Professional Documents
Culture Documents
Through Fault Current Monitoring Experience
Through Fault Current Monitoring Experience
ABSTRACT
Italian Transmission System Operator (TSO) TERNA manages about 700 transformers
and auto-transformers with a failure rate that has been kept <1% for several years.
Due to increasing aging of the fleet and the criticality of the asset, significant efforts
have been made to prevent failures and base the asset maintenance basing on the
real condition of the transformer insulation. One of the main causes of failure has
been addressed to the occurrence of unpredictable external events such as over-
voltages, lightning strikes and through-fault currents. The latter ones, in particular,
are speculated to be the indirect cause of winding displacement on autotransformers
and electrical failures on those transformers interconnected to MV grid. The paper
presents the development of a through fault current (TFC) monitoring system aimed
at detecting short circuit currents and demonstrating that the most of events are un-
known to the utility. By recording such activities, it will be possible to rank the trans-
formers, improve maintenance schedule, correlate multiple on-line data and extract
new parameters to be added into the TERNA Health Index.
1
Proceedings of My Transfo 2016 – 15th and 16th November 2016
lation, the second one is now under investigation. - are not recording inrush currents
Speculation were made in literature [4-7] about the - do not send any notification
aggregate effects of through faults on transformers, - do not send any data
potentially able to produce mechanical stresses - do not extract any parameter automatically;
which result in the progressive weakening of the they just store waveform in COMTRADE for-
winding clamping pressure and, thus, movement of mat.
the winding turns. Indeed, these kind of currents
Therefore, the current situation is that the Opera-
(typically > 50% of maximum short circuit current)
tion and Maintenance (O&M) people are, most of
can produce electromagnetic forces, proportional to
the time, unaware of the number and magnitude of
the square of the peak of the fault current, which
the short circuit events affecting the transformers.
can weaken the mechanical structure to a point
The notification of a short circuit event is, nowa-
where the transformer is no longer capable of with-
days, sent from the control center to the O&M only
standing a short-circuit at its terminals. This can
if the primary breaker is opened due to a protection
lead to severe winding displacement. Another pos-
trip. It is then up to the O&M people to go on site
sible consequence of the continuous movement of
and manually extract the data from the disturbance
the winding disks is the occurrence of inter-turn
recorded. A typical scenario is when a lightning
short circuits.
strike causes a short circuit in the HV line, which is
As a result of several investigations made on failed cleared within <100 ms and the breaker is reclosed
transformers, TERNA has recognized that a certain immediately. In such a case the notification of the
number of failures could be linked to the electrody- event is not sent anywhere, but the transformer has
namic forces caused by the repetitive occurrence of actually faced a high current, potentially very high.
through fault currents. Evidence was found in both
large auto-transformers, where deformation was 2.2. Case Study #1 - mechanical stress re-
noted in about 10% of units [8], and in smaller sulting in winding deformation
HV/MV transformers suffering turn-to-turn failures
in the MV winding. A critical inductance variation was measured in a
160 MVA autotransformer, exceeding 5% in one
These cases led TERNA to explore the possibility to phase.
monitor the occurrence of such events in order to
plan SFRA, Inductance and Winding Resistance test According to internal rules within TERNA, a trans-
basing on condition, correlate the data with Dis- former with 5% variation must be taken out of ser-
solved Gas in Oil analysis and plan proper corrective vice. Note that the previous measurement, carried
actions on time. Additionally, in case of positive re- out 4 years before, was perfect. In order to investi-
sults, the TFC parameters could be integrated into gate the possible reasons for such a significant vari-
the Health Index calculation. ation, disturbance recorders were manually interro-
gated by TERNA experts and it was found that the
same phase had experienced, few months before
2. BACKGROUND
the measurement, a through-fault current reaching
86% of the maximum short circuit current, Icc. This
2.1. Limitations of Disturbance Recorders event was recorded by the disturbance recorder but
Disturbance recorders are widely installed in the not notified to TERNA because the fault was cleared
Italian transmission network. Such devices are acti- before the transformer relay could trip. It was spec-
vated by the protection relays and, together with ulated that the transformer had experienced a sig-
various parameters, record the current waveforms nificant amount of through-fault currents over its
when the protections are armed. However, such life that could have weakened the structure in a way
devices: that it was not capable to withstand an event of
such a magnitude.
- are driven by the protection relay, not by the
current itself; reliability on the data capturing
2.3. Case Study #2 – mechanical stress re-
depends on relay reliability and settings
- are generally used to support a post-failure in- sulting in electrical failure
vestigation; not for predictive maintenance or TERNA owns about 133 transformers which inter-
condition monitoring connect the HV network to the MV grid. The protec-
2
Proceedings of My Transfo 2016 – 15th and 16th November 2016
tion at the MV side are managed by the Distribution COMTRADE format and notifications are sent to the
System Operator (DSO). Whenever a short circuit O&M when events are triggered. Three clamp hall-
occurs at the MV side, the DSO clears it before the effect type CTs were installed (Fig 3) in the trans-
transformer HV breaker opens. These faults cause former control room connected to the secondary (5
high currents within the HV/MV transformer, but no A) winding of transformer CTs.
notification is sent to the TSO for two reasons: TABLE I
Short circuit parameters
1) the transformer HV protection relay does
not open PARAMETER DESCRIPTION VALUE
2) sometimes, in old sites, disturbance re-
IN RATED CURRENT 165 A
corders are not even installed on TSO side
VCC% SHORT CIRCUIT IMPEDANCE 13.1 %
Thus, the TSO is unaware of the high currents circu-
lating in the winding, until the transformer trips. A ICC MAXIMUM SHORT CIRCUIT 1260 A
32 MVA transformer has recently experienced a CURRENT (SYMMETRIC)
failure within the MV winding insulation (summer ICCPEAK FIRST PEAK OF THE MAXIMUM 3401 A
2016). Electrical tests were carried out on the failed SHORT CIRCUIT CURRENT
transformers, showing turn-to-turn short circuit in (ASYMMETRIC)
one phase. At least other two similar cases had oc-
TMAX MAXIMUM DURATION TIME 2S
curred in the past 10 years. Also in this case, the DURING WHICH THE
repetitive occurrence of through-fault currents was TRANSFORMER CAN WITHSTAND
speculated to be the main cause of the failure, hav- THE MAXIMUM CURRENT WITH NO
ing caused the inter-turn insulation to degrade due IRREVERSIBLE DAMAGES [8]
to continuous winding movement.
EMAX MAXIMUM SHORT CIRCUIT 3172892
2*
ENERGY A S
3. TRIAL PROJECT
3.1. Description of the system Fig. 2 TFC Monitor installed in the TERNA control room
A trial project has run in 2015-2016 installing a TFC
monitoring device on a 63 MVA transformer, 220/22
kV (category IV, [8]). Basing on the transformer
nameplate it was possible to calculate the short
circuit parameters of Table 1. The monitoring sys-
tem (Fig. 2) is able to detect over-currents simulta-
neously in three phases, store the events exceeding
a configurable trigger and extract parameters such
as duration time, maximum peak, energy of the
2
event (I t), RMS and the aggregated effect of the
2
short circuit currents (cumulative I t) from each Fig. 3 CT clamp sensors at the secondary winding of the current
event. Waveforms are stored and available in transformer
3
Proceedings of My Transfo 2016 – 15th and 16th November 2016
Figure 4 shows the records from the disturbance tection relays and, thus, not recorded by any dis-
recorders (top) compared to the one from the moni- turbance recorders.
toring device (bottom) after a short circuit occurred
at the MV side. The two readings match perfectly,
thus validating the TFC monitor sensitivity and accu-
racy.
4
Proceedings of My Transfo 2016 – 15th and 16th November 2016
5
Proceedings of My Transfo 2016 – 15th and 16th November 2016
6
Proceedings of My Transfo 2016 – 15th and 16th November 2016