‘32 Aluminum conductor cables in sizes less than
16 mm? cause termination problems leading to heating
atthe terminals and enhance the possibility ofa fire, For
‘gonductr sizes less than or qual to 16 mim only copper
conductor cables should be used.
‘S83 Switch or lator controlling a water heater or
xeyser should not be located within 1 m from the
Tocation of # shower or bath tub, to avoid a person in
wet condition reaching the switch or isolator. It is
preferable to provide the contol switch ouside the bath
room near the entrance and provide an indieation at
the water heater. A socket or a connector block with
suitable protection against water spray should be
provided to connect the water heater. The above
considerations apply to switches for outdoor lights and
other appliances, with the objective of avoidance of
operation ofa switch when a person is wet.
5844 Sockets in kitchen, bathroom, tlle, garage, ete,
should not be provided within a height of 1 m from the
ground level. Similar ear as o be taken for installations
involving fountains, swimming pools te. Light fitings
fn such areas should be fed at low voltage, preferably
through an isolating transformer with a proper earth
leakage protection. Where possibility of a person in
contact with a wet surface has to operate or ouch an
clectrical switch or an appliance the cireuit should be
protected by a 100/30 mA RCCBIRCD, as applicable
5.85 Selecting and Installing Cables
S851 Cable insulation pes
Forthe purpose of this Code, cables above 1 mm shall
have stranded conductors, All cables when installed, shall,
be adequately protected against mechanical damage. This
canbe eartied outby ether having additional protection,
such a being enclosed in PVC conduit or metal pipes,
or placing the cables ina suitable location that requires
‘no additional protection, The cables for wiring circuits
in electrical installation shall have the appropriate wire
size matching the requirement of the loads and the
following table gives the recommendations for different
types of loads
For the mains cable
For installation wiring
For main earth or main equipotential wire
‘Tough plastic sheathed (TPS) cable
‘Tough plastic sheathed (TPS) cables
Poly vinyl chloride (PVC) insulated conduit
Underground installation and installation in cable trench, PVC insulated, PVC sheathed armored
feeders between buildings, ote
cables or XLPE insulated, PVC sheathed
cebles armoured cables
Installation in plant rooms, switeh rooms ete, on cable tay PVC insulated, PVC sheathed or XLPE
or ladder or protected trench, where risk of mechanical
damage to cable does not exist
insulated, PVC sheathed unarmoured cables
5.8.5.2 Circuit wire sizes
Recommended minimum wire sizes for various citcuits is piven below:
St Circuits Minimum Wire Size Wire Colour
Na.
o 2 8, Ch
i) Teway lighting 2+E cable wires Red-Black-Green or
1.5 mm Green/Yellow
ii) 2-way lighting control (straps 3 wire cable ‘Red-White-Blue
Dotween the 2 switches) 15mm?
iit) Storage water heaters up to 3 KW 2+ E cable
Red-Black-Green or
2.5 mm (stranded conductors) _Green/Yellow
iv) Storage water heaters between 2.4-F cable Red-Black-Green or
3 kW and 6 kW 4 mm’ (stranded conductors) —_Green’Yellow
¥) Socket-outlts and permanent 2+ Beable Red-Black-Green or
‘connection units 2.5 mm (stranded conductors) Green/Yellow
vi) Submains to garages or out 2+E cable Red-Black-Green or
buildings 2,5 mm (stranded conductors) GreenYellow