DDC control panel
"SUPPLY AND INSTALL HVAC CONTROL PANEL SHALL BE COMPLETE WITH MODBUS /
BACNET ALONG WITH DIGITAL DISPLAY, CONTROL WIRING TO EACH DEVICE,
CONDUITS, TRAYS, CONTACTORS, TRANSMITTERS, PUSH BUTTONS, SWITCHES,
FUSES, LEDS, PILOT LAMPS, TERMINAL STRIPS, NAME PLATES, DIFFERENTIAL
PRESSURE SWITCHES, PRESSURE SENSORS, PRESSURE DIFFERENTIAL INDICATOR
AND TRANSMITTER (PDIT), SPACE TEMPERATURE SENSORS, DUCT TEMPERATURE
SENSORS, AIR FLOW SENSORS, HORN AND BEACON, IN-BUILT PROVISION FOR

EXHAUST FANS AUTO CHANGEOVER AND POWER SUPPLY, AND ALARMS. ON-OFF
STATUS OF AHU-1, AHU-2, ACCU-1, ACCU-2, EF- 1, 2 AND CHEMICAL FILTER (CF-1)
BLOWER FAN MOTORS. DIRTY FILTERS STATUS OF AHU-1 & 2, CF-1 SHALL ALSO BE
DISPLAYED. BUILDING DDC PANEL SHALL BE INTERLOCKED WITH FIRE ALARM
CONTROL PANEL (FACP) AND SHALL BE INTERFACED WITH DCS THROUGH SOFT LINK
(MODBUS), BATTERY CHARGERS, UPS THROUGH HARDWIRE. DDC PANEL SHALL BE
UL-916 LISTED. AN INTERLOCK BETWEEN THE HVAC CONTROL PANEL AND BATTERY
HIGH-RATE CHARGING SWITCH SHALL BE PROVIDED, SUCH THAT FAILURE OF THE
AIR-HANDLING UNITS (AHU-1A/1B) AND EXHAUST FANS (EF-1 A/1B) SHALL CAUSE THE
HIGH-RATE CHARGING OF BATTERIES TO STOP. HVAC CONTROL PANEL SHALL BE
FEED FROM REDUNDANT POWER SOURCE. HVAC CONTROL PANEL SHALL BE AS PER
SAES-K-011.
SCOPE OF WORK ALSO INCLUDES:
• WRITTEN DESCRIPTION OF PROPOSED SEQUENCE OF OPERATION.
• BLOCK DIAGRAM SHOWING ALL COMPONENTS AND PROCESSING DEVICES.
• INSTALLATION AND WIRING GUIDE SPECIFICATIONS.
• SYSTEM POINTS LIST.
• INSTALLATION, SUPERVISION, START-UP, AND COMMISSIONING.
• OPERATOR'S TRAINING.
• SERVICE AND MAINTENANCE WARRANTY FOR ONE YEAR FROM
COMMISSIONING."
SUPPLY AND INSTALL HVAC CONTROL PANEL SHALL BE COMPLETE WITH MODBUS /
BACNET ALONG WITH DIGITAL DISPLAY, CONTROL WIRING TO EACH DEVICE,
CONDUITS, TRAYS, CONTACTORS, TRANSMITTERS, PUSH BUTTONS, SWITCHES,
FUSES, LEDS, PILOT LAMPS, TERMINAL STRIPS, NAME PLATES, DIFFERENTIAL
PRESSURE SWITCHES, PRESSURE SENSORS, PRESSURE DIFFERENTIAL INDICATOR
AND TRANSMITTER (PDIT), SPACE TEMPERATURE SENSORS, DUCT TEMPERATURE
SENSORS, AIR FLOW SENSORS, HORN AND BEACON, IN-BUILT PROVISION FOR
EXHAUST FANS AUTO CHANGEOVER AND POWER SUPPLY, AND ALARMS. ON-OFF
STATUS OF AHU-1, AHU-2, ACCU-1, ACCU-2, EF- 1, 2 AND CHEMICAL FILTER (CF-1)
BLOWER FAN MOTORS. DIRTY FILTERS STATUS OF AHU-1 & 2, CF-1 SHALL ALSO BE
DISPLAYED. BUILDING DDC PANEL SHALL BE INTERLOCKED WITH FIRE ALARM
CONTROL PANEL (FACP) AND SHALL BE INTERFACED WITH DCS THROUGH SOFT LINK
(MODBUS), BATTERY CHARGERS, AND UPS THROUGH HARDWIRE. DDC PANEL SHALL
BE UL-916 LISTED. AN INTERLOCK BETWEEN THE HVAC CONTROL PANEL AND
BATTERY HIGH-RATE CHARGING SWITCH SHALL BE PROVIDED, SUCH THAT THE
FAILURE OF THE AIR-HANDLING UNITS (AHU-1A/1B) AND EXHAUST FANS (EF-1 A/1B)
SHALL CAUSE THE HIGH-RATE CHARGING OF BATTERIES TO STOP. HVAC CONTROL
PANEL SHALL BE FEED FROM REDUNDANT POWER SOURCE. THE HVAC CONTROL
PANEL SHALL BE AS PER SAES-K-011.
SCOPE OF WORK ALSO INCLUDES:
• WRITTEN DESCRIPTION OF PROPOSED SEQUENCE OF OPERATION.
• BLOCK DIAGRAM SHOWING ALL COMPONENTS AND PROCESSING DEVICES.
• INSTALLATION AND WIRING GUIDE SPECIFICATIONS.
• SYSTEM POINTS LIST.
• INSTALLATION, SUPERVISION, START-UP, AND COMMISSIONING.
• OPERATOR'S TRAINING.
• SERVICE AND MAINTENANCE WARRANTY FOR ONE YEAR FROM
COMMISSIONING."
"SUPPLY AND INSTALL HVAC CONTROL PANEL SHALL BE COMPLETE WITH MODBUS /
BACNET ALONG WITH DIGITAL DISPLAY, CONTROL WIRING TO EACH DEVICE,
CONDUITS, TRAYS, CONTACTORS, TRANSMITTERS, PUSH BUTTONS, SWITCHES,
FUSES, LEDS, PILOT LAMPS, TERMINAL STRIPS, NAME PLATES, DIFFERENTIAL
PRESSURE SWITCHES, PRESSURE SENSORS, PRESSURE DIFFERENTIAL INDICATOR
AND TRANSMITTER (PDIT), SPACE TEMPERATURE SENSORS, DUCT TEMPERATURE
SENSORS, AIR FLOW SENSORS, HORN AND BEACON, IN-BUILT PROVISION FOR

EXHAUST FANS AUTO CHANGEOVER AND POWER SUPPLY, AND ALARMS. ON-OFF
STATUS OF AHU-1, AHU-2, ACCU-1, ACCU-2, EF- 1, 2 AND CHEMICAL FILTER (CF-1)
BLOWER FAN MOTORS. DIRTY FILTERS STATUS OF AHU-1 & 2, CF-1 SHALL ALSO BE
DISPLAYED. BUILDING DDC PANEL SHALL BE INTERLOCKED WITH FIRE ALARM
CONTROL PANEL (FACP) AND SHALL BE INTERFACED WITH DCS THROUGH SOFT LINK
(MODBUS), BATTERY CHARGERS, AND UPS THROUGH HARDWIRE. DDC PANEL SHALL
BE UL-916 LISTED. AN INTERLOCK BETWEEN THE HVAC CONTROL PANEL AND
BATTERY HIGH-RATE CHARGING SWITCH SHALL BE PROVIDED, SUCH THAT THE
FAILURE OF THE AIR-HANDLING UNITS (AHU-1A/1B) AND EXHAUST FANS (EF-1 A/1B)
SHALL CAUSE THE HIGH-RATE CHARGING OF BATTERIES TO STOP. HVAC CONTROL
PANEL SHALL BE FEED FROM REDUNDANT POWER SOURCE. THE HVAC CONTROL
PANEL SHALL BE AS PER SAES-K-011.
SCOPE OF WORK ALSO INCLUDES:
• WRITTEN DESCRIPTION OF PROPOSED SEQUENCE OF OPERATION.
• BLOCK DIAGRAM SHOWING ALL COMPONENTS AND PROCESSING DEVICES.
• INSTALLATION AND WIRING GUIDE SPECIFICATIONS.
• SYSTEM POINTS LIST.
• INSTALLATION, SUPERVISION, START-UP, AND COMMISSIONING.
• OPERATOR'S TRAINING.
• SERVICE AND MAINTENANCE WARRANTY FOR ONE YEAR FROM
COMMISSIONING."
SUPPLY AND INSTALL HVAC CONTROL PANEL SHALL BE COMPLETE WITH MODBUS /
BACNET ALONG WITH DIGITAL DISPLAY, CONTROL WIRING TO EACH DEVICE,
CONDUITS, TRAYS, CONTACTORS, TRANSMITTERS, PUSH BUTTONS, SWITCHES,
FUSES, LEDS, PILOT LAMPS, TERMINAL STRIPS, NAME PLATES, DIFFERENTIAL
PRESSURE SWITCHES, PRESSURE SENSORS, SPACE TEMPERATURE SENSORS, DUCT
TEMPERATURE SENSORS, AIR FLOW SENSORS, HORN AND BEACON, AND ALARMS.
ON-OFF STATUS OF PACU-1. DIRTY FILTERS STATUS OF PACU-1 SHALL ALSO BE

DISPLAYED. BUILDING DDC PANEL SHALL BE INTERFACED WITH DCS THROUGH SOFT
LINK (MODBUS).
SCOPE OF WORK ALSO INCLUDES:
• WRITTEN DESCRIPTION OF PROPOSED SEQUENCE OF OPERATION.
• BLOCK DIAGRAM SHOWING ALL COMPONENTS AND PROCESSING DEVICES.
• INSTALLATION AND WIRING GUIDE SPECIFICATIONS.
• SYSTEM POINTS LIST.
• INSTALLATION, SUPERVISION, START-UP, AND COMMISSIONING.
• OPERATOR'S TRAINING.
• SERVICE AND MAINTENANCE WARRANTY FOR ONE YEAR FROM
COMMISSIONING."
unit Price Total Price
IO QTY. Qty.
(INR) (INR)
DI: 90
DO: 60
AI: 0
AO: 50
Stand-Alone: DDC
Simplex: IO
Redundant: Power
supply
Redundant:
Communication
HMI: 15 inch.

DI: 90
DO: 60
AI: 0
AO: 50
Redundant: DDC
Simplex: IO
Redundant: Power
supply
Redundant:
Communication
HMI: 15 inch.

DI: 90
DO: 60
AI: 0
AO: 50
Redundant: DDC
Simplex: IO
Redundant: Power
supply
Redundant:
Communication
HMI: 15 inch.

1
DI: 40
DO: 30
AI: 0
AO: 20
Redundant: DDC
Simplex: IO
Redundant: Power
supply
Redundant:
Communication
1
HMI: 15 inch.