DRAWING TITLE
PUSH NUTS WITH WASHER SLAB GIS AND TRANSFORMER BUILDING -
ANGLE BAR HVAC - INSTALLATION DETAILS - SHEET 01
40x40x4 DESIGNED BY: AK CONTRACTOR

DRAWN BY: MI

5 RECTANGULAR DUCT HANGER DETAIL


CHECKED BY: MA
NTS
6 DUCT PENETRATION ON CONCRETE ROOF SLAB PROJ. MGR.: IA
NTS
QA/QC MGR:

A/E APPROVAL: WBS NO. DRAWING NO.

R.C. APPROVAL: CONT. NO. JCPDI I-2007 I-2007-HV-A1-0003-001


DATE: 06-Jun-24 SCALE NTS REV NO. 00