HVAC LOAD CALCULATION - E20 FORM SHEET

PROJECT TOWER BUILDING


LOCATION U.A.E (ABU DHABI)
CLIENT XYZ
CONSULTANT ABC
126.00
Area or Sun Gain or Factor
Item Btu/Hour Watts
(U)
ROOM HEAT Q= U*A*ΔT
ROOM SENSIBLE HEAT
Solar Gain - Glass Area ΔT U
Glass - N SqFt x x 0.00
Glass - NE SqFt x x 0.00
Glass - E SqFt x x 0.00
Glass - SE 15.50 SqFt x 13.00 x 0.30 60.45
Glass - S SqFt x x 0.00
Glass - SW 11.62 SqFt x 100.00 x 0.30 348.60
Glass - W SqFt x x 0.00
Glass - NW SqFt x x 0.00
Skylight SqFt x x 0.00
Solar & Transmission Gain - Walls & Roof
Wall - N SqFt x F x 0.00
Wall - NE SqFt x F x 0.00
Wall - E SqFt x F x 0.00
Wall - SE 138.33 SqFt x 37.50 F x 0.05 259.37
Wall - S SqFt x F x 0.00
Wall - SW 128.35 SqFt x 35.50 F x 0.05 227.82
Wall - W SqFt x F x 0.00
Wall - NW SqFt x F x 0.00
Roof 300.00 SqFt x 45.50 F x 0.05 614.25
Transmission Gain - Except Walls & Roof
All Glass 27.10 SqFt x 36.00 F x 0.30 292.68
Partition 46.15 SqFt x 31.00 F x 0.50 715.33
Ceiling SqFt x F x 0.00
Floor 300.00 SqFt x 31.00 F x 0.27 2,511.00
INFILTRATION AND BY PASSED AIR
Infiltration CFM x 36.00 T.Diff x 1.08 0.00
Outside Air 28.00 CFM x 36.00 x 130.64
Internal Heat
People 2.00 Nos. x 230.00 Btu/Hour Per Person 460.00
Lighting 300.00 SqFt x 1.00 W/SqFt x 3.41 1,023.00
Equipments 1.00 200.00 Watts x 3.41 682.00
Power kW/Hp x 0.00
Sub Total 7,325.13
Factor 5-15% 1,098.77
Effective Room Sensible Heat 8,423.90 1.00
ROOM LATENT HEAT
Infiltration 0.00 CFM x 6.00 Gr/Lb x 0.68 0.00
Outside Air 28.00 CFM x 6.00 Gr/Lb x BFx0.68 13.71
People 2.00 Nos. x 120.00 Btu/Hour Per Person 240.00
Sub Total 253.71
Factor 2.5 - 5% 12.69
Effective Room Latent Heat 266.39 2.00
EFFECTIVE ROOM TOTAL HEAT 8,690.30
OUTSIDE AIR HEAT
Sensible 28.00 CFM x 36.00 F(TD) x CF x 1.08 958.00 3.00
Latent 28.00 CFM x 6.00 Gr/Lb x CF x 0.68 100.53 4.00
OUTSIDE AIR TOTAL HEAT 1,058.53
GRAND SUB-TOTAL HEAT 9,748.83
Factor 1 - 3% 292.46
GRAND TOTAL HEAT 10,041.30
TMBH 10.04
TKW 2.91
TSMBH 9,381.90
TSKW 2,720.75
TONS=GRAND TOTAL HEAT/12000 0.84
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
FLOOR Ground Floor
SPACE REFERENCE R-01, Flat-1, Bedroom,Residential (ABU DHABI)
AREA ( SqFt) (WxH) 300.00
Falce Ceiling Height (Ft) 9.40
Volume (CuFt) 2,820.00
Estimate for Summer
Design Conditions DB (°F) WB (°F) RH (%) HR (Gr/Lb)
Ambient(Out Side) 111.00 75.00 19.00 74.00
Room (InDoor) 75.00 63.00 50.00 68.00
Difference Δ 36.00 12.00 31.00 6.00

By Pass Factor (BF) = 0.12


Contact Factor (CF = 1 - BF) = 0.88
CFM Ventilation
CFM Per Person 5.00 No = 2.00 = 10.00
CFM Per SqFt 0.06 Sqft x 300.00 = 18.00
Air Change Per Hour (CFM) =
CFM Cu.ft 2,820.00 x 0.00 x1/60 = 0.00
CFM Infiltration
Swinging x cfm/door = 0.00
Revolving Doors (People) x cfm/door = 0.00
Open Doors x 1.00 cfm/door = 0.00
Crack (feet) x cfm/ft = 0.00
0.00
Supply CFM from Machine
Effective Room Sensible Heat Factor =
Effective Room Sensible Heat/Eff Room Total Heat = 0.97
Apparatus Dew Point (ADP)
Indicated ADP (F) =
Selected ADP (F) = 54.60
Dehumidified Rise
(Room DB - ADP) x CF = 17.95
DEHUMIDIFIED AIR QUANTITY
Effective Room Sensible Heat = 434.49 CFM
Dehumidified Rise x 1.08
= 204.21 L/s
TOTAL HEAT CAPACITY
Grand Total Heat = 0.84 TR

SENSIBLE HEAT CAPACITY


Grand Sensible Heat = 0.84 TR
12,000.00