GENERAL CHARACTERISTIC
POWER SUPPLY CLIMATE CONDITIONS
SOURCE : 400/230 V, 3Ph, 4W, 60Hz MOUNTING : INDOOR
ISC : 42 kA / 3 Sec. (Main/Busbar) AMBIENT TEMPERATURE : 45°C
EARTHING SCHEMES : TNS RELATIVE HUMIDITY : 95%
BUSBAR ENCLOSURES DETAILS
TYPE : TIN BUSBAR PANEL FORM : FORM-4b (Type 6)
NEUTRAL : 100% SECTION AS PHASE DEGREE OF PROTECTION : IP-42/IK-10
EARTH : BLOKSET STANDARD ENCLOSURE MANUFACTURER : BLOKSET
: COLOR RAL:7035
AS BUILT
SUPPLY OF AUXILIARIES ENCLOSURE COLOR
CONTROL VOLTAGE : 110/230VAC (Internal) LABELS:
ORIGIN : FROM BUSBAR ENGRAVE GRAVOPLY
√ (WHITE BACKGROUND BLACK TEXT) √ ENGLISH
1 UNIT ENTRY
ESTIMATED PANEL WEIGHT INCOMING : TOP (Rear Access)
(10118 KG) OUTGOING : TOP/BOTTOM (Rear Access)
SWITCHBOARD DESIGNED FAULT LEVEL: 85KA / 1 Sec (BUSBAR) PROJECT : Dammam ISTP 200,000 M3/Day+150,000 M3/Day-
EXTERNAL SUPPLY FOR INCOMING/TIE:- 110V DC Future Extension / LV+TRX
REMARK :-
PANEL REFERENCE : MCC-02B
11
Page Page description M/D/Y Page Page description M/D/Y Page Page description M/D/Y
1 Title page / cover sheet 7/20/2022 34 Controller Control Wiring Diagram-2 7/20/2022 67 Terminal diagram XCMVA1 XCMVA4 7/25/2022
2 Table of contents : 1 - 77.d 8/10/2022 35 Controller Control Wiring Diagram-3 7/24/2022 68 Terminal diagram XCMVA4 XCP1 XCP2 XCQA1 4/7/2022
3 Legends & Symbols-1 4/7/2022 36 Resistance Heater Wiring Diagram-1 7/24/2022 69 Terminal diagram XCQA1 XCQA10 XCQAV5 XCQB6 4/10/2022
4 Legends & Symbols-2 4/7/2022 37 Resistance Heater Wiring Diagram-2 7/24/2022 70 Terminal diagram XCQB6 XCQB11 XCQB12 4/10/2022
5 Abbreviation 4/7/2022 38 Power & Control Diagram VFD-1 7/20/2022 71 Terminal diagram XCQMA XCQMB 4/7/2022
6 Panel Layout & Details 4/7/2022 39 Control Diagram VFD-1 7/24/2022 72 Terminal diagram XCQMB XCQT1 4/7/2022
7 Panel Board Name Plate 4/7/2022 40 Power & Control Diagram VFD-4 7/24/2022 73 Terminal diagram XCRA1 XCRB1 XCSAD1 XCSS 7/20/2022
8 Single Line Diagram-QMA,QMB&QT1 4/7/2022 41 Control Diagram VFD-4 7/24/2022 74 Terminal diagram XCSS XTC1 XTC2 XV1 XV2 4/7/2022
9 Single Line Diagram-1 (Section-1) 4/7/2022 42 MCCB Outgoing With (Ammeter,Toroid & Auxiliary) 8/10/2022 75 Terminal diagram XV2 XV3 XV4 7/20/2022
10 Single Line Diagram-2 (Section-1) 4/11/2022 43 Power & Control Diagram DOL-1 7/20/2022 76 Terminal diagram XV4 XVT1 XVT2 4/7/2022
11 Single Line Diagram-1 (Section-2) 7/20/2022 44 Control Diagram DOL-1 7/24/2022 77 Summarized parts list : - ZB4BVBG1+ZB4BV043 8/10/2022
12 Single Line Diagram-2 (Section-2) 4/7/2022 45 Power & Control Diagram DOL-7 7/20/2022 77.a Summarized parts list : ZB4BVBG1+ZB4BV033 - XB7NA21 7/25/2022
13 External Control Supply 110V DC 7/20/2022 46 Control Diagram DOL-7 4/12/2022 77.b Summarized parts list : METSEPM5320 - 33751 6/22/2022
14 QMA Power & Control Diagram-1 7/20/2022 47 Power & Control Diagram DOL-8 7/20/2022 77.c Summarized parts list : 33753 - 50441 7/25/2022
15 QMA Power & Control Diagram-2 7/24/2022 48 Control Diagram DOL-8 4/12/2022 77.d Summarized parts list : ATV630D22N4 - 48483 6/22/2022
16 QMA Power & Control Diagram-3 7/20/2022 49 Power & Control Diagram DOL-9 7/20/2022
17 QT1 Power & Control Diagram 7/24/2022 50 Control Diagram DOL-9 7/24/2022
18 QMB Power & Control Diagram-1 7/20/2022 51 MCCB Outgoing With (Torid & Auxiliary)-QA1 7/24/2022
19 QMB Power & Control Diagram-2 7/20/2022 52 MCCB Outgoing With Auxiliary - QA10 4/12/2022
20 QMB Power & Control Diagram-3 7/20/2022 53 MCCB Outgoing With (Torid & Auxiliary)-QB6 7/20/2022
21 QMA Trans. Protec. Relay DMCR 3.0 Wiring Diag. 4/7/2022 54 MCCB Outgoing With (Ammeter,Toroid & Auxiliary)-QB11 8/10/2022
22 QMB Trans. Protec. Relay DMCR 3.0 Wiring Diag. 4/7/2022 55 MCCB Outgoing With (Ammeter & Auxiliary)-QB12 8/10/2022
23 Wiring Diagram Micrologic 6.E (QMA&QMB) 7/24/2022 56 Terminal diagram X3 XABC1 XAC1 XBBC1 4/7/2022
24 Wiring Diagram Micrologic 6.E (QT1) 7/20/2022 57 Terminal diagram XBC1 XCA XCAD1 4/12/2022
25 Local Reset Control Wiring Diagram 8/10/2022 58 Terminal diagram XCAD1 XCAD7 XCAD8 7/25/2022
26 Control Wiring Diagram (QMA) 7/24/2022 59 Terminal diagram XCAD8 XCAD9 7/25/2022
27 Control Auxiliary Wiring Diagram (QMA) 7/20/2022 60 Terminal diagram XCAD9 XCAV1 4/7/2022
30 Control Wiring Diagram-QT1 7/24/2022 63 Terminal diagram XCE2 XCMA1 XCMAD1 4/12/2022
31 Control Wiring Diagram M-R-A 7/20/2022 64 Terminal diagram XCMAD1 XCMAD7 XCMAD8 4/12/2022
32 Ethernet Switch Network Layout (BUS-A & B) 7/20/2022 65 Terminal diagram XCMAD8 XCMAD9 4/12/2022
33 Controller Control Wiring Diagram-1 7/24/2022 66 Terminal diagram XCMB1 XCMT1 XCMVA1 7/20/2022
BREAK CONTACT DELAYED WHEN WITHDRAWABLE DEVICE DEVICE FOR RESTRICTING MOVEMENT
RELEASING
Q BLOCKED POSITION
ABBREVIATION
side B
side A
0 1 2 3 4 5 6 7 8 9
250
INCOMING-1 INCOMING-2
L1-L2-L3-N-PE L1-L2-L3-N-PE
VMR VMR
VT VT
MOTOR
MECHANISM
TIE BREAKER
RATING: 3200 Amps 4pole
L1-L2-L3-N-PE
L1-L2-L3-N-PE
(PS1) (PS2)
9.0 11.0
SECTION-1 SECTION-2
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 GV2
1 400/630
1 400/630
PE
-XPAV1 1,2,3
PE
-XPAV2 1,2,3
PE
-XPAV3 1,2,3
PE PE
-XPA1 1,2,3 PE
-XPA2 1,2,3 PE PE PE
M M M M M
3~ 3~ 3~ 3~ 3~
RATING: 50 Amps 3pole RATING: 50 Amps 3pole RATING: 50 Amps 3pole RATING: 10 Amps 3pole RATING: 500 Amps 3pole RATING: 500 Amps 3pole
CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: GV2-L14 CB TYPE: NSX 630H MCCB D.out CB TYPE: NSX 630H MCCB D.out
CIRCUIT
BREAKER TRIP UNIT: Magnetic TRIP UNIT: Magnetic TRIP UNIT: Magnetic TRIP UNIT: Magnetic TRIP UNIT: Magnetic TRIP UNIT: Magnetic
kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 100kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC
CABLE LENGTH 273 METER 273 METER 99 METER - 210 METER 210 METER 50 METER 50 METER
CABLE SIZE (mm2) 3CX25 mm²+1CX16 mm² 3CX25 mm²+1CX16 mm² 3CX25 mm²+1CX16 mm² - 3CX2.5 mm²+1CX4 mm² 3CX2.5 mm²+1CX4 mm² 2set(4Cx185 mm²) 2set(4Cx185 mm²)
CABLE TAG MCC2B-P001 MCC2B-P003 MCC2B-P004 - MCC2B-P021 MCC2B-P022 MCC2B-P029 MCC2B-P030
LOAD ANOXIC RECYCLE PUMP [D] ANOXIC RECYCLE PUMP [F] ANOXIC RECYCLE PUMP [J] SECONDARY CLARIFIER SECONDARY CLARIFIER IFAS ZONE-AIR BLOWER [D] IFAS ZONE-AIR BLOWER [D]
DESCRIPTION (17 KW) (17 KW) (17 KW) - SCRAPPER [C] -DRIVE1 (1.1 KW) SCRAPPER [C] -DRIVE2 (1.1 KW) VFD PANEL -FEEDER 1 (220 KW) VFD PANEL -FEEDER 2 (220 KW)
PROTECTION TYPE 1 X Temperature and leakage 1 X Temperature and leakage 1 X Temperature and leakage - Torque Monitoring Torque Monitoring Motor Temperature Sensor Motor Temperature Sensor
relay type ABS CA 462 relay type ABS CA 462 relay type ABS CA 462
9.8 / (PS1)
R R R R R R R R R
Y Y Y Y Y Y Y Y Y
B B B B B B B B B
1 1 1 1 1 1
-CLMA1 -CLMA2 -CLMA3 -CLMA4 -CLMA5 -CLMA6 1 1 1
Ie-32A,<=100kA Ie-32A,<=100kA Ie-32A,<=100kA Ie-32A,<=100kA Ie-32A,<=100kA Ie-32A,<=100kA
-QAD7 -RHDA7 -QAD8 -RHDA8 -QAD9 -RHDA9
2 2 2 2 2 2
1 1 1 1 1 1 46.1 2 Analog 48.1 2 Analog 50.1 2
-RHDA1 -RHDA2 -RHDA3 -RHDA4 -RHDA5 -RHDA6
46.4 1 Ammeter 48.5 1 Ammeter 50.5
-QAD1 -QAD2 -QAD3 -QAD4 -QAD5 -QAD6 -KAD7 -KAD8 1 1
44.1 1 2 Analog 1 2 Analog 1 2 Analog 1 2 Analog 1 2 Analog 1 2 Analog Contactor Contactor -KADF1 -KADR1
44.4 Ammeter Ammeter Ammeter Ammeter Ammeter Ammeter 09 Amps 2 09 Amps 2 Contactor Contactor
-KAD1 -KAD2 -KAD3 -KAD4 -KAD5 -KAD6 09 Amps 2 09 Amps 2
Contactor 2 Contactor 2 Contactor 2 Contactor 2 Contactor 2 Contactor 2
25 Amps 25 Amps 25 Amps 25 Amps 25 Amps 25 Amps Analog
-Toroid Ammeter
-Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid
CoilAD1 CoilAD2 CoilAD3 CoilAD4 CoilAD5 CoilAD6 CoilAD7 CoilAD8 CoilAD9
Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm
65 Amps 65 Amps 65 Amps 65 Amps 65 Amps 65 Amps 65 Amps 65 Amps 65 Amps
PE
-XPAD1 1,2,3 PE
-XPAD2 1,2,3 PE
-XPAD3 1,2,3 PE
-XPAD4 1,2,3 PE
-XPAD5 1,2,3 PE
-XPAD6 1,2,3 PE
-XPAD7 1,2,3 PE
-XPAD8 1,2,3 PE
-XPAD9 1,2,3 PE
M M M M M M M M M
3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
RATING: 17-23 Amps 3pole RATING: 17-23 Amps 3pole RATING: 17-23 Amps 3pole RATING: 17-23 Amps 3pole RATING: 17-23 Amps 3pole RATING: 17-23 Amps 3pole RATING: 6-10 Amps 3pole RATING: 6-10 Amps 3pole RATING: 1.6-2.5 Amps 3pole
CB TYPE: GV2-P21 CB TYPE: GV2-P21 CB TYPE: GV2-P21 CB TYPE: GV2-P21 CB TYPE: GV2-P21 CB TYPE: GV2-P21 CB TYPE: GV2-P14 CB TYPE: GV2-P14 CB TYPE: GV2-P07
CIRCUIT
BREAKER
TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC
kA RATING: 50kA/415V-IEC kA RATING: 50kA/415V-IEC kA RATING: 50kA/415V-IEC kA RATING: 50kA/415V-IEC kA RATING: 50kA/415V-IEC kA RATING: 50kA/415V-IEC kA RATING: 130kA/415V-IEC kA RATING: 130kA/415V-IEC kA RATING: 130kA/415V-IEC
CABLE SIZE
(mm2) 3CX16 mm²+1CX16 mm² 3CX16 mm²+1CX16 mm² 3CX10 mm²+1CX10 mm² 3CX16 mm²+1CX16 mm² 3CX16 mm²+1CX16 mm² 3CX10 mm²+1CX10 mm² 3CX10 mm²+1CX10 mm² 3CX10 mm²+1CX10 mm² 3CX2.5 mm²+1CX4 mm²
LOAD ANAEROBIC TANK MIXER [D] ANAEROBIC TANK MIXER [F] ANAEROBIC TANK MIXER [J] ANOXIC TANK MIXER [D] (6.2 KW) ANOXIC TANK MIXER [F] (6.2 KW) ANOXIC TANK MIXER [J] (6.2 KW) SEWAGE PUMP -A (2.7 KW) PLANT AIR COMPRESSOR [C] SECONDARY CLARIFIER [A]-
DESCRIPTION (6.2 KW) (6.2 KW) (6.2 KW) (4 KW) TELESCOPIC VALVE (0.55 KW)
TAG NUMBER M -102D M -102F M -102J M -103D M -103F M -103J SP-001A AC-102C MTV-102C
MOTOR TYPE
(DRY / SUBMERSIBLE)
SUBMERSIBLE SUBMERSIBLE SUBMERSIBLE SUBMERSIBLE SUBMERSIBLE SUBMERSIBLE SUBMERSIBLE DRY DRY
PROTECTION TYPE Leakage Sensor With Relay Leakage Sensor With Relay Leakage Sensor With Relay Leakage Sensor With Relay Leakage Sensor With Relay Leakage Sensor With Relay 1 X Temperature switch + - Positioner with wiring details
Leak Sensor CA462
(PS1) /
R R R R R R R R R R R
Y Y Y Y Y Y Y Y Y Y Y
B B B B B B B B B B B
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
-QA1 -RHA1 -QA2 -RHA2 -QA3 -RHA3 -QA4 -RHA4 -QA5 -RHA5 -QA6 -RHA6 -QA7 -RHA7 -QA8 -RHA8 -QA9 -RHA9 -QA10 -RHA10 -QA11 -RHA11
2 2 2 2 2 2 2 2 2 2 2
-Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid
CoilQA1 CoilQA2 CoilQA3 CoilQA4 CoilQA5 CoilQA6 CoilQA7 CoilQA8 CoilQA9 CoilQA10
Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm
65 Amps 65 Amps 65 Amps 65 Amps 65 Amps 65 Amps 65 Amps 65 Amps 65 Amps 65 Amps
PE PE PE PE PE PE PE PE PE PE PE
RATING: 50 Amps 3pole RATING: 50 Amps 3pole RATING: 50.4 Amps 3pole RATING: 44.1 Amps 3pole RATING: 40 Amps 3pole RATING: 16 Amps 3pole RATING: 17.5 Amps 3pole RATING: 16 Amps 3pole RATING: 22.4 Amps 3pole RATING: 200 Amps 3pole RATING: 40 Amps 3pole
CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 250H MCCB CB TYPE: NSX 100H MCCB
CIRCUIT
BREAKER
TRIP UNIT: TM63D TRIP UNIT: TM63D TRIP UNIT: TM63D TRIP UNIT: TM63D TRIP UNIT: TM50D TRIP UNIT: TM16D TRIP UNIT: TM25D TRIP UNIT: TM16D TRIP UNIT: TM32D TRIP UNIT: TM250D TRIP UNIT: TM50D
kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC
CABLE SIZE
(mm2) 4Cx35 mm²+1Cx16 mm² 4Cx35 mm²+1Cx16 mm² 4Cx16 mm² 4Cx50 mm² 4Cx50 mm²+1Cx25 mm² 4Cx2.5 mm² 4Cx16 mm²+1Cx16 mm² 4Cx10 mm²+1Cx10 mm² 4Cx35 mm²+1Cx16 mm² 3Cx185 mm²+1Cx95 mm² 4Cx50 mm²+1Cx25 mm²
LOAD BIOLOGICAL TREATMENT AREA BIOLOGICAL TREATMENT AREA AC UPS FOR BIOLOGICAL TREATMENT AC UPS FOR SCADA (ADMIN WAREHOUSE AND WORKSHOP - SECONDARY CLARIFIER GUARD ROOM (SOUTH) - WAREHOUSE AND WORKSHOP - CRANE STREET LIGHTING FEEDER FEEDER OF CAPACITOR BANK FENCE LIGHTING -
DESCRIPTION POWER DB3 - FEEDER [1] POWER DB4 - FEEDER [1] SUBSTATION - MAIN FEEDER BUILDING) - MAIN FEEDER FEEDER BUILDING SERVICES DB SCRAPPER [C] -BRUSH DRIVE BUILDING SERVICES DB PILLER [1] BUS-A [100 KVAR] FEEDER FILLER [1]
TAG NUMBER PDB-21C-F1 PDB-21D-F1 AC UPS-2-F1 AC UPS-SCADA-F1 LP-WWBB SCR-102C3 LP-GDR1 CT-111 SLFP-1 PFCU-2B1 FLFP-1
MOTOR TYPE
(DRY / SUBMERSIBLE)
N.A. N.A. N.A. N.A. N.A. DRY N.A. N.A. N.A. N.A. N.A.
8.7 / (PS2)
R R R R R N N R R R R R
Y Y Y Y Y R Y Y Y Y Y Y
B B B B B B B B B B
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 400/630
1 400/630
-QB1 -RHB1 -QB2 -RHB2 -QB3 -RHB3 -QB4 -RHB4 -QB5 -RHB5 -QB6 -RHB6 -QB7 -RHB7 -QB8 -RHB8 -QB9 -RHB9 -QB10 -RHB10 -QB11 -RHB11 -QB12 -RHB12
2 2 2 2 2 2 2 2 2 2 2 2
-Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid -Toroid
CoilQB1 CoilQB2 CoilQB3 CoilQB4 CoilQB5 CoilQB6 CoilQB7 CoilQB8 CoilQB9 CoilQB10 CoilQB11
Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 30 mm Dia 80 mm Dia 80 mm Dia 120 mm Dia 30 mm Dia 30 mm Dia 200 mm
65 Amps 65 Amps 65 Amps 65 Amps 65 Amps 160 Amps 100 Amps 250 Amps 65 Amps 65 Amps 400 Amps
PE
PE PE PE PE PE PE PE PE PE PE PE PE
RATING: 16 Amps 3pole RATING: 32 Amps 3pole RATING: 32 Amps 3pole RATING: 50 Amps 3pole RATING: 50 Amps 3pole RATING: 100 Amps 3pole RATING: 100 Amps 3pole RATING: 140 Amps 3pole RATING: 40 Amps 3pole RATING: 63 Amps 3pole RATING: 250 Amps 3pole RATING: 300 Amps 3pole
CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 250H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 400H MCCB D.out CB TYPE: NSX 400H MCCB D.out
CIRCUIT
BREAKER
TRIP UNIT: TM16D TRIP UNIT: TM40D TRIP UNIT: TM32D TRIP UNIT: TM63D TRIP UNIT: TM63D TRIP UNIT: TM100D TRIP UNIT: TM100D TRIP UNIT: TM200D TRIP UNIT: TM50D TRIP UNIT: TM63D TRIP UNIT: Micrologic 2.3 TRIP UNIT: Micrologic 2.3
kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC
CABLE SIZE
(mm2) 4Cx2.5 mm² 4Cx25 mm²+1Cx16 mm² - 4Cx35 mm²+1Cx16 mm² 4Cx35 mm²+1Cx16 mm² 3Cx25 mm² 3Cx150 mm² 4Cx240 mm²+1Cx120 mm² 4Cx25 mm²+1Cx16 mm² - 2set(4Cx185 mm²+2x185 mm²) 2set(3Cx185 mm²+1Cx185 mm²)
LOAD SECONDARY CLARIFIER SECONDARY CLARIFIER - SPARE (32A) BIOLOGICAL TREATMENT AREA BIOLOGICAL TREATMENT AREA AC UPS FOR BIOLOGICAL TREATMENT AC UPS FOR SCADA (ADMIN SECURITY BUILDING - BUILDING BIOLOGICAL TANK - LIGHTING DB SPARE (63A) ADMININSTRATION BUILDING - FEEDER OF CAPACITOR BANK
DESCRIPTION SCRAPPER [D] -BRUSH DRIVE LIGHTING DB POWER DB3 - FEEDER [2] POWER DB4 - FEEDER [2] SUBSTATION - BYPASS FEEDER BUILDING) - BYPASS FEEDER SERVICES DB BUILDING SERVICES DB BUS-B [150 KVAR]
TAG NUMBER SCR-102D3 LO-SCTT SPARE PDB-21C-F2 PDB-21D-F2 AC UPS-2-F2 AC UPS-SCADA-F2 MDB-SB LO-BLTT SPARE MDB-ADMN PFCU-2B2
MOTOR TYPE
(DRY / SUBMERSIBLE)
DRY N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A.
(PS2) / 12.1
R R R R R R R R R
Y Y Y Y Y Y Y Y Y
B B B B B B B B B
1 1 1 1 1 1
-CLMB1 -CLMB2 -CLMB3 -CLMB4 -CLMB5 -CLMB6 1 1 1
Ie-32A,<=100kA Ie-32A,<=100kA Ie-32A,<=100kA Ie-32A,<=100kA Ie-32A,<=100kA Ie-32A,<=100kA
-QBD7 -RHDB7 -QBD8 -RHDB8 -QBD9 -RHDB9
2 2 2 2 2 2
2 Analog 2 Analog 2
1 1 1 1 1 1 Ammeter Ammeter
-QBD1 -RHDB1 -QBD2 -RHDB2 -QBD3 -RHDB3 -QBD4 -RHDB4 -QBD5 -RHDB5 -QBD6 -RHDB6 1 1
-XPBD1 1,2,3 PE
-XPBD2 1,2,3 PE
-XPBD3 1,2,3 PE
-XPBD4 1,2,3 PE
-XPBD5 1,2,3 PE
-XPBD6 1,2,3 PE
-XPBD7 1,2,3 PE
-XPBD8 1,2,3 PE
-XPBD9 1,2,3 PE
M M M M M M M M M
3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
RATING: 17-23 Amps 3pole RATING: 17-23 Amps 3pole RATING: 17-23 Amps 3pole RATING: 17-23 Amps 3pole RATING: 17-23 Amps 3pole RATING: 17-23 Amps 3pole RATING: 6-10 Amps 3pole RATING: 6-10 Amps 3pole RATING: 1.6-2.5 Amps 3pole
CB TYPE: GV2-P21 CB TYPE: GV2-P21 CB TYPE: GV2-P21 CB TYPE: GV2-P21 CB TYPE: GV2-P21 CB TYPE: GV2-P21 CB TYPE: GV2-P14 CB TYPE: GV2-P14 CB TYPE: GV2-P07
CIRCUIT
BREAKER
TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC TRIP UNIT: MAGNETIC
kA RATING: 50kA/415V-IEC kA RATING: 50kA/415V-IEC kA RATING: 50kA/415V-IEC kA RATING: 50kA/415V-IEC kA RATING: 50kA/415V-IEC kA RATING: 50kA/415V-IEC kA RATING: 130kA/415V-IEC kA RATING: 130kA/415V-IEC kA RATING: 130kA/415V-IEC
CABLE SIZE
(mm2) 3CX16 mm²+1CX16 mm² 3CX10 mm²+1CX10 mm² 3CX10 mm²+1CX10 mm² 3CX16 mm²+1CX16 mm² 3CX10 mm²+1CX10 mm² 3CX10 mm²+1CX10 mm² 3CX10 mm²+1CX10 mm² 3CX10 mm²+1CX10 mm² 3CX2.5 mm²+1CX4 mm²
LOAD ANAEROBIC TANK MIXER [E] ANAEROBIC TANK MIXER [K] ANAEROBIC TANK MIXER [L] ANOXIC TANK MIXER [E] (6.2 KW) ANOXIC TANK MIXER [K] (6.2 KW) ANOXIC TANK MIXER [L] SEWAGE PUMP -B (2.7 KW) PLANT AIR COMPRESSOR [D] SECONDARY CLARIFIER [D]-
DESCRIPTION (6.2 KW) (6.2 KW) (6.2 KW) (6.2 KW) (4 KW) TELESCOPIC VALVE (0.55 KW)
TAG NUMBER M -102E M -102K M -102L M -103E M -103K M -103L SP-001B AC-102D MTV-102D
MOTOR TYPE
(DRY / SUBMERSIBLE)
SUBMERSIBLE SUBMERSIBLE SUBMERSIBLE SUBMERSIBLE SUBMERSIBLE SUBMERSIBLE SUBMERSIBLE DRY DRY
PROTECTION TYPE Leakage Sensor With Relay Leakage Sensor With Relay Leakage Sensor With Relay Leakage Sensor With Relay Leakage Sensor With Relay Leakage Sensor With Relay 1 X Temperature switch + - Positioner with wiring details
Leak Sensor CA462
1 400/630
1 400/630
1 100/250 AF
1 100/250 AF
1 100/250 AF
1 GV2
PE
PE PE
-XPBV1 1,2,3
PE
-XPBV2 1,2,3
PE
-XPBV3 1,2,3
PE PE
-XPB1 1,2,3 PE
-XPB2 1,2,3 PE
M M M M M
3~ 3~ 3~ 3~ 3~
RATING: 500 Amps 3pole RATING: 500 Amps 3pole RATING: 50 Amps 3pole RATING: 50 Amps 3pole RATING: 50 Amps 3pole RATING: 10 Amps 3pole
CB TYPE: NSX 630H MCCB D.out CB TYPE: NSX 630H MCCB D.out CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: NSX 100H MCCB CB TYPE: GV2-L14
CIRCUIT
BREAKER TRIP UNIT: Magnetic TRIP UNIT: Magnetic TRIP UNIT: Magnetic TRIP UNIT: Magnetic
TRIP UNIT: Magnetic TRIP UNIT: Magnetic
kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 70kA/415V-IEC kA RATING: 100kA/415V-IEC
CABLE LENGTH 50 METER 50 METER 273 METER 99 METER 99 METER - 189 METER 189 METER
CABLE SIZE (mm2) 2set(4Cx185 mm²) 2set(4Cx185 mm²) 3CX25 mm²+1CX16 mm² 3CX25 mm²+1CX16 mm² 3CX25 mm²+1CX16 mm² - 3CX2.5 mm²+1CX4 mm² 3CX2.5 mm²
CABLE TAG MCC2B-P031 MCC2B-P032 MCC2B-P002 MCC2B-P005 MCC2B-P006 - MCC2B-P025 MCC2B-P026
LOAD IFAS ZONE-AIR BLOWER [E] IFAS ZONE-AIR BLOWER [E] ANOXIC RECYCLE PUMP [E] ANOXIC RECYCLE PUMP [K] ANOXIC RECYCLE PUMP [L] SECONDARY CLARIFIER SECONDARY CLARIFIER
DESCRIPTION VFD PANEL -FEEDER 1 (220 KW) VFD PANEL -FEEDER 2 (220 KW) (17 KW) (17 KW) (17 KW) - SCRAPPER [D] -DRIVE1 (1.1 KW) SCRAPPER [D] -DRIVE2 (1.1 KW)
PROTECTION TYPE Motor Temperature Sensor Motor Temperature Sensor 1 X Temperature and leakage 1 X Temperature and leakage 1 X Temperature and leakage - Torque Monitoring Torque Monitoring
relay type ABS CA 462 relay type ABS CA 462 relay type ABS CA 462
TITLE : Single Line Diagram-2 (Section-2) EQ NO : EQ200489/02-R12 Page No:
REV 10
SETRAA AL AMAL 12
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
3 6 9 12
1 3 1 3
-QDCM1 -QDCM2
C60H-DC 2 4 C60H-DC 2 4
2Pole MCB 2Pole MCB
10 Amps 1 10 Amps
2
10 13
1
1 3 R1 R3
-KDC1
13.0 2 4 R2 R4
4
A1
-KDC1 2
20 Amps A2 7
110 V DC
1 2 13.1
3 4 13.1
R1 R2 13.2 4 4 4 4 4 4
R3 R4 13.2
7 7 7 7 7 7
-XABC1 1 2 -XBBC1 1 2
-XAC1 1 2 -XBC1 1 2 -XTC1 1 2 -XTC2 1 2
4 7 4 7 4 7 4 7 4 7 7 4
x1
1 3 1 3 1 3 1 3 1 3 1 3 -HDC DC POWER
Red x2 AVAILABLE
-QDCE1 -QDCE2 -QCEA1 -QCEB1 -QCET1 -QCET2
C60H-DC 2 4 C60H-DC 2 4 C60H-DC 2 4 C60H-DC 2 4 C60H-DC 2 4 C60H-DC 2 4
2Pole MCB 2Pole MCB 2Pole MCB 2Pole MCB 2Pole MCB 2Pole MCB
04 Amps 04 Amps 10 Amps 10 Amps 10 Amps 04 Amps
18 -QDC1
-PS1 20 22
(+) (-) 1 2
0V DC / 23.3
AMF1+ BMF1+ (AA1) (BA1) (TA1) 110 VDC
14.9 20.9 26.0 28.0 30.0
21 23
(-) 24 VDC (+) 3 4
24V DC / 23.3
AMF1- BMF1- (AA2) (BA2) (TA2) Power supply module
C60H-DC
Input 110V DC/
14.9 20.9 26.0 28.0 30.0 Output 24VDC 2Pole MCB
04 Amps
N1.1 / 15.0
L1.1 / 15.0
L2.1 / 15.0
-EPR1 (QMA)
26.5
BUS-A L3.1 / 15.0 27.5
P3T32-CGATA-AAFFA-BBAAA
32 REL52504 Easergy
-CTA1 P2 S2
3200/1A
25VA 5P20 33 -XC1 38
P1 S1 1 2.5 mm² 8F101
8F102 IL1
32 2
8F103 (+) 5
-CTA2 P2 S2
3200/1A IL2 1C102 AMF1+ / 13.1
8F104
25VA 5P20 34 40
P1 S1 3 2.5 mm²
(-) 8
8F105 1C101 AMF1- / 13.1
32 4 IL3
8F106
-CTA3 P2 S2
3200/1A
25VA 5P20 35 41 8F107 PE2
P1 S1 5 2.5 mm²
8F108 5A Io1
39
6 2.5 mm² 8F109 1A
PE1
8F110
7
8F111 1A Io2
(N1.A)
(L1.A)
(L2.A)
(L3.A)
EPR1 / 32.3
14.1
14.1
14.1
14.2
TO ETHERNET
25 27 29 43
-XV1 4T101 SWITCH
7 5 2 1 1
4T102 5A I`L1
-FVM1 1 3 5
4T103 1A
Fuse 04A
3 Pole TR-2B1
2 4 6 44
(2000KVA) -XV1 4T104
26 28 30
2
6 4 3 4T105 5A I`L2
14.4 / (L1.A)
14.4 / (L2.A)
14.4 / (L3.A)
/ (PE.A)
CTNA S2
3200/1A PE
25VA 5P20
S1 2.5 mm²
4x300 mm²
PE
POWER METER
METSEPM5320
50
P2 S2
PM1 (QMA)
-CTA4
0~3200Amps 51 -XC2 54 58
P1 S1 1 -AA1 10
MODEBUS TCP
(MCT-127/3200A)
x1 A x2 I1+
87654321
NOTE 0~3200 Amps
1. EXTENDED TERMINAL BLOCKS 1 AND 2
50 2 TO BE SHORTED BEFORE REMOVING PM1 / 32.3
THE CABLES ON THE CT OR ON THE
P2 S2
MAIN TERMINAL BLOCKS TO ETHERNET
-CTA5 SWITCH
0~3200Amps 52 55 57 59
(MCT-127/3200A) P1 S1 3 XCP1 1 2 XCP1 -AA2 12
TO PFC x1 A x2 I2+
0~3200 Amps
4 11
50 I1-
P2 S2
-CTA6
0~3200Amps 53 56 60
(MCT-127/3200A) P1 S1 5 -AA3 14
x1 A x2 I3+
0~3200 Amps 12
I2-
6
47
4
7 16.9 / VN1 VN
46 13
1 I3-
PE
16.9 / VR1 V1
48
2
16.9 / VY1 V2
49
3
16.9 / VB1 V3
47
1050 9
N(-)
46
8
L(+)
-Voltmeter1
0~500 Volt
x1 x2
V
46
61 62
48
49
(2) (12)
* DO NOT REMOVE FACTORY MOUNTED JUMPERS.
46
(1)
48
(3)
49
(5) -VSS1
Voltmeter Selector
47 Switch 7-position
(11)
14.9 / VN2
46
14.9 / VB2
14.3 / L2.1
14.3 / L3.1
TITLE : QMA Power & Control Diagram-2 EQ NO : EQ200489/02-R12 Page No:
REV 10
SETRAA AL AMAL 15
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
46 46
-QCA1 VR1 3 4 -XV2 2
06 Amps 4pole
iC60L MCB
25 63 48 48
1 2 5 8 VY1 5 6 -XV2 3
400/R3 0
27 64 66 49 49
3 4 9 VB1 7 8 -XV2 4
110/R3
29 65
5 6
0
7 8 7
-XV2 5
SA1 / 33.0
TO BUSCOUPLER
SYNCHROCHECK
46
PE -XV2 6
SA2 / 33.0
-VT2 48
-XV2 7
2 VT:400/R3:110/R3 SA3 / 33.0
0
30VA, CL.0.5/1P 49
-XV2 8
SA4 / 33.0
5 8
400/R3 0
67
9
110/R3
N1
PE
-VT3
2 VT:400/R3:110/R3
0
30VA, CL.0.5/1P
5 8
400/R3 0
68
9
110/R3
15.1 / N1.1 7
15.1 / L1.1
15.1 / L2.1 PE PE PE
15.1 / L3.1
N1.2 / 18.0
FROM BUS-B
L1.2 / 18.0
L2.2 / 18.0
POWER (BUS-B)
021
(N1.2) / 25.0
020
(L1.2) / 25.0
022
(L2.2) / 53.0
023
(L3.2) / 53.0
1 3 5 7
MOTOR
-QT1 MECHANISM
2 4 6 8
POWER (BUS-A)
011
(N1.1) / 25.0
010
(L1.1) / 25.0
012
(L2.1) / 38.0
013
(L3.1) / 38.0
16.0 / N1.1
BUS-A
FROM BUS-A
16.1 / L1.1
16.1 / L2.1
16.1 / L3.1
N1.2 / 19.0
75 -HB1
x2 x1
L1.2 / 19.0 RED
76 -HB2
L2.2 / 19.0 x2 x1
YELLOW
L3.2 / 19 77 -HB3
x2 x1
BUS-B 110V BLUE
-VT4 -QCB2
2 VT:400/R3:110/R3
0 06 Amps 4pole
30VA, CL.0.5/1P iC60L MCB
(N2)
VN1 1 2 -XV3 1
VN1 / 19.5
79 79
-QCB1 VR1 3 4 -XV3 2
06 Amps 4pole VR1 / 19.5
iC60L MCB
(69) 72 80 80
1 2 5 8 VY1 5 6 -XV3 3
400/R3 0 VY1 / 19.5
(70) 73 75 81 81
3 4 9 VB1 7 8 -XV3 4
110/R3 VB1 / 19.5
(71) 74
5 6
(78)
(00)
7 8 7
-XV3 5
SB1 / 33.0
TO BUSCOUPLER
SYNCHROCHECK
79
PE -XV3 6
SB2 / 33.0
-VT5 80
-XV3 7
2 VT:400/R3:110/R3 SB3 / 33.0
1 3 5 7
0
30VA, CL.0.5/1P (000) 81
-QMB MOTOR -XV3 8
MECHANISM SB4 / 33.0
2 4 6 8
5 8
400/R3 0
76
9
110/R3
(N2)
PE
-VT6
2 VT:400/R3:110/R3
0
30VA, CL.0.5/1P
5 8
400/R3 0
77
9
110/R3
17.8 / N1.2 7
17.8 / L1.2
17.8 / L2.2 PE PE PE
17.8 / L3.2
N1.2 / 20.0
L1.2 / 20.0
L2.2 / 20.0
L3.2 / 20.0
POWER METER
METSEPM5320
82
P2 S2
-PM2 (QMB)
-CTB4
0~3200Amps 83 -XC4 86 90
P1 S1 1 -BA1 10
MODEBUS TCP
(MCT-127/3200A)
x1 A x2 I1+
87654321
NOTE 0~3200 Amps
1. EXTENDED TERMINAL BLOCKS 1 AND 2
82 2 TO BE SHORTED BEFORE REMOVING PM2 / 32.8
THE CABLES ON THE CT OR ON THE
P2 S2
MAIN TERMINAL BLOCKS TO ETHERNET
-CTB5 SWITCH
0~3200Amps 84 87 89 91
(MCT-127/3200A) P1 S1 3 -XCP2 1 2 -XCP2 -BA2 12
TO PFC x1 A x2 I2+
0~3200 Amps
4 11
82 I1-
P2 S2
-CTB6
0~3200Amps 85 88 92
(MCT-127/3200A) P1 S1 5 -BA3 14
x1 A x2 I3+
0~3200 Amps 12
I2-
6
78
4
7 18.9 / VN1 VN
79 13
1 I3-
-PE1
18.9 / VR1 V1
80
2
18.9 / VY1 V2
81
3
18.9 / VB1 V3
78
9
N(-)
79
8
L(+)
N9
-Voltmeter2
0~500 Volt
x1 x2
V
79
93 94
80
81
(2) (12)
* DO NOT REMOVE FACTORY MOUNTED JUMPERS.
79
(1)
80
(3)
81
(5) -VSS2
Voltmeter Selector
Switch 7-position
(11)
VN2 / 20.9
79
VR2 / 20.9
18.3 / N1.2 80
VY2 / 20.9
18.3 / L1.2 81
VB2 / 20.9
18.3 / L2.2
19.2 / N1.2
19.2 / L1.2
19.2 / L2.2
19.2 / L3.2
EPR2 (QMB)
28.5
29.5
P3T32-CGATA-AAFFA-BBAAA
100 REL52504 Easergy
-CTB1 P2 S2
3200/1A
25VA 5P20 101 -XC3 106
P1 S1 1 2.5 mm² 8F101
8F102 IL1
100 2
8F103 (+) 11
-CTB2 P2 S2
3200/1A IL2 1C102 BMF1+ / 13.2
8F104
25VA 5P20 102 108
P1 S1 3 2.5 mm²
(-) 14
8F105 1C101 BMF1- / 13.2
100 4 IL3
8F106
-CTB3 P2 S2
3200/1A
25VA 5P20 103 109 8F107 PE2
P1 S1 5 2.5 mm²
8F108 5A Io1
107
6 2.5 mm² 8F109 1A
PE1
8F110
7
8F111 1A Io2
69 70 71
TO BUSWAY TRANSFORMER
EPR2 / 32.8
(N2.B)
(L1.B)
(L2.B)
(L3.B)
20.1
20.1
20.1
20.1
-FVM2 1 3 5
TO ETHERNET
Fuse 04A 111
3 Pole
-XV4 4T101 SWITCH
2 4 6 7 5 2 1 1
4T102 5A I`L1
96 97 98
4T103 1A
-XCRB1 1 2
VMR STATUS L1 L2 L3
TO REMOTE (PLC) 13.8KV INCOMING
14.2 / PE PE / 42.6 POWER SUPPLY
2.5 mm²
-CTNB S2
20.3 / (N2.B)
20.4 / (L1.B)
20.4 / (L2.B)
20.4 / (L3.B)
/ (PE.B)
3200/1A PE
25VA 5P20
S1 2.5 mm²
4x300 mm²
PE
TITLE : QMB Power & Control Diagram-3 EQ NO : EQ200489/02-R12 Page No:
INCOMING-2 (NEUTRAL EARTHING REV 10
SETRAA AL AMAL 20
FROM BUSWAY JOB ORDER : JO200287-R06
ELECTRODE) PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
44 41 42 34 31 32 24 21 22 14 11 12
TITLE : QMA Trans. Protec. Relay DMCR 3.0 EQ NO : EQ200489/02-R12 Page No:
Wiring Diag. REV 10
SETRAA AL AMAL 21
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
44 41 42 34 31 32 24 21 22 14 11 12
TITLE : QMB Trans. Protec. Relay DMCR 3.0 EQ NO : EQ200489/02-R12 Page No:
Wiring Diag. REV 10
SETRAA AL AMAL 22
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
INCOMING-1 INCOMING-2
N1 L1.1 L2.1 L3.1 N2 L1.2 L2.2 L3.2
VN
VN
V3
V3
V1
V2
V1
V2
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
1 3 5 7 1 3 5 7
QMA QMB
2 4 6 8 2 4 6 8
I I
Micrologic 6.E Micrologic 6.E
U U
F2+
F2+
F1-
F1-
M1
M2
M3
M1
M2
M3
T1
T2
T3
T4
T1
T2
T3
T4
(+) QMA(+) (+)
QMB(+)
QMA(-) (-) QMB(-) (-)
1 1 1 1
-FMA1 -FMA2 -FMB1 -FMB2
04A 04A 04A 04A
2 2 2 2
22 23 22 23
LOAD LOAD
22
(-)
13.9 / 0V DC 0V DC / 24.3
23
(+)
13.9 / 24V DC 24V DC / 24.3
FROM INCOMING-1
N1 L1.1 L2.1 L3.1
MICROLOGIC 6.E
"QT1"
VN
V3
V1
V2
Z1
Z2
Z3
Z4
Z5
1 3 5 7
QT1
2 4 6 8
I
Micrologic 6.E
U
F2+
F1-
M1
M2
M3
T1
T2
T3
T4
(+) QT1(+)
QT1(-) (-)
1 1
-FMT1 -FMT2
04A 04A
2 2
22 23
TO INCOMING-2
(-)
23.9 / 0V DC 0V DC / 32.0
(+)
23.9 / 24V DC 24V DC / 32.0
(N1.1) / 36.0
-FATL1
-FNAT1 10A -K1 13 14 10A
1 2 1 2
17.5 / (L1.1)
25.2
0114 3 3 3
0117
0116 -PBRRA 4 -PBRRB 4 -PBRRT 4
(LOCAL RESET) (LOCAL RESET) (LOCAL RESET)
(L1.2) / 37.0 A1
Reset Reset Reset
-K1 K2 K2 K2
A2
(N1.2) / 37.0
RES RES RES
QMA QMB QT1
13.3 / (AA1)
15 15
11
-RSD1
26.6 12 14
127
120 128
134
11 11 11 21 21 21 11 31
-RA1 -RT1 -RM1 -RM1 -RA1 -RT1 -R7 -RT1
31.5 12 14 31.3 12 14 31.1 12 14 31.1 22 24 31.5 22 24 31.3 22 24 33.8 12 14 31.3 32 34
-XCMA1 -XCMA1
CLOSE
1 3 0133
TRIP
(LOCATED @ CELL-12)
0
11 11 3 3 11 11
From Transformer
11
TERMINALS BLOCK
-R1 -RAC1 -R2 -RAO1
Protection Relay
-SSA TRIP -RTT1
33.3 12 14 27.8 12 14 CLOSE 33.4 12 14 27.6 12 14 2/G/1:17 81 411 41 31 21 11
FROM 4 4 FROM 26.7 12 14 EPR1 -OF14 -TT -AT -PS -OLG
DMCR 3.0
T15 SDE
MARSHALLING
CELL (BUSA)
MARSHALLING
CELL (BUSA) (QMA) QMA TPR1 TPR1 TPR1 TPR1
2/G/1:18 QMA 82 84 412 414 42 44 32 34 22 24 12 14
126 14.7 21.2 21.4 21.5 21.7
-XCMA1 2 -XCMA1 4
122 130
127 133 135
A1 C1 B1 D1 A1 A1 A1 A1 A1 A1 A1 A1
01
INCOMING-1
TITLE : Control Wiring Diagram (QMA) EQ NO : EQ200489/02-R12 Page No:
REV 10
SETRAA AL AMAL 26
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
11 21 31 31
OF2 OF3
-RRA 12 14 22 24 32 34 -RSD1 32 34
26.4 QMA QMA 26.6
15
26.9 / (LQA)
147 148 149 150 151 152 153 154
CLOSE
OPEN
COM
COM
-XCQMA 1 2 3 4 5 6 7 8
3
AVAILABLE IN MARSHALLING CELL (BUSA)
-PBLTA1 4
(LAMP TEST)
21 31 11 11 11
142
-RTT1 22 24 -RTT1 32 34 -RAT1 12 14 -RPS1 12 14 -ROLG1 12 14
26.7 26.7 26.8 26.8 26.9
155 156 0155 0156 157 158 159 160 161 162
-XCQMA 9 10 11 12 13 14 15 16 17 18
12 14 22 24 22 24 12 14
-ROF1 -ROF1 -RSD1 -SPD1 TRIPPING REMOTE DEVICE ALARM PRESSURE OIL LEVEL / GAS
11 26.6 21 26.6 21 26.6 11 14.2 TEMPERATURE TRIPPING TEMPERATURE FEEDBACK TO PLC FEEDBACK TO PLC
FEEDBACK TO PLC FEEDBACK TO RMU FEEDBACK TO PLC
13.4 / (BA1)
16 16
11
-RSD2
28.6 12 14
176
176
169 177
11 21
31 41 31 41 41 11 -R8 -RT2
-RA1 -RT1 -RM1 -RM1 -RA1 -RT2 33.8 12 14 31.4 22 24
31.5 32 34 31.3 42 44 31.1 32 34 31.1 42 44 31.5 42 44 31.4 12 14 0182
1 3
TRIP
(LOCATED @ CELL-14)
0
11 11 3 3 11 11 182
From Transformer
TERMINALS BLOCK
-R3 -RBC1 -R4 -RBO1
Protection Relay
-SSB TRIP 21
33.5 12 14 29.8 12 14 CLOSE 33.5 12 14 29.6 12 14 2/G/1:17 81 411 41 31 21 11
FROM 4 4 FROM -RPS2 EPR2 -OF14 -TT -AT -PS -OLG
DMCR 3.0
T15 SDE
MARSHALLING
CELL (BUSB)
MARSHALLING
CELL (BUSB) 28.8 22 24 (QMB) QMB TPR2 TPR2 TPR2 TPR2
2/G/1:18 QMB 82 84 412 414 42 44 32 34 22 24 12 14
175 20.7 22.2 22.4 22.5 22.7
-XCMB1 2 -XCMB1 4
171 179
176 21
179
-ROLG2 -XCB 2 -XCB 4 -XCB 6 -XCB 8
173
28.9 22 24
A1 C1 B1 D1 A1 A1 A1 A1 A1 A1 A1 A1
02
INCOMING-2
TITLE : Control Wiring Diagram-QMB EQ NO : EQ200489/02-R12 Page No:
REV 10
SETRAA AL AMAL 28
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
11 21 31 31
OF2 OF3
-RRB 12 14 22 24 32 34 -RSD2 32 34
28.5 QMB QMB 28.6
16
28.9 / (LQB)
196 197 198 199 200 201 202 203
CLOSE
OPEN
COM
COM
-XCQMB 1 2 3 4 5 6 7 8
3
AVAILABLE IN MARSHALLING CELL (BUSB)
-PBLTB1 4
(LAMP TEST)
21 31 11 11 11
191
-RTT2 22 24 -RTT2 32 34 -RAT2 12 14 -RPS2 12 14 -ROLG2 12 14
28.7 28.7 28.8 28.8 28.9
204 205 0204 0205 206 207 208 209 210 211
-XCQMB 9 10 11 12 13 14 15 16 17 18
12 14 22 24 22 24 12 14
-ROF2 -ROF2 -RSD2 -SPD2 TRIPPING REMOTE DEVICE ALARM PRESSURE OIL LEVEL / GAS
11 28.6 21 28.6 21 28.6 11 20.2 TEMPERATURE TRIPPING TEMPERATURE FEEDBACK TO PLC FEEDBACK TO PLC
FEEDBACK TO PLC FEEDBACK TO PLC
17
CONTROL SUPPLY (110V DC) AVAILABLE IN MARSHALLING CELL (BUSB) AVAILABLE IN MARSHALLING CELL (BUSB)
13.6 / (TA1)
OF2 OF3 A2 A2
-RRT 12 14 22 24 32 34 -RSD3 32 34
30.4 QT1 QT1 30.5
17 -RTC1 A1 -RTO1 A1
241 242 243 244 245 246 247 248
11 249 250 251 252
CLOSE
-RSDA
OPEN
COM
COM
26.5 12 14 17 (-) (+) (-) (+)
-XCQT1 1 2 3 4 5 6 7 8 -XCMT1 5 6 7 8
228
REMOTE/AVAILABLE CLOSE OPEN FAULT COM OPEN COM CLOSE
11 REMOTE COMMAND (24V DC)
FEEDBACK TO PLC FEEDBACK TO PLC FEEDBACK TO PLC FEEDBACK TO PLC
-RSDB
28.5 12 14 14 11 30.0 14 11 30.3
12 12
227 24 21
24 21
22 22
11 34 31 34 31
(PTL) / 31.0 32 32
-RSD3 44 41 44 41
30.5 12 14 42 42
225
225 225
11
-OF11
111 211 -OF13 311 31
-OF12 QT1 -K25
OF1 QMA
QT1 12 14 112 114 QMB 212 214 312 314
33.1
32 34
17 17 17 17 17
233 233 233
233
218 226
11 31 11 21 21 41
11 4
-RA2 -RT2 -RM2 -RM2 -RA2 -RT2 11 -PBLTT1
31.6 12 14 31.4 32 34 31.2 12 14 31.2 22 24 31.6 22 24 31.4 42 44 -R9 -RT3 (LAMP TEST)
34.2 12 14 31.4 12 14
219 221 223 229 231 232
0238
-XCMT1 -XCMT1
CLOSE
1 3
TRIP
0
11 11 3 3 11 11
-R5 -RTC1 -SST -R6 -RTO1
33.7 12 14 30.8 12 14 CLOSE TRIP 33.7 12 14 30.9 12 14 81 411 12 14 22 24 22 24
FROM 4 4 FROM -OF14
-SDE -ROF3 -ROF3 -RSD3
MARSHALLING
CELL (BUSB)
MARSHALLING
CELL (BUSB)
QT1 30.6 30.6 30.5
QT1 82 84 412 414 11 21 21
224
-XCMT1 2 -XCMT1 4
220 230
225 234
230
222
235
A1 C1 B1 D1 A1 A1 A1 x1 x1 x1
03
30.6 / (PTL)
17 21 31
-RT3 -RA2
31.4 22 24 31.6 32 34
-XCSS 1 2 3 4
AUTO
3 1 3
-SS1 MANUAL REMOTE AUTO
4 2 4
A1 A1 A1 A1 A1 A1 A1
-RM1 -RM2 -RT1 -RT2 -RT3 -RA1 -RA2
A2 A2 A2 A2 A2 A2 A2
03
30.8 / (PTN)
22
24.5 / 0V DC 0V DC / 33.0
23 22 23 22
1 1
-FE1 -FE2
04A 04A
2 2
260 261
192.168.3.146 FOR EXTERNAL 192.168.3.154 FOR EXTERNAL
(+) (2) /
MANAGEMENT
(+) (2) /
MANAGEMENT
(P1)
(P1)
DUAL POWER SUPPLY
(P2)
(-) (-)
192.168.3.149 192.168.3.157
(5) VFDA1 / 38.2TAG : P -105D (5) VFDB1 / TAG : P -105E
(P3)
(P3)
192.168.3.150 192.168.3.158
(6) VFDA2 / TAG : P -105F (6) VFDB2 / TAG : P -105K
Managed Ethernet switch
(SDS-3016-2GTX)
192.168.3.151 192.168.3.159
(7) VFDA3 / TAG : P -105J (7) VFDB3 / TAG : P -105L
-ETHSA1
-ETHSB1
192.168.3.152 192.168.3.160
(8) VFDA4 / 40.2TAG : SCR-102C1 & SCR-102C2 (8) VFDB4 / TAG : SCR-102D1 & SCR-102D2
MOXA
(16) SPARE-8 (16) SPARE-8
BUS-A BUS-B
22
32.9 / 0V DC
23
32.9 / 24V DC
22 23
23
-FP1
04A (QMA) (QMA) (QMB) (QMB)
2
OF4QMA
OF4QMB
21 41 41 21 41 41
-RSD1
26.6
-RSD2
28.6
3
-VMR1
14.0
-VMR2
20.0
24V DC / 34.0 -Auto
SS1 4 22 24 42 44 42 44 22 24 42 44 42 44
0V DC / 34.0
266
I0 I1 I2 I3 I4 I5 I6 I7
AUTO
-CONTROLLER1
(TM221ME16R)
16.9 / SA1 Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7
16.9 / SA2 0 1 2 3 COM1 4 5 6 7 COM2
16.9 / SA3
41
16.9 / SA4 -K25 301
47 46 48 49 33.1 44 42
308
N L1 L2 L3 BI1 BI3 B02 264 265 267 268 272 274 276 278
INCOMING #1 VOLTAGE
22
22
(IM-NT-BB) A1 A1 A1 A1 A1 A1 A1 A1
OUTPUT POWER 8-36 VDC -R1 -R2 -R3 -R4 -R5 -R6 -R7 -R8
INCOMING #2 VOLTAGE A2 A2 A2 A2 A2 A2 A2 A2
N L1 L2 L3 B01 COM + - 263
(PL) / 34.0
QMA (ON) QMA (OFF) QMB (ON) QMB (OFF) QT1 (ON) QT1 (OFF) QMA (TRIP) QMB (TRIP)
78 79 80 81 262
18.9 / SB1 14 11 26.0 14 11 26.2 14 11 28.0 14 11 28.2 14 11 30.0 14 11 30.2 14 11 26.4 14 11 28.4
A2 12 12 12 12 12 12 12 12
18.9 / SB2
-K25 24 21 24 21 24 21 24 21 24 21 24 21 24 21 24 21
A1 22 22 22 22 22 22 22 22
34 31 34 31 34 31 34 31 34 31 34 31 34 31 34 31
18.9 / SB3 32 32 32 32 32 32 32 32
44 41 44 41 44 41 44 41 44 41 44 41 44 41 44 41
18.9 / SB4 14 11 26.5 42 42 42 42 42 42 42 42
12
24 21 28.6
22
34 31 30.5
32
42 41 33.1
44
22 263
(-) (+)
EXPENSION MODULE
-CONTROLLER EXE1 (TM3DQ8R)
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7
0 1 2 3 COM1 4 5 6 7 COM2
279
A1
-R9
A2
263
33.9 / (PL)
QT1 (TRIP)
14 11 30.4
12
24 21
22
34 31
32
TITLE : Controller Control Wiring Diagram-2 EQ NO : EQ200489/02-R12 Page No:
44 41 REV 10
42 SETRAA AL AMAL 34
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
PARALLEL OPERATION
TRIP SELECTION
22
34.9 / 0V DC
263
34.2 / 24V DC
1-QMA TRIP
2-QMB TRIP
3-QT1 TRIP
3 3 3
-SSP1 QMA TRIP QMB TRIP QT1 TRIP
4 4 4 (QT1) (QT1)
-X3 1 -X3 3 -X3 5
OF4QT1
41 41
-RSD3
30.5
SPARE SPARE SPARE
42 44 42 44
-X3 2 -X3 4 -X3 6
-CONTROLLER EXE2 I0 I1 I2 I3 I4 I5 I6 I7
EXPENSION MODULE
(TM3DI8)
010
25.1 / (L1.1) (L1.1) / 38.0
1 1 1 1 1 1 1 1 1 1 1
-FAH1 -FAH2 -FAH3 -FAH4 -FAH5 -FAH6 -FAH7 -FAF1 -FAF2 -FAF3 -FAF4
06A 2 06A 2 06A 2 06A 2 06A 2 06A 2 06A 2 06A 2 06A 2 06A 2 06A 2
C1 L C1 L C1 L C1 L C1 L C1 L C1 L 13 13 13 13
-HAG1 -HAG2 -HAG3 -HAG4 -HAG5 -HAG6 -HAG7 -TAH1 -TAH2 -TAH3 -TAH4
Hygrometer Hygrometer Hygrometer Hygrometer Hygrometer Hygrometer Hygrometer Thermostat 14 Thermostat 14Thermostat 14 Thermostat 14
NO1 N NO1 N NO1 N NO1 N NO1 N NO1 N NO1 N
x1 x1 x1 x1 x1 x1 x1 x1 x1 x1 x1
-HAE1 -HAE2 -HAE3 -HAE4 -HAE5 -HAE6 -HAE7 -EAFAN1 -EAFAN2 -EAFAN3 -EAFAN4
Heater x2 Heater x2 Heater x2 Heater x2 Heater x2 Heater x2 Heater x2
150 Watts 150 Watts 150 Watts 150 Watts 150 Watts 150 Watts 150 Watts x2 x2 x2 x2
011
25.1 / (N1.1) (N1.1) / 38.0
MARSHALLING CELL-1 CELL-2 CELL-3 CELL-4 CELL-5 CELL-6 CELL-1 CELL-2 CELL-6
CELL (BUSA)
020
25.1 / (L1.2) (L1.2) / 53.0
1 1 1 1 1 1 1 1 1 1 1
-FBH1 -FBH2 -FBH3 -FBH4 -FBH5 -FBH6 -FBH7 -FBH8 -FBF1 -FBF2 -FBH9
06A 06A 06A 06A 06A 06A 06A 06A 06A 06A 2 06A
2 2 2 2 2 2 2 2 2 2
326
324
C1 L C1 L C1 L C1 L C1 L C1 L C1 L C1 L 13 13 C1 L
-HBG1 -HBG2 -HBG3 -HBG4 -HBG5 -HBG6 -HBG7 -HBG8 -TBH5 -TBH6 -HBG9
Hygrometer Hygrometer Hygrometer Hygrometer Hygrometer Hygrometer Hygrometer Hygrometer Thermostat 14 Thermostat 14 Hygrometer
NO1 N NO1 N NO1 N NO1 N NO1 N NO1 N NO1 N NO1 N NO1 N
x1 x1 x1 x1 x1 x1 x1 x1 x1 x1 x1
-HBE1 -HBE2 -HBE3 -HBE4 -HBE5 -HBE6 -HBE7 -HBE8 -EBFAN1 -EBFAN2 -HBE8
Heater x2 Heater x2 Heater x2 Heater x2 Heater x2 Heater x2 Heater x2 37.9 x2 37.7 x2
150 Watts 150 Watts 150 Watts 150 Watts 150 Watts 150 Watts 150 Watts Heater x2 x2 Heater
150 Watts 150 Watts
021
25.1 / (N1.2) (N1.2) / 53.0
CELL-7 CELL-8 CELL-9 CELL-10 CELL-11 CELL-12 CELL-13 MARSHALLING CELL-13 CELL-14
CELL (BUSB)
011 010
-QCAV1
10 Amps 2pole
iC60L MCB
QAV1\1 QAV1\2
2 4
230 230 FN(A) / 39.0
1 3
QAV1\3
PROGRAMMABLE PROGRAMMABLE PULSE
0 0 L1(A) / 39.0 INPUT DIGITAL INPUTS
PE
-TRVA1
100 VA -XCAV1 10 11 12 13 14 15
230/230
1 3 5
Rotary
QAV1\21
QAV1\17
QAV1\22
QAV1\17
QAV1\23
QAV1\17
QAV1 handle (B)N / 39.0
2 4 6 QAV1\N
(A)L / 39.0 QAV1\17 QAV1\17 QAV1\17
QAV1\17
PROGRAMMABLE 11 11 21 3
FAULT SIGNAL VFD RUN SIGNAL RELAY OUTPUT 3 -RPAV1 -RCAV1 -RPAV1 -PBRVA1
39.2 12 14 39.4 12 14 39.2 22 24 4
(RESET)
-XCAV1 1 2
QAV1\18
QAV1\18
QAV1\19
QAV1\20
QAV1\4
QAV1\5
R/L1 S/L2 T/L3 R1A R1C R1B R2A R2C R3A R3C DI1 DI2 DI3 DI4 DI5 DI6 24+
-HMI1
RUN PRESET SPEED RESET FAULT
REMOTE HMI
-RJ1
VFD VW3A1104R50
DISPLAY UNIT
VW3A1112
MODBUS TCP
U/T1 V/T2 W/T3
87654321 RJ45
10 V AI1 COM AI2 AI3 COM AQ1 AQ2 STOA STOB 24V
ATV630 ON MODULE DOOR
AVAILABLE IN
MARSHALLING CELL
1 2 5
VFDA1
32.3
QAV1\10
QAV1\11
QAV1\12
QAV1\13
QAV1\14
QAV1\15
QAV1\16
QAV1\6
QAV1\7
QAV1\8
QAV1\9
TO ETHERNET SWITCH
-SINUSA1
Sinus Filter
-XCAV1 3 4 5 6 -XCAV1 7 8 9
PTC1
-XCMVA1 1 2 3 4 5 SAFE TORQUE OFF
10.SVDC, 10mA
FOR ANALOG INPUT
INTERNAL SUPPLY
INPUT (COM)
0V FOR ANALOG
ANALOG OUTPUT
PROGRAMABLE
OUTPUT (COM)
0V FOR ANALOG
FEEDBACK TO PLC
MOTOR CURRENT
FEEDBACK TO PLC
OUTPUT 4-20mA
CURRENT ANOLOG
PTC2
3 4 6
-XPAV1 1 2 3 E
PTC3
3~
COMMAND FROM PLC LEVEL SENSOR FEEDBACK TO PLC (BUS-B) - QBV5, QBV6, QBV7
PE TITLE : Power & Control Diagram VFD-1 EQ NO : EQ200489/02-R12 Page No:
REV 10
SETRAA AL AMAL 38
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
A2 14 11 39.4 A2 14 11 39.2
12 12
-RREAV1 11 -RRAV1 41 -RFAV1 21 24 21
39.5 39.6 39.5 -RSSV1 A1 24 21
-RPSV1 A1
22 22
12 14 42 44 22 24 34 31 34 31
QAV1\61
QAV1\62
QAV1\63
QAV1\64
32 32
44 41 44 41
42 42
QAV1\55
QAV1\56
QAV1\57
QAV1\58
QAV1\59
QAV1\60
(-) (+) (-) (+)
-XCMVA1 16 17 18 19
START/STOP PROTECTION
COM COM
COMMAND STOP COMMAND
-XCMVA1 10 11 12 13 14 15
FROM PLC FROM PLC 24V DC
REMOTE/AVAILABLE RUN FEEDBACK FAULT FEEDBACK 24V DC
QAV1\2 TO PLC TO PLC
FEEDBACK TO PLC
38.4 / FN(A)
REMOTE COMMAND (24V DC)
QAV1\3
38.4 / L1(A)
-QCDAV1
04 Amps 2pole
iC60L MCB
38.2 / (A)L
QAV1\26
38.2 / (B)N
QAV1\28
QAV1\28
-XCAV1 16
-EPBAV1 11
TO LCS
12
EMERGENCY QAV1\26
STOP
QAV1\30
-XCAV1 17
QAV1\1
QAV1\27 QAV1\28 QAV1\26 QAV1\26 QAV1\26 QAV1\26
11
-XCAV1 18 -QAV1
OF1 12 14
9.1
JUMPER
QAV1\N Future 3
Interlock QAV1\31
31
11 -PLTAV1 4
-RFAV1 -RKAD1 (LAMP TEST)
-XCAV1 19
39.5 39.7 12 14
QAV1\28 32 34
QAV1\32
QAV1\50
QAV1\26
-XCMVA1 6 QAV1\41
31 11
-RRAV1 -RPSV1
39.6 32 34 39.9 12 14
FROM
MARSHALLING
CELL
QAV1\26
-XCMVA1 7 11 QAV1\50
QAV1\29 QAV1\29 QAV1\29 -QAV1
REMOTE
SD 12 14
LOCAL
QAV1\29 9.1 1 3
OFF
LCS
-KSBAD1 -KSBAD1
0123 1 3 7 5
39.6 2 39.6 4
-SSAV1 LOCAL LCS REMOTE REMOTE
22 24 12 14 12 14 -XCAV1 28
2 4 8 6 -RRAV1 -RRAV1 -RFAV1
QAV1\36 QAV1\35 21 39.6 11 39.6 11 39.5
QAV1\33
QAV1\38
QAV1\36
FAULT SIGNAL
4 39.2 32 34 39.2 42 44
RUN SIGNAL
(START) MARSHALLING
(START) 4 (STOP) 2 Temperature Leakage TEST)
CELL
QAV1\37
TO LCS QAV1\51
R1B R1A R2A -XCAV1
QAV1\45
QAV1\47
QAV1\46
QAV1\48
-XCAV1 22 QAV1\53 29
QAV1\37
1 QAV1\39
QAV1\54 30
-PBFV1
QAV1\43 31
(STOP) 2 QAV1\44
START
STOP
FAULT
*
CUSTOMER SUPPLIED
QAV1\35 QAV1\35 x1 x1 x1
x1 x1
A1 A1 A1 A1 A1 8 9 10 11 12 A1 x1 x1 x1 -HR x2 -HG x2 -HY x2
-KSBAD1
230V AC
-RPAV1 -RCAV1 -RREAV1 -RFAV1 -RRAV1 -RKAD1 -HRAV1 -HGAV1 -HYAV1
A2 A2 A2 A2 A2
39.7
A2 x2 x2 x2 TO LCS
RELAY.
-FANA1 x2 -FANA2 x2 Red Green Yellow
39.7
7 -XCAV1 27
QAV1\25 QAV1\25
011 010
-QCAV4
10 Amps 2pole
iC60L MCB
QAV4\1 QAV4\2
2 4
230 230 FN(A) / 41.0
1 3
QAV4\3
PROGRAMMABLE PROGRAMMABLE PULSE
0 0 L1(A) / 41.0 INPUT DIGITAL INPUTS
-TRVA4 PE
100 VA -XCAV4 10 11 12 13 14 15
230/230
1 3 5
Rotary
QAV4\21
QAV4\17
QAV4\22
QAV4\17
QAV4\23
QAV4\17
-QAV4 handle (B)N / 41.0
I> I> I> (A)L / 41.0 QAV4\17 QAV4\17 QAV4\17
2 4 6
QAV4\17
PROGRAMMABLE 11 11 21 3
FAULT SIGNAL VFD RUN SIGNAL RELAY OUTPUT 3 -RPAV4 -RCAV4 -RPAV4 -PBRVA4
41.3 12 14 41.5 12 14 41.3 22 24 4
(RESET)
-XCAV4 1 2
QAV4\18
QAV4\18
QAV4\19
QAV4\20
QAV4\4
QAV4\5
R/L1 S/L2 T/L3 R1A R1C R1B R2A R2C R3A R3C DI1 DI2 DI3 DI4 DI5 DI6 24+
-HMI4
RUN PRESET SPEED RESET FAULT
REMOTE HMI
-RJ4
VFD VW3A1104R50
DISPLAY UNIT
VW3A1112
MODBUS TCP
U/T1 V/T2 W/T3
87654321 RJ45
10 V AI1 COM AI2 AI3 COM AQ1 AQ2 STOA STOB 24V
ATV630 ON MODULE DOOR
AVAILABLE IN
1 2 5 MARSHALLING CELL
VFDA4
QAV4\10
QAV4\11
QAV4\12
QAV4\13
QAV4\14
QAV4\15
QAV4\16
32.3
QAV4\6
QAV4\7
QAV4\8
QAV4\8
QAV4\9
-SINUSA4 TO ETHERNET SWITCH
Sinus Filter
-XCAV4 3 4 5 6 -XCAV4 7 8 9
INPUT (COM)
0V FOR ANALOG
OUTPUT (COM)
0V FOR ANALOG
FEEDBACK TO PLC
MOTOR CURRENT
FEEDBACK TO PLC
OUTPUT 4-20mA
CURRENT ANOLOG
PROGRAMABLE ANALOG OUTPUT
FOR PT100,1000, PTC WATER
LEVEL SENSOR
XPA1 1 2 3 E XPA2 1 2 3 E
TYPICAL POWER & CONTROL DIAGRAM
U1 V1 W1 U1 V1 W1 SPEED REFERENCE SPEED REFERENCE
COMMAND FROM PLC FEEDBACK TO PLC DEVICE TAG:- (BUS-A) - QAV4 / (BUS-B) - QBV8
-Motor1
M -Motor2
M
3~ 3~ TITLE : Power & Control Diagram VFD-4
REV 10
EQ NO : EQ200489/02-R12 Page No:
SETRAA AL AMAL 40
PE PE JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
A2 14 11 41.5 A2 14 11 41.2
12 12
-RREAV4 11 -RRAV4 41 -RFAV4 21 24 21
41.5 41.6 41.6 -RSSV4 A1 24 21
-RPSV4 A1
22 22
12 14 42 44 22 24 34 31 34 31
QAV4\55
QAV4\56
QAV4\57
QAV4\58
QAV4\2 32 32
40.4 / FN(A) 44 41 44 41
42 42
QAV4\49
QAV4\50
QAV4\51
QAV4\52
QAV4\53
QAV4\54
QAV4\3
40.4 / L1(A) (-) (+) (-) (+)
-XCMVA4 16 17 18 19
START/STOP PROTECTION
COM COM
COMMAND STOP COMMAND
-QCDAV4 -XCMVA4 10 11 12 13 14 15
FROM PLC FROM PLC 24V DC
04 Amps 2pole REMOTE/AVAILABLE RUN FEEDBACK FAULT FEEDBACK 24V DC
iC60L MCB
FEEDBACK TO PLC TO PLC TO PLC
40.2 / (A)L REMOTE COMMAND (24V DC)
QAV4\26
40.2 / (B)N
QAV4\28
-XCAV4 16
TO LCS QAV4\28
-EPBAV4 11
QAV4\26
EMERGENCY
STOP
12
-XCAV4 17
QAV4\N QAV4\1 QAV4\27 QAV4\28 QAV4\30 QAV4\26 QAV4\26 QAV4\26 QAV4\26
53
-QAV4
-XCAV4 18
OF
9.4 54
JUMPER
97 3
Future QAV4\31 -QAV4
Interlock SD -PLTAV4
9.4 98 4
31 (LAMP TEST)
-RFAV4
-XCAV4 19 QAV4\28 41.6
32 34
QAV4\32
QAV4\26
-XCMVA4 6
QAV4\44
31 11
-RRAV4 -RPSV4
41.6 32 34 41.9 12 14
FROM
MARSHALLING
CELL
QAV4\26
-XCMVA4 7 QAV4\44
QAV4\29 QAV4\29 QAV4\29 QAV4\41 QAV4\26
REMOTE
LOCAL
QAV4\29
OFF
LCS
0123 1 3 7 5
-SSAV4 LOCAL LCS REMOTE REMOTE
22 24 12 14 12 14 -XCAV4 24
2 4 8 6 -RRAV4 -RRAV4 -RFAV4
QAV4\36 QAV4\35 21 41.6 11 41.6 11 41.6
QAV4\33
QAV4\38
QAV4\36
FAULT SIGNAL
4 41.3 32 34 41.3 42 44
RUN SIGNAL
(START) MARSHALLING
(START) 4 (STOP) 2 TEST)
CELL
QAV4\37
TO LCS QAV4\45
R1B R1A R2A -XCAV4
-XCAV4 22 QAV4\47 25
QAV4\37
1 QAV4\39
QAV4\48 26
-PBFV4
QAV4\42 27
(STOP) 2 QAV4\43
START
STOP
FAULT
QAV4\35 QAV4\35 x1 x1 x1
011
QAV5\11 QAV5\11
Rotary 01
handle S1
I1+
1 3 5 C2 A1
-CTAV1
0~600Amps QAV5\12 QAV5\12
-QAV5 -RQVA5 (MCT-300/60A) S2 02
-MXQAV5 C1 A2 I1-
2 4 6 14 11 42.4 QAV5\8
Shunt trip coil QAV5\13 QAV5\13
208~277 Volt 12 QAV5\6 03
24 21 91
QAV5\6
S1
I2+
22 -CTAV2
34 31 -SD 0~600Amps QAV5\12 QAV5\12
32 92 94 S2 04
44 41
QVA5 (MCT-300/60A) I2-
A1 A2
42 QAV5\7
31 QAV5\14 QAV5\14
05
S1
I3+
32 -CTAV3
QAV5\5
0~600Amps QAV5\12 QAV5\12
34 (MCT-300/60A) S2 06
I3-
PE Digital Ammeter
-EFRAQVA5
(METSEDM3110)
QAV5\9 -DAQAV5
42.0 / (T1) T1 11
VN
QAV5\10
08
42.0 / (T2) T2 V1
09
V2
10
V3
AVAILABLE IN MARSHALLING CELL 011
13
N(-)
QAV5\2
12
L(+)
11 21 11
OF5 OF2 -RQVA5
12 14 22 24 42.2 12 14
QAV1 QAV5
QAV5\15 QAV5\16 QAV5\17 QAV5\18 QAV5\19 QAV5\20
20.2 / PE PE / 51.0
-XCQAV5 1 2 3 4 5 6
COM CLOSE COM OPEN COM TRIP
CLOSE FEEDBACK OPEN FEEDBACK TRIP FEEDBACK
TO PLC TO PLC TO PLC
BREAKER STATUS
PE N L1 L2 L3
OUTGOING
TYPICAL WIRING DIAGRAM FOR ALL OUTGOING MCCB TOROID COIL WITH DIGITAL AMMETER
DEVICE TAG:- (BUS-A) - QAV5, QAV6 / (BUS-B) - QBV1, QBV2
TITLE : MCCB Outgoing With (Ammeter,Toroid EQ NO : EQ200489/02-R12 Page No:
& Auxiliary) REV 10
SETRAA AL AMAL 42
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
-QCAD1
04 Amps 2pole
iC60L MCB
QAD1\4
1 3 5
QAD1\3
-CLMA1
QAD1\4 -TRDA1 QAD1\5
2 4
I>> I>> I>> 230 230
QAD1\3 QAD1\6
2 4 6 1 3
1 3 5 0 0
Rotary 100 VA PE
-QAD1 handle 230/230
QAD1\5
QAD1\6
I> I> I>
2 4 6
-QCDAD1
04 Amps 2pole
iC60L MCB
QAD1\7
QAD1\8
QAD1\7 QAD1\7
1 3 5
L1(A) / 44.0
-KAD1 2 4 6 QAD1\8 QAD1\8
44.1 FN(A) / 44.0
QAD1\7
QAD1\8
x1
32 A1 A2
A 31
AMMETER
x2
34
-EFRAD1
44.5
QAD1\1
T1 T1
-Toroid
QAD1\2
Coil
T2
T2
-XPAD1 1 2 3 E
TYPICAL POWER & CONTROL DIAGRAM
U1 V1 W1 DEVICE TAG:-
M (BUS-A) - QAD1, QAD2, QAD3, QAD4, QAD5, QAD6,
-Motor (BUS-B) - QBD1, QBD2, QBD3, QBD4, QBD5, QBD6,
3~
PE TITLE : Power & Control Diagram DOL-1 EQ NO : EQ200489/02-R12
10 Page No:
REV
SETRAA AL AMAL 43
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
QAD1\7 QAD1\7
43.9 / L1(A)
QAD1\7
A2 14 11 44.3 A2 14 11 44.1
-RRAD1 -RSAD1
QAD1\38
QAD1\40
11 83 21 12 12
(P) / 44.9 44.4 44.4 24 21
-KAD1 -RSSD1 A1 24 21
-RPSD1 A1
22 22
-XCAD1 1 12 14 44.1 84 22 24 34 31 34 31
QAD1\39
QAD1\41
32 32
TO LCS 44 41 44 41
42 42
QAD1\32
QAD1\33
QAD1\34
QAD1\35
QAD1\36
QAD1\37
EMERGENCY
STOP (-) (+) (-) (+)
-XCAD1 2 -XCMAD1 11 12 13 14
START/STOP PROTECTION
COM COM
QAD1\9 COMMAND STOP COMMAND
-XCMAD1 5 6 7 8 9 10
FROM PLC FROM PLC 24V DC
-XCAD1 3
REMOTE/AVAILABLE RUN FEEDBACK FAULT FEEDBACK 24V DC
FEEDBACK TO PLC TO PLC TO PLC
JUMPER
-XCAD1 4
QAD1\10
QAD1\7
-XCMAD1 1
11
-RPSD1
44.9 12 14
FROM
MARSHALLING
CELL
-XCMAD1 2
31
-RSAD1
44.4
32 34
QAD1\12
53
-QAD1
OF
10.0 54
QAD1\7 QAD1\7
QAD1\13 QAD1\13 QAD1\13
REMOTE
LOCAL
-RLAD1
44.6
-RLAD1
44.6
-RLAD1
44.6
QAD1\13
OFF
LCS
0123 1 3 7 5 31 3 11 21 31
-SSAD1 LOCAL LCS REMOTE REMOTE -EFRAD1 -XCAD1 11
2 4 8 6 43.7 32 34 -PLTAD1 4 12 14 22 24 32 34
QAD1\17 (LAMP TEST)
QAD1\14
QAD1\19 QAD1\7
QAD1\17
QAD1\25
-PBRAD1 44.8 12 14
QAD1\26
44.1 44.1 QAD1\29 QAD1\30 QAD1\31
FROM
(START) 4 14 74 (LAMP 4 14 14
MARSHALLING
(START) 4 (STOP) 2 CELL -KMCAD1 8 9 TEST)
QAD1\15 QAD1\15 44.5 QAD1\24 QAD1\28
-XCMAD1 4
QAD1\18
QAD1\20 QAD1\21
QAD1\15
TO LCS 95
QAD1\29 -XCAD1
-QAD1
-XCAD1 6 SD QAD1\30 12
QAD1\16 3
1 QAD1\16 10.0 96
QAD1\18 QAD1\31 13
-PBSAD1
2
-PRSAD1 4
(STOP) (RESET) 14
START
STOP
FAULT
CUSTOMER SUPPLIED
QAD1\27
x1 x1 x1
200~240 Volt
A2 A2 A2 C1 10 44.4 A2 Red x2 Green x2 Yellow x2
-XCAD1 10
QAD1\8 QAD1\8 QAD1\8
43.9 / FN(A)
FLYGT MiniCAS II START STOP FAULT
-QCAD7
04 Amps 2pole
iC60L MCB
QAD7\4
QAD7\3
QAD7\4 -TRDA7 QAD7\5
2 4
230 230
QAD7\3 QAD7\6
1 3
1 3 5 0 0
Rotary 100 VA PE
-QAD7 handle 230/230
QAD7\5
QAD7\6
I> I> I>
2 4 6
-QCDAD7
04 Amps 2pole
iC60L MCB
QAD7\7
QAD7\8
QAD7\7 QAD7\7
1 3 5
L1(A) / 46.0
-KAD7 2 4 6 QAD7\8 QAD7\8
46.1 FN(A) / 46.0
QAD7\7
QAD7\8
x1
32 A1 A2
A 31
AMMETER
x2
34
-EFRAD7
46.4
QAD7\1
T1 T1
-Toroid
QAD7\2
Coil
T2
T2
-XPAD7 1 2 3 E
A2 14 11 46.3 A2 14 11 46.1
-RRAD7 -RSAD7
QAD7\40
QAD7\42
11 83 21 12 12
46.3 46.4 24 21
-KAD7 -RSSD7 A1 24 21
-RPSD7 A1
(P) / 46.9 12 14 46.1 84 22 24
22 22
34 31 34 31
QAD7\41
QAD7\43
QAD7\7 32 32
44 41 44 41
-XCAD7 1 42 42
QAD7\34
QAD7\35
QAD7\36
QAD7\37
QAD7\38
QAD7\39
TO LCS (-) (+) (-) (+)
-XCMAD7 11 12 13 14
EMERGENCY START/STOP PROTECTION
STOP COM COM
COMMAND STOP COMMAND
-XCMAD7 5 6 7 8 9 10
FROM PLC FROM PLC 24V DC
-XCAD7 2 REMOTE/AVAILABLE RUN FEEDBACK FAULT FEEDBACK 24V DC
FEEDBACK TO PLC TO PLC TO PLC
QAD7\9
REMOTE COMMAND (24V DC)
-XCAD7 3
JUMPER
Future QAD7\7
Interlock
-XCAD7 4
QAD7\10
-XCMAD7 1
11
-RPSD7
46.9 12 14
FROM
MARSHALLING
CELL
-XCMAD7 2
31
-RSAD7
46.4
32 34
QAD7\12
53 1 3
-QAD7
OF -KSBAD2 -KSBAD2
10.5 54 46.5 2 46.5 4 QAD7\7 QAD7\7
QAD7\13 QAD7\13
REMOTE
LOCAL
-RLAD7
46.6
-RLAD7
46.6
-RLAD7
46.6
QAD7\13
OFF
LCS
0123 1 3 7 5 31 3 11 21 31
-SSAD7 LOCAL LCS REMOTE REMOTE -EFRAD7 -XCAD7 13
2 4 8 6 45.7 32 34 -PLTAD7 4 12 14 22 24 32 34
QAD7\17 (LAMP TEST)
QAD7\14
QAD7\19 QAD7\20
QAD7\17
-XCAD7 5 7 -XCMAD7 3
QAD7\23 QAD7\7 53 61 11
QAD7\14
11 -KAD7 -KAD7 -RSAD7
3 11 46.1 54 46.1 62 46.4 12 14 3
-KAD7
13
-KAD7
73
3 1
-RSSD7 13 13
-PBRAD7 46.8 12 14 -RKAD2 QAD7\31 QAD7\32 QAD7\33
46.1 46.1
4 14 74
FROM 46.6 12 14 (LAMP 4 14 14
(START) MARSHALLING
(START) 4 (STOP) 2 QAD7\24
Temperature Leakage TEST)
CELL
QAD7\15 QAD7\15 sensors sensors QAD7\29 QAD7\30
-XCMAD7 4 -XCAD7 8 9 10 11
QAD7\18
QAD7\15
TO LCS QAD7\31 -XCAD7
QAD7\25
QAD7\27
QAD7\21
QAD7\26
QAD7\28
-XCAD7 6 QAD7\32 14
QAD7\16 95
1 QAD7\16 -QAD7
QAD7\18 SD QAD7\33 15
-PBSAD7 10.5 96
(STOP) 2 16
START
STOP
FAULT
CUSTOMER SUPPLIED
-KAD7 -RRAD7 -RSAD7 Shunt trip coil 46.5 -RKAD2 -RLAD7 -HRAD7 -HGAD7 -HYAD7 TO LCS
RELAY.
-QCAD8
04 Amps 2pole
iC60L MCB
QAD8\4
QAD8\3
QAD8\4 -TRDA8 QAD8\5
2 4
230 230
QAD8\3 QAD8\6
1 3
1 3 5 0 0
Rotary 100 VA PE
-QAD8 handle 230/230
QAD8\5
QAD8\6
I> I> I>
2 4 6
-QCDAD8
04 Amps 2pole
iC60L MCB
QAD8\7
QAD8\8
QAD8\7 QAD8\7
1 3 5
L1(A) / 48.0
-KAD8 2 4 6 QAD8\8 QAD8\8
48.1 FN(A) / 48.0
QAD8\7
QAD8\8
x1 32 A1 A2
A 31
AMMETER
x2
34
-EFRAD8
48.5
QAD8\1
T1 T1
-Toroid
QAD8\2
Coil
T2
T2
-XPAD8 1 2 3 E
U1 V1 W1
TYPICAL POWER & CONTROL DIAGRAM
-Motor
M DEVICE TAG:- (BUS-A) - QAD8 / (BUS-B) - QBD8
3~
PE TITLE : Power & Control Diagram DOL-8 EQ NO : EQ200489/02-R12
10 Page No:
REV
SETRAA AL AMAL 47
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
QAD8\7
AVAILABLE IN MARSHALLING CELL AVAILABLE IN MARSHALLING CELL
47.9 / L1(A)
A2 14 11 48.4 A2 14 11 48.1
-RRAD8 -RSAD8
QAD8\34
QAD8\36
11 83 21 12 12
48.4 48.5 24 21
-KAD8 -RSSD8 A1 24 21
-RPSD8 A1
22 22
QAD8\7 12 14 48.1 84 22 24 34 31 34 31
QAD8\35
QAD8\37
32 32
44 41 44 41
(P) / 48.9 42 42
QAD8\28
QAD8\29
QAD8\30
QAD8\31
QAD8\32
QAD8\33
QAD8\10
-XCAD8 1 (-) (+) (-) (+)
TO LCS -XCMAD8 11 12 13 14
QAD8\10
START/STOP PROTECTION
COM COM
COMMAND STOP COMMAND
EMERGENCY -XCMAD8 5 6 7 8 9 10
FROM PLC FROM PLC 24V DC
STOP QAD8\7 REMOTE/AVAILABLE RUN FEEDBACK FAULT FEEDBACK
-XCMAD8 1 24V DC
FEEDBACK TO PLC TO PLC TO PLC
-XCAD8 2
11 REMOTE COMMAND (24V DC)
QAD8\9 -RPSD8
48.9 12 14
FROM
MARSHALLING
CELL
-XCAD8 3 -XCMAD8 2
JUMPER
Future
Interlock
QAD8\7 QAD8\7 QAD8\7 QAD8\7
QAD8\10
48.0 / (P)
QAD8\11
-XCAD8 4
QAD8\10 31
-RSAD8
48.5
32 34
QAD8\10
QAD8\12
53
-QAD8
OF
10.5 54
QAD8\7 QAD8\7
QAD8\13 QAD8\13 QAD8\13
-PLTAD8
REMOTE
LOCAL
-RLAD8
48.6
-RLAD8
48.6
-RLAD8
48.6
QAD8\13
OFF
LCS
0123 1 3 7 5 31 3 11 21 31
-SSAD8 LOCAL LCS REMOTE REMOTE -EFRAD8 -XCAD8 9
47.7 32 34 (LAMP 4 12 14 22 24 32 34
2 4 8 6
QAD8\17 TEST)
QAD8\14
QAD8\19
QAD8\21
QAD8\17
-XCAD8 5 7 -XCMAD8 3
QAD8\21 53 61 11
QAD8\14
11 -KAD8 -KAD8 -RSAD8
3 48.1 54 48.1 62 48.5 12 14 3
-KAD8
13
-KAD8
73
3 1
-RSSD8 13 13
-PBRAD8 48.1 48.1
48.8 12 14
FROM
(START) 4 14 74 95 (LAMP 4 14 14
MARSHALLING
(START) 4 (STOP) 2 CELL
-QAD8 TEST)
QAD8\15 QAD8\15 QAD8\20 SD QAD8\23 QAD8\24
-XCMAD8 4 10.5
QAD8\18
START
STOP
FAULT
QAD8\16 QAD8\16 QAD8\16
x1 x1 x1
-QCAD9
04 Amps 2pole
iC60L MCB
QAD9\4
QAD9\3
QAD9\4 -TRDA9 QAD9\5
2 4
230 230
QAD9\3 QAD9\6
1 3
1 3 5 0 0
Rotary 100 VA PE
-QAD9 handle 230/230
QAD9\5
QAD9\6
I> I> I>
2 4 6
-QCDAD9
04 Amps 2pole
iC60L MCB
QAD9\7
QAD9\8
QAD9\7 QAD9\7
L1(A) / 50.0
1 3 5 1 3 5 QAD9\8 QAD9\8
FN(A) / 50.0
-KADF1 2 4 6 -KADR1 2 4 6
QAD9\7
50.0 50.1
QAD9\8
32 A1 A2
x1 31
A 34
AMMETER
x2
-EFRAD9
50.6
QAD9\1
T1 T1
-Toroid
QAD9\2
Coil
T2
T2
-XPDA9 1 2 3 E
U1 V1 W1
TYPICAL POWER & CONTROL DIAGRAM
-Motor
M
3~ DEVICE TAG:- (BUS-A) - QAD9 / (BUS-B) - QBD9
PE TITLE : Power & Control Diagram DOL-9 EQ NO : EQ200489/02-R12
10 Page No:
REV
SETRAA AL AMAL 49
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
QAD9\7
49.9 / L1(A)
AVAILABLE IN MARSHALLING CELL AVAILABLE IN MARSHALLING CELL
A2 14 11 50.1
12
-RRAD9 -RODF1 -RCDR1 -RSAD9 A1 24 21
11 21 21 31 -RPAD1 22
50.5 50.6 50.7 50.5
34 31
(P) / 50.9 12 14 22 24 22 24 32 34
32
QAD9\10
QAD9\47
QAD9\48
QAD9\7 44 41
42
QAD9\39
QAD9\40
QAD9\41
QAD9\42
QAD9\43
QAD9\44
QAD9\45
QAD9\46
QAD9\10
QAD9\10
(-) (+)
-XCAD9 1 -XCMAD9 1 QAD9\7
-XCMAD9 11 12
PROTECTION
11 COM
-XCMAD9 3 4 5 6 7 8 9 10 STOP COMMAND
-RPAD1 AUTO/AVAILABLE OPEN FEEDBACK CLOSE FEEDBACK FAULT FEEDBACK FROM PLC 24V DC
EMERGENCY 50.9 12 14
FEEDBACK TO PLC TO PLC TO PLC TO PLC
TO LCS STOP FROM
MARSHALLING
-XCAD9 2 CELL REMOTE COMMAND (24V DC)
-XCMAD9 2
QAD9\9
-XCAD9 3 QAD9\15
JUMPER
11
Future -RSAD9
Interlock 50.5
12 14 QAD9\7 QAD9\7 QAD9\7
50.0 / (P)
QAD9\16
-XCAD9 4
53
-QAD9
QAD9\10 OF 3
10.6 54
(LAMP TEST)
LOCAL
QAD9\17 QAD9\7
OFF
LCS
QAD9\35
0123 1 3 7 5
-SSAD9 LOCAL LCS AUTO AUTO
2 4 8 6
QAD9\11 QAD9\26
-XCAD9 5 6 7
QAD9\27
QAD9\28
QAD9\29
QAD9\30
12 14 12 14 22 24
-RODF1 -RCDR1 -RSAD9
13 13 50.6 50.7 50.5
CLOSE
11 11 21
OPEN
3 1 3
OFF
QAD9\32
3 3 -KADF1 -KADR1
14 14
-SSD9 50.0 (START 4 (STOP) 2 (START 4
50.1 15 12 11 10 9 2
4 OPEN CLOSE 4 OPEN) CLOSE) (+) (-) (+) (-)
-POAD1 95
QAD9\22
-QAD9
Positioner SD
TO LCS MS-20 10.6 96
QAD9\7
-XCAD9 8
QAD9\12 QAD9\22 14 16 8 7 6 5 1
QAD9\33 QAD9\34 QAD9\7 QAD9\7 QAD9\36 QAD9\37 QAD9\38
QAD9\22 QAD9\22
QAD9\31
-XCAD9 14
QAD9\12 QAD9\12 QAD9\12
QAD9\18
3 13 13
21 21
-KADR1 -KADF1 (LAMP 4 14 14
50.1 50.0 TEST)
22 22
QAD9\13 QAD9\19 QAD9\36 -XCAD9
QAD9\37 15
QAD9\21
A1 A1 16
QAD9\38
QAD9\23
-KADF1 -KADR1 17
A2 50.6 A2 50.7 QAD9\24
52
A B
51
QAD9\14 QAD9\20
CLOSE
FAULT
OPEN
A1 A1
-XCSAD1 3 1 6 4 9 8 7
x1 x1 x1
1 3 1 3 A2 A2
-RODF1 -RCDR1 -HR -HR -HG
x2 x2 x2
P1
2 4 2 4 A1 A1 QAD9\14 QAD9\20
-MXAD9 C2 x1 x1 x1
TO LCS
SERVOMOTOR TERMINAL'S -RRAD9 -RSAD9 Shunt trip coil -HRFAD1 -HRRAD1 -HYRAD1
A2 A2 200~240 Volt -XCAD9 13
-XCSAD1 2 5
C1 A B Red x2 Red x2 Yellow x2
50.0 50.1
QAD9\8 QAD9\8
49.9 / FN(A)
OPEN CLOSE OPEN CLOSE OPEN CLOSE FAULT
14 11 50.6 14 11 50.1 14 11 50.7 14 11 50.8
1 2 49.1 1 2 49.2 12 12 12 12
3 4 49.1 3 4 49.2 24 21 24 21 50.8 24 21 50.7 24 21 50.7
22 22 22 22
5 6 49.1 5 6 49.2
34 31 34 31 50.8 34 31 34 31
13 14 50.2 13 14 50.3 32 32 32 32
21 22 21 22 44 41 44 41 44 41 44 41
53 54 53 54 42 42 42 42
61 62 61 62
73 74 73 74
TITLE : Control Diagram DOL-9 EQ NO : EQ200489/02-R12 Page No:
83 84 83 84
REV 10
21 22 50.1 21 22 50.0
SETRAA AL AMAL 50
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
-FUQA1
010 04A QA1\5
1 2
011
A1
Rotary
handle -RQA1
1 3 5 C2
A2
-QA1 14 11 51.8
12
2 4 6
-MXQA1 C1
24 21
Shunt trip coil QA1\7
22
208~277 Volt QA1\5
34 31 QA1\5
32 91
44 41 SD
42 92 94
QA1
A1 A2
QA1\6
31 AVAILABLE IN MARSHALLING CELL
32
QA1\4
34
11 21 11
OF1 OF2 -RQA1
12 14 22 24 51.3 12 14
QA1 QA1
-EFRQA1
QA1\8 QA1\9 QA1\10 QA1\11 QA1\12 QA1\13
QA1\2
T1
T1
-XCQA1 1 2 3 4 5 6
-Toroid COM CLOSE COM OPEN COM TRIP
QA1\3
Coil CLOSE FEEDBACK OPEN FEEDBACK TRIP FEEDBACK
T2
TO PLC TO PLC TO PLC
T2
BREAKER STATUS
42.7 / PE PE / 52.0
TYPICAL WIRING DIAGRAM FOR ALL OUTGOING MCCB WITH TOROID COIL
DEVICE TAG:-
(BUS-A) - QA1, QA2, QA3, QA4 QA5, QA6, QA7, QA8, QA9, QA11
PE N L1 L2 L3
(BUS-B) - QB1, QB2, QB3, QB4, QB5, QB8, QB9, QB10
OUTGOING TITLE : MCCB Outgoing With (Torid & EQ NO : EQ200489/02-R12 Page No:
Auxiliary)-QA1 REV 10
SETRAA AL AMAL 51
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
1 3 5
Rotary
-QA10 handle
2 4 6
11 21 81
OF1 OF2 SDE
QA10 12 14 QA10 22 24 QA10 82 84
-XCQA10 1 2 3 4 5 6
COM CLOSE COM OPEN COM TRIP
CLOSE FEEDBACK OPEN FEEDBACK TRIP FEEDBACK
TO PLC TO PLC TO PLC
BREAKER STATUS
51.4 / PE PE / 53.0
PE N L1 L2 L3
OUTGOING TITLE : MCCB Outgoing With Auxiliary - QA10 EQ NO : EQ200489/02-R12 Page No:
REV 10
SETRAA AL AMAL 52
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
37.9 / (N1.2) (N1.2) / 54.0 MCCB Outgoing With (Toroid & Auxiliary)
37.9 / (L1.2) (L1.2) / 54.0
-FUQB6
020 04A QB6\5
1 2
021
A1
-RQB6
1 3 5 C2
A2
-QB6 14 11 53.8
12
2 4 6
-MXQB6 C1
24 21
Rotary Shunt trip coil QB6\7
22
handle 208~277 Volt QB6\5
34 31 QB6\5
32 91
44 41 SD
AVAILABLE IN MARSHALLING CELL
42 92 94
QB6
A1 A2
QB6\6
31
11 21 11
32
QB6\4 OF1 OF2 -RQB6
34 12 14 22 24 53.4 12 14
QB6 QB6
QB6\8 QB6\9 QB6\10 QB6\11 QB6\12 QB6\13
-EFRQB6
-XCQB6 1 2 3 4 5 6
COM CLOSE COM OPEN COM TRIP
QB6\2
T1 CLOSE FEEDBACK OPEN FEEDBACK TRIP FEEDBACK
T1 TO PLC TO PLC TO PLC
-Toroid
QB6\3 BREAKER STATUS
Coil
T2
T2
52.5 / PE PE / 54.6
TYPICAL WIRING DIAGRAM FOR ALL OUTGOING MCCB WITH TOROID COIL
PE N L1
DEVICE TAG:- (BUS-B) - QB6, QB7
OUTGOING TITLE : MCCB Outgoing With (Torid & EQ NO : EQ200489/02-R12 Page No:
Auxiliary)-QB6 REV 10
SETRAA AL AMAL 53
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
-FUQB11
020 04A QB11\6
1 2
021
QB11\11 QB11\11
Rotary 01
handle S1
I1+
1 3 5 C2 A1
-CT1
0~600Amps QB11\12 QB11\12
-QB11 -RQB11 (MCT-300/60A) S2 02
-MXQB11 C1 A2 I1-
2 4 6 14 11 54.3 QB11\8
Shunt trip coil QB11\13 QB11\13
208~277 Volt 12 QB11\6 03
24 21 91
QB11\6
S1
I2+
22 -CT2
34 31 -SD 0~600Amps QB11\12 QB11\12
32 92 94 S2 04
44 41
QB11 (MCT-300/60A) I2-
A1 A2
42 QB11\7
31 QB11\14 QB11\14
05
S1
I3+
32 -CT3
QB11\5
0~600Amps QB11\12 QB11\12
34 (MCT-300/60A) S2 06
I3-
PE Digital Ammeter
-EFRQB11
(METSEDM3110)
QB11\9 -DAQB11
54.6 / (T1) T1 11
VN
QB11\10
08
54.6 / (T2) T2 V1
09
V2
10
V3
021
13
N(-)
AVAILABLE IN MARSHALLING CELL QB11\2
12
L(+)
11 21 11 T1
54.2 / (T1)
OF5 OF2 -RQB11
54.2 12 14 -Toroid
QB11 12 14 QB11 22 24
Coil
54.2 / (T2)
QB11\15 QB11\16 QB11\17 QB11\18 QB11\19 QB11\20 T2
53.5 / PE PE / 55.0
-XCQB11 1 2 3 4 5 6
COM CLOSE COM OPEN COM TRIP
CLOSE FEEDBACK OPEN FEEDBACK TRIP FEEDBACK
TO PLC TO PLC TO PLC
BREAKER STATUS
PE N L1 L2 L3
OUTGOING
1 3 5
Rotary
-QB12 handle
2 4 6
QB12\2 QB12\2
01
S1
I1+
-CT4
0~400Amps QB12\3 QB12\3
(MCT-300/400A) S2 02
I1-
QB12\5 QB12\5
03
S1
I2+
-CT5
0~400Amps QB12\3 QB12\3
(MCT-300/400A) S2 04
I2-
QB12\7 QB12\7
05
S1
I3+
-CT6
0~400Amps QB12\3 QB12\3
(MCT-300/400A) S2 06
I3-
PE Digital Ammeter
AVAILABLE IN MARSHALLING CELL
(METSEDM3110)
-DAQB12
11 11 21 81
VN
OF1 OF2 SDE
08 12 14 22 24 82 84
V1 QB12 QB12 QB12
09
V2 QB12\8 QB12\9 QB12\10 QB12\11 QB12\12 QB12\13
10
V3
-XCQB12 1 2 3 4 5 6
021 COM CLOSE COM OPEN COM TRIP
13
N(-) CLOSE FEEDBACK OPEN FEEDBACK TRIP FEEDBACK
QB12\1 TO PLC TO PLC TO PLC
12
L(+) BREAKER STATUS
54.7 / PE PE /
PE N L1 L2 L3
OUTGOING TITLE : MCCB Outgoing With (Ammeter & EQ NO : EQ200489/02-R12 Page No:
Auxiliary)-QB12 REV 10
SETRAA AL AMAL 55
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
Terminals Diagram
X3
Function text Wiring Numbers Target designation Path Placement
1 SPARE OF4QT1:41 35.5
2 = 285 CONTROLLER EXE2:I5 35.6
3 =
XABC1
XAC1
XBBC1
Terminals Diagram
XBC1
Function text Wiring Numbers Target designation Path Placement
1 EXTERNAL SUPPLY VOLTAGE 110 VDC 4 QCEB1:1 13.4
2 = 7 QCEB1:3 13.4
XCA
XCAD1
3 Future Interlock
Terminals Diagram
XCAD1
Function text Wiring Numbers Target designation Path Placement
12 TO LCS QAD1\29 KAD1:54 44.7
13 = QAD1\30 KAD1:62 44.7
14 = QAD1\31 RSAD1:12 44.8
XCAD7
3 Future Interlock
XCAD8
Terminals Diagram
XCAD8
Function text Wiring Numbers Target designation Path Placement
3 Future Interlock
XCAD9
Function text Wiring Numbers Target designation Path Placement
1 TO LCS QAD9\7 50.0
2 =
Terminals Diagram
XCAD9
Function text Wiring Numbers Target designation Path Placement
16 TO LCS QAD9\37 RCDR1:11 50.8
17 = QAD9\38 RSAD9:21 50.8
XCAV1
Terminals Diagram
XCAV1
Function text Wiring Numbers Target designation Path Placement
24 Temperature sensors QAV1\46 KSBAD1:10 39.6
25 Leakage sensors QAV1\47 KSBAD1:11 39.6
26 = QAV1\48 KSBAD1:12 39.7
27 TO LCS HYAV1:x2 39.8
28 = QAV1\26 RFAV1:12 39.8
29 = QAV1\51 RRAV1:21 39.8
30 = QAV1\53 RRAV1:11 39.8
31 = QAV1\54 RFAV1:11 39.8
XCAV4
Terminals Diagram
XCAV4
Function text Wiring Numbers Target designation Path Placement
18 Future Interlock 41.2
19 = QAV4\28 EPBAV4:11 41.3
20 TO LCS QAV4\36 SSAV4:4;RPAV4:41 41.4;41.3
21 = QAV4\35 RPAV4:A1 41.3
22 = QAV4\37 RPAV4:44 41.3
23 = HYAV4:x2 41.8
24 = QAV4\26 RFAV4:14 41.8
25 = QAV4\45 RRAV4:21 41.7
26 = QAV4\47 RRAV4:11 41.8
27 = QAV4\48 RFAV4:11 41.8
XCB
Function text Wiring Numbers Target designation Path Placement
1 T15 16 OF14QMB:411 28.6
2 = 187 RTT2:A1 28.7
3 =
XCE2
Terminals Diagram
XCE2
Function text Wiring Numbers Target designation Path Placement
4 EXTERNAL SUPPLY VOLTAGE 110 VDC 12 QDCM2:3 13.2
XCMA1
XCMAD1
Function text Wiring Numbers Target designation Path Placement
1 FROM MARSHALLING CELL QAD1\10 XCAD1:4 44.1
2 = 44.1
3 = QAD1\19 SSAD1:8 44.3
4 = QAD1\16 XCAD1:7 44.2
5 REMOTE/AVAILABLE FEEDBACK TO PLC QAD1\32 RRAD1:11 44.5
6 = QAD1\33 RRAD1:14 44.5
7 RUN FEEDBACK TO PLC QAD1\34 KAD1:83 44.6
8 = QAD1\35 KAD1:84 44.6
9 FAULT FEEDBACK TO PLC QAD1\36 RSAD1:21 44.7
10 = QAD1\37 RSAD1:22 44.7
11 COM QAD1\38 RSSD1:A2 44.8
12 START/STOP COMMAND FROM PLC 24V DC QAD1\39 RSSD1:A1 44.8
TITLE : Terminal diagram XCE2 XCMA1 XCMAD1 EQ NO : EQ200489/02-R12 Page No:
REV 10
SETRAA AL AMAL 63
JOB ORDER : JO200287-R06
PANEL MCC-02B Manufacturing Co. 81
REFERENCE : SCALE NTS DRAWING NO : AA-EE-013 Total Pages
0 1 2 3 4 5 6 7 8 9
Terminals Diagram
XCMAD1
Function text Wiring Numbers Target designation Path Placement
13 COM QAD1\40 RPSD1:A2 44.9
14 PROTECTION STOP COMMAND FROM PLC 24V DC QAD1\41 RPSD1:A1 44.9
XCMAD7
XCMAD8
Terminals Diagram
XCMAD8
Function text Wiring Numbers Target designation Path Placement
6 REMOTE/AVAILABLE FEEDBACK TO PLC QAD8\29 RRAD8:12 48.5
7 RUN FEEDBACK TO PLC QAD8\30 KAD8:83 48.6
8 = QAD8\31 KAD8:84 48.6
9 FAULT FEEDBACK TO PLC QAD8\32 RSAD8:21 48.6
10 = QAD8\33 RSAD8:22 48.6
11 COM QAD8\34 RSSD8:A2 48.8
12 START/STOP COMMAND FROM PLC 24V DC QAD8\35 RSSD8:A1 48.8
13 COM QAD8\36 RPSD8:A2 48.9
14 PROTECTION STOP COMMAND FROM PLC 24V DC QAD8\37 RPSD8:A1 48.9
XCMAD9
Terminals Diagram
XCMB1
Function text Wiring Numbers Target designation Path Placement
1 FROM MARSHALLING CELL (BUSA) 172 RT1:44 28.0
2 = 171 QMBCE:312 28.1
3 = 181 RT2:14 28.3
4 = 179 R4:14 28.2
5 CLOSE 214 RBO1:A1 29.6
6 COM 215 RBO1:A2 29.6
7 = 216 RBC1:A1 29.8
8 CLOSE 217 RBC1:A2 29.8
XCMT1
XCMVA1
Terminals Diagram
XCMVA1
Function text Wiring Numbers Target designation Path Placement
6 FROM MARSHALLING CELL QAV1\32 RFAV1:34 39.2
7 = SSAV1:1 39.2
8 = QAV1\38 SSAV1:8 39.4
9 = QAV1\39 RCAV1:A1 39.4
10 REMOTE/AVAILABLE FEEDBACK TO PLC QAV1\55 RREAV1:11 39.6
11 = QAV1\56 RREAV1:14 39.6
12 RUN FEEDBACK TO PLC QAV1\57 RRAV1:41 39.7
13 = QAV1\58 RRAV1:44 39.7
14 FAULT FEEDBACK TO PLC QAV1\59 RFAV1:21 39.7
15 = QAV1\60 RFAV1:22 39.7
16 COM QAV1\61 RSSV1:A2 39.8
17 START/STOP COMMAND FROM PLC 24V DC QAV1\62 RSSV1:A1 39.8
18 COM QAV1\63 RPSV1:A2 39.9
19 PROTECTION STOP COMMAND FROM PLC 24V DC QAV1\64 RPSV1:A1 39.9
XCMVA4
Terminals Diagram
XCMVA4
Function text Wiring Numbers Target designation Path Placement
12 RUN FEEDBACK TO PLC QAV4\51 RRAV4:41 41.6
13 = QAV4\52 RRAV4:44 41.6
14 FAULT FEEDBACK TO PLC QAV4\53 RFAV4:21 41.7
15 = QAV4\54 RFAV4:22 41.7
16 COM QAV4\55 RSSV4:A2 41.8
17 START/STOP COMMAND FROM PLC 24V DC QAV4\56 RSSV4:A1 41.8
18 COM QAV4\57 RPSV4:A2 41.9
19 PROTECTION STOP COMMAND FROM PLC 24V DC QAV4\58 RPSV4:A1 41.9
XCP1
XCP2
XCQA1
Terminals Diagram
XCQA1
Function text Wiring Numbers Target designation Path Placement
5 COM QA1\12 RQA1:11 51.8
6 TRIP QA1\13 RQA1:12 51.8
XCQA10
XCQAV5
XCQB6
Function text Wiring Numbers Target designation Path Placement
1 COM QB6\8 OF1QB6:11 53.7
2 CLOSE QB6\9 OF1QB6:14 53.7
Terminals Diagram
XCQB6
Function text Wiring Numbers Target designation Path Placement
3 COM QB6\10 OF2QB6:21 53.7
4 OPEN QB6\11 OF2QB6:22 53.7
5 COM QB6\12 RQB6:11 53.8
6 TRIP QB6\13 RQB6:12 53.8
XCQB11
Function text Wiring Numbers Target designation Path Placement
1 COM QB11\15 OF5QB11:11 54.2
2 CLOSE QB11\16 OF5QB11:14 54.2
3 COM QB11\17 OF2QB11:21 54.3
4 OPEN QB11\18 OF2QB11:22 54.3
5 COM QB11\19 RQB11:11 54.3
6 TRIP QB11\20 RQB11:12 54.3
XCQB12
Terminals Diagram
XCQMA
Function text Wiring Numbers Target designation Path Placement
1 EASERGY RELAY TRIP FEEDBACK TO PLC 147 RRA:11 27.5
2 = 148 RRA:14 27.5
3 CLOSE FEEDBACK TO PLC 149 OF2QMA:21 27.6
4 COM 150 OF2QMA:24 27.6
5 ALARM TEMPERATURE FEEDBACK TO PLC 151 OF3QMA:31 27.7
6 COM 152 OF3QMA:32 27.7
7 CLOSE 153 RSD1:31 27.8
8 PRESSURE FEEDBACK TO PLC 154 RSD1:32 27.8
9 EASERGY RELAY TRIP FEEDBACK TO PLC 155 RTT1:21 27.5
10 = 156 RTT1:24 27.5
11 CLOSE FEEDBACK TO PLC 0155 RTT1:31 27.6
12 COM 0156 RTT1:34 27.6
13 ALARM TEMPERATURE FEEDBACK TO PLC 157 RAT1:11 27.7
14 OPEN 158 RAT1:14 27.7
15 PRESSURE FEEDBACK TO PLC 159 RPS1:11 27.8
16 = 160 RPS1:14 27.8
17 OIL LEVEL / GAS FEEDBACK TO PLC 161 ROLG1:11 27.9
18 = 162 ROLG1:14 27.9
19 EASERGY RELAY TRIP FEEDBACK TO PLC 163 EPR1 (QMA):3/G/1:19 27.5
20 = 164 EPR1 (QMA):3/G/1:20 27.5
XCQMB
Terminals Diagram
XCQMB
Function text Wiring Numbers Target designation Path Placement
6 COM 201 OF3QMB:32 29.7
7 FAULT FEEDBACK TO PLC 202 RSD2:31 29.8
8 CLOSE 203 RSD2:32 29.8
9 EASERGY RELAY TRIP FEEDBACK TO PLC 204 RTT2:21 29.5
10 = 205 RTT2:24 29.5
11 CLOSE FEEDBACK TO PLC 0204 RTT2:31 29.6
12 COM 0205 RTT2:34 29.6
13 OPEN 206 RAT2:11 29.7
14 COM 207 RAT2:14 29.7
15 CLOSE 208 RPS2:11 29.8
16 = 209 RPS2:14 29.8
17 OIL LEVEL / GAS FEEDBACK TO PLC 210 ROLG2:11 29.9
18 = 211 ROLG2:14 29.9
19 EASERGY RELAY TRIP FEEDBACK TO PLC 212 EPR2 (QMB):3/G/1:19 29.5
20 = 213 EPR2 (QMB):3/G/1:20 29.5
XCQT1
Terminals Diagram
XCRA1
Function text Wiring Numbers Target designation Path Placement
1 AVAILABLE IN MARSHALLING CELL (BUSA) 24 VMR1:11 14.0
2 VMR STATUS TO REMOTE (PLC) 31 VMR1:14 14.0
XCRB1
XCSAD1
XCSS
Function text Wiring Numbers Target designation Path Placement
1 SELECTOR SWITCH REMOTE FEEDBACK TO PLC 256 RT3:21 31.8
2 = 257 RT3:24 31.8
3 SELECTOR SWITCH AUTO FEEDBACK TO PLC 258 RA2:31 31.9
Terminals Diagram
XCSS
Function text Wiring Numbers Target designation Path Placement
4 SELECTOR SWITCH AUTO FEEDBACK TO PLC 259 RA2:34 31.9
XTC1
XTC2
Function text Wiring Numbers Target designation Path Placement
1 EXTERNAL SUPPLY VOLTAGE 110 VDC 7 QCET2:1 13.7
2 = 4 QCET2:3 13.7
XV1
XV2
Terminals Diagram
XV2
Function text Wiring Numbers Target designation Path Placement
2 VR1
3 VY1
4 VB1
XV3
2 VR1
3 VY1
4 VB1
XV4
Function text Wiring Numbers Target designation Path Placement
1 FROM TRANSFORMER NEUTRAL CT 111 EPR2 (QMB):4T101 20.7
2 = 112 EPR2 (QMB):4T104 20.7
3 FROM MV SWITCHGEAR CT INPUT FOR DIFFERENTIAL PROTECTION 113 EPR2 (QMB):4T107 20.7
4 = 110;110 20.7;20.7
EPR2 (QMB):4T103;EPR2 (QMB):4T106
5 = 105 EPR2 (QMB):4T110 20.7
Terminals Diagram
XV4
Function text Wiring Numbers Target designation Path Placement
6 FROM MV SWITCHGEAR CT INPUT FOR DIFFERENTIAL PROTECTION 104 EPR2 (QMB):4T112 20.7
XVT1
XVT2
Bill of Quantities
Device tag Function text Part Number Quantity Device tag Function text Part Number Quantity
42.3;43.7;45.7;47.7;49.7;51.4;53.4;54.3
AA1...AA3;BA1...BA3 ME Ammeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90°/ ME96-3200A 6 EPBAV1;EPBAV4 Push Button Emergency turn release XB4BS8442 2
96x96mm- 0~3200Amps (22mm/IEC947/IP66/NEMA.4) Red color
15.5;19.5 39.2;41.3
AutoSS1 Auxiliary contact for Normally Open use to extension for ZBE101 1 EPR1 (QMA);EPR2 (QMB) Easergy Protection Relay P3T32, Transformer Protection REL52504 2
selector switch Relay with Differential Protection
33.5 14.7;20.7
CLMA1...CLMA6;CLMB1...CLMB6 GV2 ME,P,L Current Limiting Module (Ie-32A, <=100kA, GV1L3 12 ETHSA1;ETHSB1 SDS-3016-2GTXSmart Managed Ethernet switch with 14 SDS-3016-2GTX 2
Ue-690VAC) 10/100BaseT(X) ports, 2 10/100/1000BaseT(X) ports,
and -10 to 60°C operating temperature, dual power
10.0...10.4;11.0...11.4 32.1;32.6
supply 12/24/48 VDC
CONTROLLER1 TM221 Modicon Module/ Ethernet I/O Relays-16 / TM221ME16R 1 FAF1...FAF4;FAH1...FAH7;FBF1;FBF2;FBH1...FBH9 Fuse carriers STI Isolatable (500V-IEC 947.3 Iemax-32A) A9N15636+DF2CN06 22
24VDC/ IP20/ EN/IEC 61131-2 1P 10.3x38 mm+Fuse STI Isolatable gG
(100kA/500V-IEC/ NF/ EN 60269-1) 10.3x38- 06 A
33.3 36.0...36.9;37.0...37.9
CONTROLLER EXE1 TM3 Modicon Module/ Out Relays-08/ 24VDC/ IP20/ TM3DQ8R 1 FANA4,A5;FANB4,B5 Fan Schneider/ IP-54/ RAL-7035/ Air flow 72m3/h- 230V/ NSYCVF85M230PF+NS 4
EN/IEC 61131-2 60Hz- 15W+Fan Schneider Exhaust grill & filters/ ABS/ YCAG125LPF
IP-54/ RAL-7035/ CVF 85
34.1 9.4;12.7
CONTROLLER EXE2 TM3 Modicon Module/ Input Relays-08/ 24VDC/ IP20/ TM3DI8 1 FATL1;FATN1;FLAT1;FLBT1;FNAT1;FNBT1 Fuse carriers STI Isolatable (500V-IEC 947.3 Iemax-32A) A9N15636+DF2CN10 6
EN/IEC 61131-2 1P 10.3x38 mm+Fuse STI Isolatable gG
(100kA/500V-IEC/ NF/ EN 60269-1) 10.3x38- 10 A
35.0 25.2;25.4
CT1...CT3;CTAV1...CTAV3 MCT Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: MCT-300/60A 6 FE1;FE2;FMA1;FMA2;FMB1;FMB2;FMT1;FMT2;FP1 Fuse carriers STI Isolatable (500V-IEC 947.3 Iemax-32A) A9N15636+DF2CN04 13
2.6xIth)- 0~600Amps FUQA1;FUQAV5;FUQB6;FUQB11 1P 10.3x38 mm+Fuse STI Isolatable gG
(100kA/500V-IEC/ NF/ EN 60269-1) 10.3x38- 04 A
42.6;42.7;54.6;54.7 23.4;23.8;23.9;24.4;32.1;32.6;33.3;42.2;51.2;53.3;54.2
CT4...CT6 MCT Current Transformer/720V/ 5A/ IEC.60044/ Idyn: MCT-300/400A 3 FVM1;FVM2 Fuse carriers STI Isolatable (500V-IEC 947.3 Iemax-32A) A9N15656+DF2CN04x 2
2.6xIth)- 0~400Amps 3P 10.3x38 mm+Fuse STI Isolatable gG 3
(100kA/500V-IEC/ NF/ EN 60269-1) 10.3x38- 04 A
55.1 14.0;20.0
CTA1...CTA3;CTB1...CTB3;CTNA;CTNB MCT. Current Transformer/ 5P20,25VA,1A/ 400V/ 60Hz/ MCT-55.130E.1 3200/1 8 HA1;HB1 Pilot- Lamp Integral LED bulb(IEC-60947.5/ IP66)- XB4BVG4 2
IEC.61869- 3200Amps A 40~132Volt Red color
14.1;14.2;20.1;20.2 16.6;18.7
CTA4...CTA6;CTB4...CTB6 MCT Current Transformer/ 720V/ 5A/ IEC.60044/ Idyn: MCT-127/3200A 6 HA2;HB2 Pilot- Lamp Integral LED bulb(IEC-60947.5/ IP66)- XB4BVG5 2
2.6xIth)-0~3200Amps 40~132Volt Yellow
15.1;19.1 16.6;18.7
DAQAV5;DAQB11;DAQB12 Digital 3P/ Ammeter/ Class 1.0/ Class A/ IP50/ METSEDM3110 3 HA3;HB3 Pilot- Lamp Integral LED bulb(IEC-60947.5/ IP66)- XB4BVG6 2
96x96mm/Se.1A~5A/230VAC 40~132Volt Blue color
42.8;54.8;55.3 16.6;18.7
EAFAN1...EAFAN4;EBFAN1;EBFAN2;FANA1...FANA3 Fan Schneider/ IP-54/ RAL-7035/ Air flow 307m3/h- NSYCVF300M230PF+N 12 HA4;HB4;HDC;HT1 Pilot Light bodies (fixing collar+LED light block)- 24~120 ZB4BVBG1+ZB4BV043 4
FANB1...FANB3 230V/ 60Hz- 37W+Fan Schneider Exhaust grill & filters/ SYCAG223LPF AC/DC White color+Pilot Light bodies head
ABS/ IP-54/ RAL-7035/CVF 300 Ø22/IK06/IP66 plain lens integral LED- Red color
9.1...9.3;12.3...12.5;36.7...36.9;37.8 13.8;27.1;29.1;30.7
Bill of Quantities
Device tag Function text Part Number Quantity Device tag Function text Part Number Quantity
HA5;HB5;HT2 Pilot Light bodies (fixing collar+LED light block)- 24~120 ZB4BVBG1+ZB4BV033 3 KMCAD1 MiniCAS II, 230 VAC Supervision relay Customer Supplied Rel 1
AC/DC White color+Pilot Light bodies head ay (MiniCAS II)
Ø22/IK06/IP66 plain lens integral LED-Green color
27.2;29.2;30.7 44.5
HA6;HA7;HB6;HB7;HT3 Pilot Light bodies (fixing collar+LED light block)- 24~120 ZB4BVBG1+ZB4BV083 5 KSBAD1;KSBAD2 Temperature and leakage relay type ABS CA 462 Customer Supplied Rel 2
AC/DC White color+Pilot Light bodies head ay (16907006)
Ø22/IK06/IP66 plain lens integral LED- Yellow color
27.3;29.3;30.8 39.6;46.5
HAE1...HAE7;HBE1...HBE8 Resistance Heater Schneider/ Class II/ 110-230 Volt/ NSYCR150WU2 16 MCHQMA;MCHQMB;MCHQT1 Motor Mechanism for Air Circuit Breaker NW D.out type 48523 3
60Hz- 150 Watts DC-100~130Volt
36.0...36.6;37.0...37.7;37.9 26.3;28.3;30.3
HAG1...HAG7;HBG1...HBG9 Thermostat Schneider for NO+NC control/ 05A/ 230V/ NSYCCOHY230VER 16 MNQMA;MNQMB;MNQT1 MN under voltage release (IEC-947/ 0.85xUn) ACB-NW 48503 3
60Hz (Hygrometer) D.out.130Volt AC/DC
36.0...36.6;37.0...37.7;37.9 26.4;28.4;30.4
HGAD1;HGAD7;HGAD8;HGAV1;HGAV4 Pilot, Lamp Integral LED bulb (IEC-60947.5/ XB7EV03MP 5 MXAD1;MXAD7...MXAD9 Shunt trip coil for (IEC-60947-2/ 0.7xUn) GVAS226 4
IP65)-230~240Vol Green color MCB-GV2-3/220~240Volt/ 60Hz
39.8;41.8;44.7;46.8;48.7 44.5;46.4;48.5;50.6
HMI1;HMI4 VFD- Altivar Remote Operator Graphic Display Terminal VW3A1112 2 MXQA1;MXQAV5;MXQB6;MXQB11 Shunt trip coil for (IEC-60947-2/ 0.7xUn) MCCB- LV429387 4
Mounting Kit NSX100/630-208~277 Volt
38.9;40.9 42.2;51.2;53.2;54.2
HRAD1;HRAD7;HRAD8;HRAV1;HRAV4;HRFAD1 Pilot, Lamp Integral LED bulb (IEC-60947.5/ IP65) XB7EV04MP 7 MXQMA;MXQMB;MXQT1 MX opening release (IEC-947/ 0.85~1.1xUn) ACB 48493 3
HRRAD1 -230~240Volt Red color D.out-NW- 130Volt AC/DC
39.8;41.7;44.7;46.7;48.7;50.7;50.8 26.2;28.2;30.2
HYAD1;HYAD7;HYAD8;HYAV1;HYAV4;HYRAD1 Pilot, Lamp Integral LED bulb (IEC-60947.5/ IP65) XB7EV05MP 6 OF1QA1;OF1QA10;OF1QB6;OF1QB12;OF2QA1 Auxiliary contact (IEC-60947) MCCB-INS/NS/NSX 29450 18
-230~240Volt Yellow OF2QA10;OF2QAV5;OF2QB6;OF2QB11;OF2QB12 100/630- OF/ SDE/ SDV
OF5QAV1;OF5QB11;SDEQA10;SDEQB12;SDQA1
39.8;41.8;44.8;46.8;48.8;50.8
SDQB6;SDQB11;SDQVA5
42.2;42.3;51.3;51.7;52.4;52.5;53.3;53.7;54.2;54.3;55.6...55.8
K1 CAD Contactor (440V/ IEC.947/ AC-7a/ 3NO+2NC) coil CAD32M7 1 OF1QMA;OF1QMB;OF1QT1 Auxiliary contact for (IEC-60947.5.1) Air Circuit 48468 3
supply- 220V/ 60Hz Breaker-NW D.out 4Nos.OF
25.2 26.1;28.1;30.1
K25;R1...R9;RAC1;RAO1;RBC1;RBO1;RPAD1;RPSD1 14 - Pin plug miniature control relay (IEC-255.1) base for RXZE2M114+RXM4AB1 27 PBFV1;PBFV4;PBSAD1;PBSAD7;PBSAD8 Push Button spring return (22mm/ IEC/EN.947/ IP54/ XB7NA42 5
RPSD7;RPSD8;RPSV1;RPSV4;RSSD1;RSSD7;RSSD8 250V/ 10Amps+14- Pin plug in control relay (IEC/EN BD AC-15) 1N/C Red color
RSSV1;RSSV4;RTC1;RTO1 61810-1/ 6Amps) 24 VDC Supply
27.6;27.8;29.6;29.8;30.8;30.9;33.1;33.3...33.5;33.7;33.8;34.2;39.8;39.9;41.8 39.2;41.3;44.1;46.1;48.1
41.9;44.8;44.9;46.8;46.9;48.8;48.9;50.9
KAD1...KAD6;KADB1...KADB6 LC1-D 3P Contactor (690V/ IEC947/ AC-3/ 60°) coil LC1D25M7+LADN31 12 PBLTA1;PBLTB1;PBLTT1;PBRRA;PBRRB;PBRRT Push Button spring return(22mm/ XB4BA21 6
220Volt/ 60Hz- 25 Amps+LC1 front mounting IEC/EN.947/IP66/AC-15) 1N/O Black color
instantaneous auxiliary contact blocks- 03-NO + 01-NC
10.1...10.4;11.0...11.4;44.1 25.5;25.7;25.8;27.1;29.0;30.7
KAD7;KAD8;KADB7;KADB8;KADF1;KADR1;KBDF1 LC1-D 3P Contactor (690V/ IEC947/ AC-3/ 60°) coil LC1D09M7+LADN31 8 PBNV1;PBNV4;PBRAD1;PBRAD7;PBRAD8 Push Button spring return (22mm/ XB7NA31 5
KBDR1 220Volt/ 60Hz- 09 Amps+LC1 front mounting IEC/EN.947/IP54/AC-15) 1N/O Green color
instantaneous auxiliary contact blocks- 03-NO + 01-NC
11.5...11.7;46.1;48.1;50.0;50.1 39.2;41.3;44.1;46.1;48.1
KDC1 TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 - <=440 V LC1D098FD 1 PBRVA1;PBRVA4;PLTAD1;PLTAD7...PLTAD9;PLTAV1 Push Button spring return (22mm/ XB7NA21 9
20 A - 110 V DC coil PLTAV4;PRSAD1 IEC/EN.947/IP54/AC-15) 1N/O Black color
13.0 38.6;39.7;40.6;41.7;44.6;46.6;48.6;50.7
Bill of Quantities
Device tag Function text Part Number Quantity Device tag Function text Part Number Quantity
PM1 (QMA);PM2 (QMB) PowerLogic Digital Meter with Backlit LCD display. METSEPM5320 2 QAV4;QBV6 GV2-L14 3P Magnetic Trip Unit 100kA/ 415V/ IEC-947/ GV2L14 2
Reading with all Measurements including Accuracy 0.5, AC.3- 10 Amps
2DO/2SI, 31ind Harmonic, 28 Alarms, Ethernet, Multi
15.6;19.6
Tariff, Logging, Supply Voltages- 100...415VAC 9.4;12.6
POAD1 MS-20 Positioner Entry Signal 4/20 Ma. Output Signal MS-20 Positioner (Cust 1 QAV5;QAV6;QBV1;QBV2 NSX. 3P MCCB Magnetic Trip Unit 630H LV432950+LV432538+ 4
4/20 Ma. 230volt AC omer Supply) (70kA/415V/IEC947/1.3M)-500 A+Chassis 3 pole plug-in device LV432532+LV432533
with connection for MCCB-NSX 400/630 Amps+Chassis 4/3 pole
side plates for base compact kit+Chassis 4/3 pole side plates
50.4 9.7;9.8;12.1;12.2 for breaker compact
PS1 External Power supply, protective coating, In 2320911 1 QB2 NSX 3P MCCB Adjustable 100H (70kA/415V-IEC947/ LV429674 1
100VAC-110VDC/ Out 24VDC- 10A 50°C/ TMD)- 40Amps
13.8 11.1
QA1...QA4;QB4;QB5;QB10 NSX 3P MCCB Adjustable 100H (70kA/415V-IEC947/ LV429672 7 QB6;QB7 NSX 3P MCCB Adjustable 100H (70kA/415V-IEC947/ LV429670 2
50°C/ TMD)- 63Amps 50°C/ TMD)-100Amps
10.0...10.3;11.3;11.7 11.4;11.5
QA5;QA11;QB9 NSX 3P MCCB Adjustable 100H (70kA/415V-IEC947/ LV429673 3 QB8 NSX 3P MCCB Adjustable 250H (70kA/415V-IEC947/ LV431671 1
50°C/ TMD)- 50Amps 50°C/ TMD)-200Amps
10.3;10.8;11.6 11.5
QA6;QA8;QB1 NSX 3P MCCB Adjustable 100H (70kA/415V-IEC947/ LV429677 3 QB11;QB12 NSX 3P MCCB Adjustable 400H (70kA/415V-IEC947/ Micro. LV432695+LV432538+ 2
50°C/ TMD)- 16Amps 2.3)-400Amps+Chassis 3 pole plug-in device with connection LV432532+LV432533
for MCCB-NSX 400/630 Amps+Chassis 4/3 pole side plates for
base compact kit+Chassis 4/3 pole side plates for breaker
10.4;10.5;11.0 11.8 compact
QA7 NSX 3P MCCB Adjustable 100H (70kA/415V-IEC947/ LV429676 1 QCA1;QCA2;QCB1;QCB2 iC60L 4Pole MCB (Icu-25kA/415V-IEC947,Class-3/ 50°C/ A9F94406 4
50°C/ TMD)- 25Amps C-curve)- 06Amps
10.5 16.2;16.7;18.2;18.7
QA9;QB3 NSX 3P MCCB Adjustable 100H (70kA/415V-IEC947/ LV429675 2 QCAD1;QCAD7...QCAD9;QCDAD1;QCDAD7...QCDAD9 iC60L 2Pole MCB (Icu-25kA/415V-IEC947,Class-3/ 50°C/ A9F94204 10
50°C/ TMD)- 32Amps QCDAV1;QCDAV4 C-curve)- 04Amps
10.6;11.2 39.1;41.1;43.4;43.7;45.3;45.7;47.3;47.7;49.4;49.7
QA10 NSX 3P MCCB Adjustable 250H (70kA/415V-IEC947/ LV431670 1 QCAV1;QCAV4 iC60L 2Pole MCB (Icu-25kA/415V-IEC947,Class-3/ 50°C/ A9F94210 2
50°C/ TMD)-250Amps C-curve)- 10Amps
10.7 38.2;40.2
QAD1...QAD6;QBD1...QBD6 GV2-P21 Thermal-magnetic trip unit GV2P21+GVAD0110 12 QCEA1;QCEB1;QCET1;QDCM1;QDCM2 C60H-DC 2Pole MCB (Icu-20kA/250VDC-IEC 947-2/ 40°/ A9N61528 5
(50kA/415V/IEC-947)- 17-23 Amps+Auxiliary contact C-curve)- 10Amps
(IEC-60947) for MCB-GV2/3- 1NO + fault (Side
10.0...10.4;11.0...11.4
mounting) 13.1...13.4;13.6
QAD7;QAD8;QBD7;QBD8 GV2-P14 Thermal-magnetic trip unit GV2P14+GVAD0110 4 QCET2;QDC1;QDCE1;QDCE2 C60H-DC 2Pole MCB (Icu-20kA/250VDC-IEC 947-2/ 40°/ A9N61524 4
(130kA/415V/IEC-947)- 6-10 Amps+Auxiliary contact C-curve)- 04Amps
(IEC-60947) for MCB-GV2/3- 1NO + fault (Side
10.5;11.5
mounting) 13.1;13.2;13.7;13.9
QAD9;QBD9 GV2-P07 Thermal-magnetic trip unit GV2P07+GVAD0110 2 QMA;QMB;QT1 NW 4P-H1 Drawout type 3200 Amps+Micrologic 48317+48500+48407+ 3
(130kA/415V/IEC-947)- 1.6-2.5 Amps+Auxiliary contact 6.E+Chassis 3200Amps+ Top rear ¶48159+48164
(IEC-60947) for MCB-GV2/3- 1NO + fault (Side conn.-2100/3200A+Bottom rear conn.-2100/3200A
10.6;11.6
mounting) 8.2;8.5;8.7
QAV1...QAV3;QBV3...QBV5 NSX. 3P MCCB Magnetic Trip Unit 100H LV429761+29450 6 QMACE;QMBCE;QT1CE Auxiliary contact switches NS/NT/NW Chassis Connected 33751 3
(70kA/415V/IEC947/MA)-50Amps+Auxiliary contact position (CE)
(IEC-60947) MCCB-INS/CVS/NSX 100/630- OF/SDE/SDV
9.1...9.3;12.3...12.5 26.1;28.1;30.1
Bill of Quantities
Device tag Function text Part Number Quantity Device tag Function text Part Number Quantity
QMACT;QMBCT;QT1CT Auxiliary contact switches NS/NT/NW Chassis Test 33753 3 SPD1;SPD2 Surge Arrestors PRD D.out/ Type-2/ Imax(8/20us) 65kA/ A9L65601 2
position (CT) 3P+N/ IP20/indicator
26.1;28.1;30.1 14.2;20.2
QS1;QS2 NG125L 4Pole MCB (Icu-50kA/415V-IEC 947-2/ 40°C/ 18818 2 SS1;SSD9 Selector Switch Standard - A-0-M 3Position (IEC-947.5/ XB4BD33 2
C-curve)- 80Amps IP66/4X) 1contact
14.2;20.2 31.1;50.0
RA1;RA2;RAT1;RAT2;RM1;RM2;ROF1...ROF3;ROLG1 14 - Pin plug miniature control relay (IEC-255.1) base for RXZE2M114+RXM4AB1 26 SSA;SSB;SST Selector Switch Standard Spring return to center XB4BD53 3
ROLG2;RPS1;RPS2;RRA;RRB;RRT;RSD1...RSD3;RSDA 250V/ 10Amps+14- Pin plug in control relay (IEC/EN FD 3Position (IP67/4X/2NO)
RSDB;RT1...RT3;RTT1;RTT2 61810-1/ 6Amps) 110 VDC Supply
26.4...26.9;28.5...28.9;30.4...30.6;31.1...31.6 26.1;28.1;30.1
RCAV1;RCAV4;RCDR1;RFAV1;RFAV4;RKAD1;RKAD2 14 - Pin plug miniature control relay (IEC-255.1) base for RXZE2M114+RXM4AB1 29 SSAD1;SSAD7...SSAD9;SSAV1;SSAV4 Selector Switch Standard- 4 Position 3 contact (IEC-947/ PR12 2303A4 6
RLAD1;RLAD7;RLAD8;RODF1;RPAV1;RPAV4;RQA1 250V/ 10Amps+14- Pin plug in control relay (IEC/EN P7 IP55/ 4X/ ATS Use)
RQB6;RQB11;RQVA5;RRAD1;RRAD7...RRAD9;RRAV1 61810-1/ 6Amps) 230 VAC/ 60Hz
RRAV4;RREAV1;RREAV4;RSAD1;RSAD7...RSAD9
39.2;39.4...39.7;41.3;41.5;41.6;42.2;44.4;44.6;46.3;46.4;46.6;48.4...48.6 39.2;41.3;44.1;46.1;48.1;50.1
50.5...50.7;51.3;53.4;54.2
REMOTE Auxiliary contact for Normally Closed use to extension for ZBE102 1 SSP1 Selector Switch Standard- A-0-M 3Position Key Lock XB4BG03 1
selector switch (IEC-947.5/ IP66/4X)
31.3 35.2
RESQMA;RESQMB;RESQT1 Remote reset after fault trip for Air Circuit Breaker NW 48473 3 Synchro-check Relay ComAp InteliMains NT Synchro-Check relay without IM-NT-BB 1
Drawout~240 Volt display
25.5;25.7;25.8 33.0
RHA1...RHA11;RHAV1...RHAV3;RHB1...RHB10 Rotary Extended handle use Moulded Case Circuit LV429338 27 TAH1...TAH4;TBH5;TBH6 Thermostat Schneider for NO control/ 10A/ 120-250V NSYCCOTHO 6
RHVB3...RHVB5 Breaker type NSX 100/250 (Cooling system)
9.1...9.3;10.0...10.8;11.0...11.7;12.3...12.5 36.7...36.9;37.8
RHAV5;RHAV6;RHB11;RHB12;RHVB1;RHVB2 Rotary Extended handle use Moulded Case Circuit LV432598 6 TRDA1;TRDA7...TRDA9;TRVA1;TRVA4 Stepdown Transformer- 1P/IP00/40°C/IC-B/ 230/400V & EL100VA1 6
Breaker type NSX 400/630 115/230V- 100 VA
9.7;9.8;11.8;12.1;12.2 38.3;40.3;43.6;45.6;47.6;49.6
RHDA1...RHDA9;RHDB1...RHDB9;RHVA4;RHVB6 Rotary Handle extended use GV2 (standard/ IP54) Motor GV2APN01 20 Toroid CoilAD1...Toroid CoilAD9;Toroid Toroid Coil closed 50/60Hz, Icw-100/0.5S, TA30 Dia 30 50437 35
Circuit Breaker CoilBD1...Toroid CoilBD9;Toroid CoilQA1...Toroid mm - 65 Amps
CoilQA10;Toroid CoilQB1...Toroid CoilQB5;Toroid
9.4;10.0...10.6;11.0...11.6;12.7
CoilQB9;Toroid CoilQB10
10.0...10.6;10.8;11.0...11.7
RJ1;RJ4 VFD-Remote Operator Terminal Cable equipped with 2 VW3A1104R50 2 Toroid CoilQAV1;Toroid CoilQAV2;Toroid CoilQBV1 Toroid Coil closed 50/60Hz, Icw-100/0.5S,GA300 Dia 50442 4
RJ45 - 05M Toroid CoilQBV2 300mm- 630Amps
38.8;40.8 9.7;9.8;12.1;12.2
SDEQMA;SDEQMB;SDEQT1 Auxiliary contact for (IEC-60947.5.1) Air Circuit 48475 3 Toroid CoilQB6;Toroid CoilQB7 Toroid Coil closed 50/60Hz, Icw- 100/0.5S, IA80 Dia 80 50439 2
Breaker-NW D.out 1No.SDE mm - 160Amps
26.6;28.6;30.5 11.4;11.5
SINUSA1...SINUSA3;SINUSB1...SINUSB3 VFD Sinus Dv/dt filter <=1kM Cable/ VW3A5404 6 Toroid CoilQB8 Toroid Coil closed 50/60Hz, Icw-100/0.5S, MA120 50440 1
ATV630-650/IP20/In-050A/22.0KW Dia120mm -250Amps
9.0...9.2;12.3...12.5 11.5
SINUSA4;SINUSB4 VFD Sinus Dv/dt filter <=1kM Cable/ VW3A5402 2 Toroid CoilQB11 Toroid Coil closed 50/60Hz, Icw-100/0.5S, SA200 Dia 50441 1
ATV630-650/IP20/In-015A/05.5KW 200mm- 400Amps
9.3;12.6 11.8
Bill of Quantities
Device tag Function text Part Number Quantity Device tag Function text Part Number Quantity
9.0...9.2;12.3...12.5
9.3;12.6
14.0;20.0
VSS1;VSS2 Voltmeter Selector Switch (Ui 690V/ IEC 947.5/ Ith12A) K1F027MLH 2
Multi fixing 6+OFF
15.7;19.7
16.3;18.3
Voltmeter1;Voltmeter2 ME Voltmeter/ M. Iron/ Class 1.5/ IEC 521/ Scale 90°/ ME96-500 2
96x96mm- 0~500 Volt
15.7;19.7
26.2;28.2;30.2