10 Lighting DB for Mills, Workshop, Office 1 Box Green T&D No. 12 UnHold
11 Main Lighting DB 2 Boxes Green T&D No. 1 UnHold
12 LAB DB 1 Box Green T&D No. 1 UnHold
Blow Room DB & 1 Box+ 1 Ally Green T&D
13 No. 2 UnHold
Waste Room DB 1 Panel+ 1 Ally Green T&D
14 Packing DB 1 Box+ 1 Ally Green T&D No. 1 UnHold
15 Compressor DB 2 Boxes Green T&D No. 1 UnHold
16 Labour Colony Main DB 1 Panel+ 1 Ally Green T&D No. 1 UnHold
17 Labour Color Sub DB 1 Box Green T&D No. 10 UnHold
18 Masjid DB 1 Box Green T&D No. 1 UnHold
19 Junior Staff Hostel DB G1-G6,F1-F6,S1-S6 1 Box Green T&D No. 7 UnHold
20 Senior and Guest House Main DB 1 Panel+ 1 Ally Green T&D No. 1 UnHold
21 Senior Staff DB 1 Box Green T&D No. 1 UnHold
22 Senior Staff DB 2 1 Box Green T&D No. 1 UnHold
BTD 6300A for LT-01 & LT-02 for neutral as
23 Green T&D Job. 1 UnHold
per Drawing Std 2.5M with fitting
24 Flexible Link for BTD for LT-01 & LT-02 Green T&D No. 2 UnHold
Special Instructions:
Copper LOCAL - IMPORTED √
Sleeves TINNED √ Color SLEEVES -
Paint RAL-7035 √ RAL-7032 -
Packing Normal √ Wooden -
Sales Mngr/Engr
Mr. Hamad Gul
ATTACHMENT
PO Attached
GA Drawings Attached
Prepared By:
Syed Ahmed Hassan
SPECIAL-NOTE
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF OF
POWER HOUSE PANEL (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED,
DUPLICATED,REPRODUCED TO THE THIRD PARTY IN
ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION
OF GREEN T&D (PVT) LTD.
SPECIAL INSTRUCTIONS
-
-
FOR APPROVAL
FOR MANUFACTURING
AS BUILT
DESCRIPTION
-
NG
11KV,630A 25KA VCB PANEL
R I CLIENT
NASEEM TEXTILE MILLS
TU PROJECT
AC
NASEEM TEXTILE MILLS
UF
CONSULTANT
N/A
A N PROJECT-NO
M GTD-570341221-REV04
O R DRAWING-NO
F MO-NUMBER
SGA-570341221
MO-412311222
REVISION
- - -
- - - -
- - -
DRAWING INDEX
Ser.
No DRAWING NO Description SHEET NO REV REMARKS
G R B W Y R G G R B W Y R G R B W Y R G
E.M OFF ON
E.M OFF ON E.M OFF ON
PB PB PB
PB PB PB PB PB PB
INTERLOCKED
INTERLOCKED
MECHANICAL
MECHANICAL
EARTH EARTH
SWITCH SWITCH
-F26 -F26
T/F STATUS T/F STATUS
-1T1~1T3 RELAY -1T1~1T3 RELAY -1T1~1T3
200/ 5A -F50/51N 200/ 5A -F50/51N 400/ 5A -F50/51N
O/C & E/F O/C & E/F O/C & E/F
PROTECTION CT PROTECTION CT PROTECTION CT
RELAY RELAY RELAY
CL-5P20, 15VA CL-5P20, 15VA CL-5P20, 15VA
SURGE
ARRESTOR
PANEL
185
-H1 -H2 -H3 -H4 -H5 -H6 -H7 -H8 -H9 -H10 -H1 -H2 -H3 -H4 -H5 -H6 -H7 -H8 -H9 -H10 -H1 -H2 -H3 -H4 -H5 -H6 -H7 -H8 -H9
PANEL LIMIT PANEL LIMIT PANEL LIMIT
RED YELLOW BLUE ON OFF TRIP
RED YELLOW BLUE ON OFF TRIP VCB TEST VCB SERVICE HEATER ON E.S ON RED YELLOW BLUE ON OFF TRIP VCB TEST VCB SERVICE HEATER ON E.S ON VCB TEST VCB SERVICE HEATER ON
LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH
565
615
E/A E/A E/A
365
AMP-METER VOLT-METER ENERGY ANALYZER AMP-METER VOLT-METER ENERGY ANALYZER AMP-METER VOLT-METER ENERGY ANALYZER
-F26 -S69 -S70 -S3 -F26 -S69 -S70 -S3 -S69 -S70 -S3
TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK
AMP-SELECTOR VOLT-SELECTOR M/O/A SELECTOR AMP-SELECTOR VOLT-SELECTOR M/O/A SELECTOR AMP-SELECTOR VOLT-SELECTOR M/O/A SELECTOR
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH
SIDE DISH
293
COVER
OUTGOING OUTGOING INCOMING
SIDE DISH
SIDE DISH
PANEL PANEL PANEL
COVER
COVER
SIDE DISH
295
295
GREEN T&D (PVT.) LTD. GREEN T&D (PVT.) LTD. GREEN T&D (PVT.) LTD.
300
2200
2200
110
110
110
GLASS WINDOW GLASS WINDOW GLASS WINDOW
850
! ! !
300
340
340
HVX HVX HVX
128
128
128
68
68
68
140
295
675
262
540
PT 1 PT 2 PT 3
200
60
60
60
235
175
175
175
210 210 210
1040
60
60
60
HANDLE HANDLE HANDLE
235
175
175
175
210 210 210
60
60
60
SIDE DISH
SIDE DISH
COVER
COVER
SIDE DISH
DISH
COVER
COVER
MONO MONO MONO
2200 SIDE
2200
210 210 210 210 210 210
REAR DOOR REAR DOOR REAR DOOR
C.T,S
C.T,S
C.T,S
240
1040
180
180
180
GLASS WINDOW GLASS WINDOW GLASS WINDOW
680
OUTGOING CABLE OUTGOING CABLE INCOMING CABLE
300 300 300
1600
LIFTING LIFTING LIFTING
BOLT BOLT BOLT
WALL WALL
1000 1600 1800
Explosion vent
FROM REAR WALL BUSHING PLATE FROM FRONT
METERING
BUS BAR
235
COMPARTMENT
COMPARTMENT
235
FRONT
60
VCB COMPARTMENT
VCB 630A
VCB TEST & SERVICE
240 POSITION
C.T,s
INCOMING
VCB TROLLEY
575
CABLE
ARRESTER
SURGE
P.T,S
WALL WALL
1000 1600 1800
Explosion vent
FROM REAR WALL BUSHING PLATE FROM FRONT
METERING
BUS BAR
235
COMPARTMENT
COMPARTMENT
235
FRONT
60
VCB COMPARTMENT
2200
VCB 630A
VCB TEST & SERVICE
240 POSITION
C.T,s EARTH
SWITCH
OUTGOING
VCB TROLLEY
575
CABLE
SIDE VIEW
OUTGOING PANEL
SPECIAL INSTRUCTIONS
-
-
FOR APPROVAL
FOR MANUFACTURING
AS BUILT
DESCRIPTION
CLIENT
NASEEM TEXTILE MILLS
IN G PROJECT
UR
N/A
T
CONSULTANT
C N/A
UFA PROJECT-NO
GTD-570341221-REV04
AN DRAWING-NO
R M M.O-NUMBER
SGA-570341221
F O MO-412311222
REVISION
- - -
1800 X 1200
1000
1200
DN.
PFI PANEL
300KVAR
700
CUBICAL 1
230
300KVAR
700
CUBICAL 2
2800
REAR SIDE
PFI PANEL
FRONT SIDE
PFI PANEL
MAIN L. T. ROOM
700
5880
3700
CUBICAL 3
PFI PANEL
300KVAR
6000
900
PFI PANEL
300KVAR
700
650 12500 CUBICAL 4
PFI PANEL FRONT SIDE LT PANEL FRONT SIDE LT PANEL FRONT SIDE LT PANEL FRONT SIDE
CUBICAL 10 CUBICAL 9 100
CUBICAL 14 CUBICAL 13 CUBICAL 11
700 700 CUBICAL 8 CUBICAL 7
CUBICAL 21 CUBICAL 20 CUBICAL 19 CUBICAL 18 CUBICAL 17 CUBICAL 16 CUBICAL 15 CUBICAL 12
DUMMY PANEL
CUBICAL 5
PFI INCOMING
FLANGE 2500A FLANGE 2500A
400
700 700 OTHER MCCB OUT 700 700 1000 1000 400 OTHER MCCB OUT 700 700 1000 1200
FROM BOTTOM FROM BOTTOM
400
1180
700 700 700 700
780
780
780
ALD1 DOOR 700
PFI PANEL REAR SIDE
13800
1500 X 2700
5000
5000
710
BTD 5000A
BTD 5000A
FUTURE SPACE
OUTGIONG PANEL
BOTTOM
800
VIEW
PANEL
OUTGIONG PANEL
6000
BOTTOM
OUTGIONG PANEL
800
VIEW
1
OUTGIONG PANEL
BOTTOM
OUTGIONG PANEL
800
5710
VIEW
1300 900
CABLING PLATE
INCOMING CABLING PLATE
INCOMING
BOTTOM
800
VIEW
900
EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 6"
WITH COVER WITH COVER WITH COVER WITH COVER WITH COVER
PFI INCOMING
PFI PANEL PFI PANEL PFI PANEL PFI PANEL
40M PANEL
ON OFF TRIP
CONTINUE SWITCHBOARD
TO NEXT SHEET 04 OF 30
ON ON ON ON ON ON ON ON ON ON ON ON
ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB
2200
2200
LOUVERS LOUVERS LOUVERS LOUVERS
WITH FAN 8" WITH FAN 8" WITH FAN 8" WITH FAN 8"
600
BOTTOM VIEW
TRANSFORMER INCOMING SOLAR INCOMING BUS COUPLER TRANSFORMER INCOMING SOLAR INCOMING
OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL BUS BAR CHAMBER
14M PANEL 01
14M PANEL 01
14M 40M 14M 14M PANEL
14M PANEL 01
14M PANEL 01
ON P/B OFF P/B ON P/B OFF P/B ON P/B OFF P/B ON P/B OFF P/B ON P/B OFF P/B
EARTHING
E/Stop A/O/M E/Stop A/O/M
CONTINUE SWITCHBOARD
TO NEXT SHEET 05 OF 30
CONTINUE SWITCHBOARD
DOOR
EARTHING
14M INCOMING 14M INCOMING 14M OUTGOING 14M OUTGOING 14M BUS COUPLER 14M INCOMING 14M INCOMING
ACB 5000A TP ACB 3200A TP ACB 3200A TP ACB 2500A TP ACB 5000A TP ACB 5000A TP ACB 3200A TP
DOOR POCKET
DOOR POCKET
DOOR
EARTHING
LOUVER DOOR
EARTHING
LOUVER DOOR
EARTHING
LOUVER DOOR
EARTHING
DOOR
EARTHING
LOUVER DOOR DOOR
EARTHING
LOUVER DOOR
EARTHING
LOUVER DOOR
EARTHING
LOUVER
EARTHING
LOUVERS
400
FROM BOTTOM
800
BUS WAY
TOP SIDE
BOTTOM VIEW
PFI INCOMING
OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL PFI PANEL PFI PANEL PFI PANEL PFI PANEL
14M 40M 14M 14M PANEL
PFI
R 8888
E
L
A P/F
Y
PFI RELAY
TO PREVIOUS SHEET 04 OF 30
CONTINUE SWITCHBOARD
ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB
OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB
DOOR POCKET
DOOR
EARTHING
LOUVER DOOR
EARTHING
DOOR
EARTHING
LOUVER DOOR
EARTHING
LOUVER DOOR
EARTHING
DOOR
EARTHING
DOOR
EARTHING
DOOR
EARTHING
LOUVERS
600
1600A MCCB OUT
800
BUS WAY
600
TOP SIDE
BOTTOM VIEW
EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 6"
WITH COVER WITH COVER WITH COVER WITH COVER WITH COVER
CONTINUE SWITCHBOARD
TO NEXT SHEET 07 OF 30
50 KVR 50 KVR 50 KVR 150 KVR 100 KVR 50 KVR 50 KVR 50 KVR
2200
H.R.C FUSE H.R.C FUSE H.R.C FUSE H.R.C FUSE
12K3 12K2 12K1 10K3 10K2 10K1 8K2 8K1 7K2 5K2 5K1 4K1
PFI INCOMING
150 KVR 150 KVR 100 KVR 100 KVR 100 KVR 50 KVR ACB 2000TP
Auxiliary Auxiliary
TERMINAL TERMINAL
F1~F5 TH TH Contactor F1 TH BLOCK
F1TH BLOCK
F1~F5 TH TH Contactor
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
RED YELLOW BLUE
PHASE PHASE PHASE
PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT
LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH
CONTINUE SWITCHBOARD
TO NEXT SHEET 08 OF 30
CONTINUE SWITCHBOARD
ACRYLIC
Schneider
Electric
Schneider
Electric
SHEET
2200
2200
O/G 1600A
O/G 400A
SPACE ONLY OUTGOING OUTGOING SPACE ONLY
INCOMING ACB 5000A TP ACB 5000A TP INCOMING ACB 5000A TP
INCOMING ACB 3200A TP ACB 3200TP ACB 2500TP INCOMING ACB 3200A TP
F1~F3
Schneider
Electric
NSX 400-630A
400
OTHER MCCB OUT
FROM BOTTOM
OUTGOING
CONNECTION 1600A MCCB OUT
800
BUS WAY
THROUGH BUS WAY TOP SIDE
FROM TOP
3200A
TOP VIEW
REVISION GA OF LT & PFI PANEL
FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LT-01&02 (OPTION 01;WITH CIRCUTOR PFI)
PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT
LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH
F1~F3 Auxiliary
TERMINAL TERMINAL TERMINAL
F1~F5 TH TH Contactor F1TH BLOCK
F1TH BLOCK
F1 TH BLOCK
Schneider
Electric
NSX 400-630A
Schneider
Electric
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
30 KVR CAPACITOR
CUBICAL 14 CUBICAL 15 CUBICAL 16 CUBICAL 17 CUBICAL 18 CUBICAL 19 CUBICAL 20 CUBICAL 21
700 700 700 700 700 700 700 700
5600
PFI INCOMING
OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL PANEL PFI PANEL PFI PANEL PFI PANEL PFI PANEL
600
OUTGOING
CONNECTION
THROUGH BUS WAY 1600A MCCB OUT
BUS WAY
600
FROM TOP TOP SIDE
3200A
TOP VIEW
TIE DUCT
HANDLE
DOOR
WITH LOUVERS 10"
VENTILATION
VENTILATION
VENTILATION
EXHAUST FAN 8"
LOUVER
FRONT DOOR
FRONT DOOR
FRONT DOOR
FRONT DOOR
BACK DOOR
BTD
BACK DOOR
BACK DOOR
CONNECTION
FROM TOP
DETUNED
LOUVER
REACTOR 50KVAR
O/G
2200
2200
2200
ACB 5000A CABLES
TP
30 KVR CAPACITOR
30 KVR CAPACITOR
DETUNED
LOUVERS
LOUVER
LOUVERS
LOUVERS
REACTOR 50KVAR
LOUVERS
C.T
30 KVR CAPACITOR
30 KVR CAPACITOR
VENTILATION
VENTILATION
VENTILATION
VENTILATION
Earth
800
800 800 600
1200
LEFT SIDE VIEW LEFT SIDE VIEW PFI PANEL SIDE VIEW
INCOMING PANELS OUTGOING PANELS SIDE VIEW WITH DISH COVER
7. PROTECTION CLASS IP42 (INDOOR TYPE FLOOR STANDING) FORM 1. DROPPER BUS BARS
PANEL NO 09 & 15 1(30x5)
8. ENCLOSURE SHALL BE : BOLTED TYPE. PFI PANEL BUS BAR
MAIN BUSBAR 2500A 3(100x5)
9. LIVE PARTS COVERED WITH THE PROTECTION SHEET. EARTH BUS BAR 1(100x5)
ACB 2500A TP 3(100x5)
200
400
200
400
200
400
300
500
600
300
500
600
300
500
600
100
100
100
100
150
0
0
900
900 900 900
LABEL
800
800 LIVE PHASE
800 800
R Y B
700
700 700 700
CAPS LOCK Neutral CU. (30x3)
600
600 600 600
EZC 100F EZC 100F
Earth CU. (15x3)
Schneider
Electric
500
500 500 500
I/C MCCB
50A
400
400 400 400 F1~F3
300
300 300 300 O/G MCB SP O/G MCB
CAPS LOCK 20A 10A SP
32A 3PIN
SOCKET DOOR 200
200 EARTHING 200 200 O/G MCB SP 20A
100
100 100 100
0
0 0 0
400
300
500
600
100
NOTE:
0
DOOR
Neutral
LOCK
CABLE
Neutral
LIVE PHASE
O/G 50A x 5
R Y B
EARTH (20x5)
CU. (20x5)
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
KING
LOC
.IN TER
H
MEC
8888 8888 I/C MCCB I/C MCCB
400A 400A
P/M P/M
O/G MCCB O/G 50A x 5
125A
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
F1~F3 F1~F3
1300
1300
1300
EZC 250F
(60X80)
NSX 400-630A NSX 400-630A
Schneider Schneider
Electric Electric O/G 50A x 4
DOOR
LOCK
Schneider Schneider Schneider Schneider
Electric Electric Electric Electric
C.T C.T
DOOR POCKET
DOOR DOOR
CAPS LOCK EARTHING CAPS LOCK EARTHING
NOTE:
1. ALL DIMENSIONS ARE IN MM.
2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET.
1400 3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT.
700 700 4. QTY: 01 NOS
5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM TOP. COPPER SIZES
CABLING CABLING 6. PANELS SHALL BE FRONT & REAR ACCESS.
250
200
400
200
400
200
400
300
500
600
700
300
500
600
700
300
500
600
700
100
100
100
100
175
0
0
800
800 800 800
LABEL
700
700 LIVE PHASE
B 700 700 I/C MCCB 125A
R Y
600
600 600 600 Earth CU. (15x3)
8888 8888 F1~F3
A/M V/M EZC 250F
500
500 500 500
400
400 400 EZC 100F EZC 100F EZC 100F 400 EZC 100F EZC 100F EZC 100F
A.S.S V.S.S
Schneider Schneider Schneider
Electric Electric Electric
CAPS LOCK
300
300 300 300 O/G MCCB 50A X 3
DOOR 200
200 EARTHING 200 200
100
100 100 100 O/G MCB 20&10A
0
0 0 0
NOTE:
700
200
400
600
300
500
100
2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
175 3.
100
CABLING AREA 3. PAINT OF ENCLOSURE SHOULD BE 7035.
0
4.
6.
INCOMING FROM TOP & OUTGOING CABLES SHALL BE FROM TOP & BOTTOM.
DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
QTY: 01 NOS
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B. PHASE DISTRIBUTION BOARD
TOP & BOTTOM VIEW 8. ENCLOSURE SHALL BE : WELDED TYPE.
RED YELLOW BLUE
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET.
20Ax3 (SP) 20Ax3 (SP) 20Ax3 (SP)
10. COPPER TINED.
10Ax1 (SP) 10Ax1 (SP) 10Ax1 (SP)
LABEL LABEL
DOOR
LOCK
LIVE PHASE
R Y B
CAPS LOCK
8888 8888
A/M V/M
C.T C.T
C.T
A.S.S V.S.S
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
1300
1300
1300
(60X80)
EZC 250F
NSX 400-630A
O/G MCB
F1~F3 Schneider
Electric 20A
DOOR
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
LOCK
Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider
Electric Electric Electric Electric Electric Electric Electric Electric
O/G MCCB
125A O/G 50A x 8
I/C MCCB
EARTH (20x5)
400A
O/G MCB
DOOR POCKET 20A
CU. (20x5)
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
DOOR DOOR Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider
Neutral
Electric Electric Electric Electric Electric Electric Electric Electric
NOTE:
1. ALL DIMENSIONS ARE IN MM.
1400
2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET.
450 950
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT. QTY: 01 NOS
4.
COPPER SIZES
5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM BOTTOM.
CABLING MAIN BUS BAR 400A 1(30x5)
CABLING
250
VENTILATION
LIGHT
NEUTRAL
LIVE PHASE
R Y B
A.S.S V.S.S
FRONT DOOR
I/C MCCB 400A O/G 60A x 3 O/G 30A x 3
1800
1800
1800
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
M.S DOOR
POCKET
F1~F3
Schneider
Electric EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
C.T C.T
VENTILATION
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
EARTHING EARTHING
LOUVER
NOTE:
1. ALL DIMENSIONS ARE IN MM.
CABLING
CABLING
CABLING
AREA
AREA
AREA
2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
400
9. LIVE PARTS COVERED WITH THE PROTECTION SHEET. MCCB 400A 3P 1(30x5)
MCCB 125A 3P 1(20x5)
LABEL LABEL
DOOR
LOCK
LIVE PHASE
R Y B
CAPS LOCK
8888 8888
A/M V/M
C.T C.T
C.T
A.S.S V.S.S
EZC 100F EZC 100F EZC 100F EZC 100F
1300
1300
1300
F1~F3
(60X80)
EZC 250F
NSX 400-630A
Schneider
Electric
DOOR
EZC 100F EZC 100F EZC 100F EZC 100F
LOCK
Schneider Schneider Schneider Schneider
Electric Electric Electric Electric
O/G MCCB
320A O/G 30A x 4
I/C MCCB
EARTH (20x5)
400A
DOOR POCKET
CU. (20x5)
EZC 100F EZC 100F
Neutral
Electric Electric
NOTE:
1100 1. ALL DIMENSIONS ARE IN MM.
500 600 2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET. QTY: 01 NOS
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT. COPPER SIZES
4. MAIN BUS BAR 400A 1(30x5)
CABLING CABLING
250
AREA
5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM BOTTOM. 1(20x5)
AREA NEUTRAL BUS BAR
6. PANELS SHALL BE FRONT & REAR ACCESS.
EARTH BUS BAR 1(20x5)
7. PROTECTION CLASS IP42 (INDOOR TYPE SEMI CANCELLED).FORM 1
INTERCONNECTION
8. ENCLOSURE SHALL BE : WELLDED TYPE.
BOTTOM VIEW 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET.
MCCB 400A 3P 1(30x5)
MCCB 125A 3P 1(20x5)
LABEL LABEL
DOOR
LOCK
EARTH (20x5)
LIVE PHASE
R Y B
O/G 30A x 4
CU. (20x5)
CAPS LOCK
Neutral
8888
P/M I/C MCCB
600A
8888 8888
A/M V/M
1300
1300
1300
A.S.S V.S.S
F1~F3
(60X80)
O/G MCCB
200A X 4
NSX 400-630A
Schneider
Electric
DOOR
LOCK
C.T C.T
C.T
DOOR POCKET
DOOR DOOR
CAPS LOCK EARTHING CAPS LOCK EARTHING
NOTE:
1200 1. ALL DIMENSIONS ARE IN MM.
600 600 2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET.
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT.
QTY: 01 NOS
4. COPPER SIZES
CABLING CABLING
250
AREA
5. INCOMING FROM TOP & OUTGOING CABLES SHALL BE FROM BOTTOM. 2(30x5)
AREA MAIN BUS BAR 630A
6. PANELS SHALL BE FRONT & REAR ACCESS. NEUTRAL BUS BAR 1(30x5)
7. PROTECTION CLASS IP42 (INDOOR TYPE SEMI CANCELLED).FORM 1 EARTH BUS BAR 1(25x5)
INTERCONNECTION
8. ENCLOSURE SHALL BE : WELLDED TYPE.
BOTTOM VIEW 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET.
MCCB 630A 3P 2(30x5)
MCCB 200A 3P 1(20x5)
R Y B R Y B
8888 8888
P/M P/M O/G MCCB O/G MCCB
60A 60A
C.T C.T
EZC 100F
Schneider Schneider
Electric Electric
C.T
C.T
O/G MCCB O/G MCCB O/G MCCB O/G MCCB
GLASS 125A 125A 125A 125A
1500
1500
Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider
Electric Electric Electric Electric Electric Electric Electric Electric Electric Electric
1600
1600
Schneider O/G MCCB X 2 O/G MCCB 100A X 3 Schneider O/G MCCB X 2 O/G MCCB 100A X 3
Electric Electric
I/C 600A EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
I/C 600A EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider
Electric Electric Electric Electric Electric Electric Electric Electric Electric Electric
N N N N
PE PE PE PE
DOOR DOOR
EARTHING EARTHING
100
100
100
400 600 400 600 400 600 400
CUBICAL -01 CUBICAL -02 CUBICAL -01 CUBICAL -02 CUBICAL -01 CUBICAL -02
1000 1000 1000
SIDE VIEW
EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW
WITH METERING DOOR WITHOUT METERING DOOR
NOTE:
1000
400 600 1. ALL DIMENSIONS ARE IN MM.
2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET.
QTY: 01 NOS
COPPER SIZES
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT.
MAIN BUS BAR 630A 2(30x5)
4. NEUTRAL BUS BAR 1(30x5)
400
5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM BOTTOM. EARTH BUS BAR 1(25x5)
6. PANELS SHALL BE FRONT & REAR ACCESS. INTERCONNECTION
MCCB 630A 3P 2(30x5)
7. PROTECTION CLASS IP65 (INDOOR TYPE FLOOR STANDING).FORM 1
MCCB 200A 3P 1(20x5)
8. ENCLOSURE SHALL BE : WELLDED TYPE. DROPPERS BUS BAR
BOTTOM VIEW 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET. CUBICAL 02 1(30x5)
200
400
200
400
200
400
300
500
600
300
500
600
300
500
600
100
100
100
100
150
0
0
900
900 900 900
LABEL
800
800 LIVE PHASE 800 800
R Y B
CAPS LOCK
700
700 700 700
8888 8888
600
600 A/M V/M 600 600 O/G MCB SP 10A
500
500 500 500
A.S.S V.S.S
400
400 400 400
DOOR 200
200 EARTHING 200 EZC 100F
200 EZC 100F
Schneider
Electric
Earth CU. (15x3)
0
0 0 0
NOTE:
200
400
300
500
600
100
0
200
400
200
400
200
400
300
500
600
700
300
500
600
700
300
500
600
700
100
100
100
100
175
0
0
800
800 800 800
LABEL
LIVE PHASE
700
700 R Y B 700 700
600
600 600 600 C.T O/G MCB 16A X 10
8888 8888 C.T C.T
400
400 400 400
A.S.S V.S.S
O/G MCB 100A X 5
CAPS LOCK F1~F3
EZC 250F EZC 250F
300
300 300 300
DOOR 200
200 EARTHING 200 200 Neutral CU. (30x3)
0
0 0 0
400
600
300
500
100
NOTE:
0
0
3.
4.
PAINT OF ENCLOSURE SHOULD BE 7035.
INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
QTY: 02 NOS
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS. PHASE DISTRIBUTION BOARD
TOP & BOTTOM VIEW 7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
8. ENCLOSURE SHALL BE : WELDED TYPE. RED YELLOW BLUE
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. 20Ax3 (SP) 20Ax3 (SP) 20Ax3 (SP)
10. COPPER TINED. 10Ax1 (SP) 10Ax1 (SP) 10Ax1 (SP)
R Y B R Y B
8888 8888
P/M P/M
C.T
C.T
O/G MCCB O/G MCCB O/G MCCB O/G MCCB
GLASS 150A 150A 150A 150A
1500
1500
Schneider Schneider Schneider Schneider Schneider Schneider
Electric Electric Electric Electric Electric Electric
1600
1600
Schneider O/G MCCB 100A X 3 Schneider O/G MCCB 100A X 3
Electric Electric
N N N N
PE PE PE PE
DOOR DOOR
EARTHING EARTHING
100
100
100
400 600 400 600 400 600 400
CUBICAL -01 CUBICAL -02 CUBICAL -01 CUBICAL -02 CUBICAL -01 CUBICAL -02
1000 1000 1000
SIDE VIEW
EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW
WITH METERING DOOR WITHOUT METERING DOOR
NOTE:
1000
1. ALL DIMENSIONS ARE IN MM.
400 600
2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET.
QTY: 01 NOS
COPPER SIZES
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT. 1(30x5)
MAIN BUS BAR 400A
4. NEUTRAL BUS BAR 1(20x5)
400
5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM BOTTOM. EARTH BUS BAR 1(20x5)
6. PANELS SHALL BE FRONT & REAR ACCESS. INTERCONNECTION
MCCB 400A 3P 1(30x5)
7. PROTECTION CLASS IP65 (INDOOR TYPE FLOOR STANDING).FORM 1 MCCB 150A 3P 1(20x5)
8. ENCLOSURE SHALL BE : WELLDED TYPE. DROPPERS BUS BAR
BOTTOM VIEW 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET. CUBICAL 02 1(30x5)
200
400
200
400
200
400
300
500
600
300
500
600
300
500
600
100
100
100
100
150
0
0
900
900 900 900
LABEL
800
800 LIVE PHASE 800 800
R Y B
CAPS LOCK
700
700 700 700
8888 8888
600
600 A/M V/M 600 600
O/G MCB 63A
C.T 500
500 500 500
A.S.S V.S.S
C.T C.T
400
400 400 400
F1~F3 300
300 300 EZC 250F
300 EZC 250F
CAPS LOCK
Earth
Neutral
DOOR 200
200 EARTHING 200 200
CU. (15x3)
CU. (15x3)
100
100 100 100
I/C MCCB 200A
0
0 0 0
NOTE:
200
400
300
500
600
100
0
200
400
200
400
200
400
300
500
600
300
500
600
300
500
600
100
100
100
100
150
0
0
900
900 900 900
LABEL
800
800 LIVE PHASE 800 800
R Y B
CAPS LOCK
700
700 700 700
8888 8888
600
600 A/M V/M 600 600
O/G MCB 63A
C.T 500
500 500 500
A.S.S V.S.S
C.T C.T
400
400 400 400
F1~F3 300
300 300 EZC 250F
300 EZC 250F
CAPS LOCK
Earth
Neutral
DOOR 200
200 EARTHING 200 200
CU. (15x3)
CU. (15x3)
100
100 100 100
I/C MCCB 150A
0
0 0 0
400
300
500
600
100
0
NOTE:
150 1. ALL DIMENSIONS ARE IN MM.
100
CABLING AREA 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
3.
3. PAINT OF ENCLOSURE SHOULD BE 7035.
QTY: 01 NOS
0
200
400
200
400
200
400
300
500
600
300
500
600
300
500
600
100
100
100
100
150
0
0
900
900 900 900
LABEL
800
800 LIVE PHASE 800 800
R Y B
CAPS LOCK
700
700 700 700
8888 8888
600
600 A/M V/M 600 600 O/G MCB SP 40A X 13
500
500 500 500
A.S.S V.S.S
400
400 400 400
C.T C.T C.T
300
300 300 300
CAPS LOCK F1~F3
DOOR
EZC 100F EZC 100F
200
200 EARTHING 200 200 Schneider
Electric
0
0 0 0
NOTE:
200
400
300
500
600
100
0
200
400
200
400
200
400
300
500
600
700
800
300
500
600
700
800
300
500
600
700
800
100
100
100
100
175
0
0
1000 1000 1000
1000
Earth CU. (15x3)
LABEL
LIVE PHASE NEUTRAL FOR UPS CU. (15x3)
900 R Y B 900 900
900
Neutral CU. (30x3)
500
F1~F3
400 400 400
G
EZC 250F EZC 250F
UV/OV Relay
400
300 300
200
CAPS LOCK
DOOR
EARTHING 200
UR 200
SPD FP
200
T
I/C MCCB 200A
AC
100 100 100
100
0 0
U F
INTERNAL VIEW
0
INTERNAL VIEW
0
WITH N
EXTERNAL VIEW SIDE VIEW
D Y
NOTE:
A
400
700
800
200
300
500
600
100
E
0
0
CABLING AREA
A 3.
3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
TOP & BOTTOM VIEW
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
QTY: 01 NOS
8. ENCLOSURE SHALL BE : WELDED TYPE.
PHASE DISTRIBUTION BOARD
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. RED YELLOW BLUE
10. COPPER TINED. 16Ax3 (SP) 16Ax3 (SP) 16Ax4 (SP)
16Ax2 (SP) 16Ax2 (SP) 16Ax1 (SP)
200
400
200
400
200
400
300
500
600
700
800
300
500
600
700
800
300
500
600
700
800
100
100
100
100
175
0
0
1000 1000 1000
1000
LABEL Earth CU. (15x3)
LIVE PHASE
900 R Y B 900 900 NEUTRAL FOR UPS CU. (15x3)
900
Neutral CU. (30x3)
F1~F3
G
400 400 EZC 250F 400 EZC 250F
400
UV/OV Relay
N
O/G & UPS MCB 16A X 14
300
CAPS LOCK
300
SPD FP
300
U
DOOR
200 EARTHING 200 200
200
100 100
C T 100
I/C MCCB 200A
100
0 0
F A 0
0
EXTERNAL VIEW
WITH N
U
INTERNAL VIEW INTERNAL VIEW
SIDE VIEW
DNOTE: Y
A 1. ALL DIMENSIONS ARE IN MM.
400
700
800
200
300
500
600
100
E
0
175
L R 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
100
CABLING AREA A 3.
0
3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
TOP & BOTTOM VIEW
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
QTY: 01 NOS
8. ENCLOSURE SHALL BE : WELDED TYPE. PHASE DISTRIBUTION BOARD
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. RED YELLOW BLUE
10. COPPER TINED. 16Ax3 (SP) 16Ax3 (SP) 16Ax3 (SP)
16Ax2 (SP) 16Ax2 (SP) 16Ax1 (SP)
200
400
200
400
200
400
300
500
600
700
800
300
500
600
700
800
300
500
600
700
800
100
100
100
100
175
0
0
1000 1000 1000
1000
LABEL
LIVE PHASE
900 R Y B 900 900
900
R1 MCB TP
O/G MCB 16A X 10
400
F1~F3
300 300 300
O/G UPS MCB 16A X 5 300
CAPS LOCK
DOOR
200 EARTHING 200 200 O/G MCB DP 20A & 32A X 7
0 0 0
0
NOTE:
400
700
800
200
300
500
600
100
0
200
400
200
400
200
400
300
500
600
300
500
600
300
500
600
100
100
100
0
100
150
0
700 700 700 700
LABEL
Schneider
Earth CU. (15x3)
Electric
F1~F3
Neutral CU. (15x3)
100 100 100 I/C
100
MCCB 60A
0 0 0 0
400
300
500
600
100
0
NOTE:
150 1. ALL DIMENSIONS ARE IN MM.
100
CABLING AREA 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
3.
0
3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
TOP & BOTTOM VIEW 6.
7.
DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
QTY: 06 NOS
COPPER SIZES
8. ENCLOSURE SHALL BE : WELDED TYPE.
MAIN BUS BAR 63A 1(15x3)
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET.
NEUTRAL BUS BAR 1(15x3)
10. COPPER TINED.
EARTH BUS BAR 1(15x3)
200
400
200
400
200
400
300
500
600
300
500
600
300
500
600
100
100
100
0
100
150
0
700 700 700 700
LABEL
Schneider
Earth CU. (15x3)
Electric
0 0 0 0
400
300
500
600
100
0
NOTE:
150 1. ALL DIMENSIONS ARE IN MM.
100
CABLING AREA 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
3.
0
3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
TOP & BOTTOM VIEW 6.
7.
DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
QTY: 06 NOS
COPPER SIZES
8. ENCLOSURE SHALL BE : WELDED TYPE.
MAIN BUS BAR 63A 1(15x3)
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET.
NEUTRAL BUS BAR 1(15x3)
10. COPPER TINED.
EARTH BUS BAR 1(15x3)
400
450
400
450
400
450
200
300
200
300
200
300
100
100
100
0
100
150
0
400 400 400 400
BLOCK A BOXES
Neutral Earth
LIVE PHASE
DOOR LOCK
300 R Y B 300 300 300
F1~F3
200 200 200 200
EZC 100F EZC 100F
CAPS LOCK
Schneider
Electric
0 0 0 0
300
100
0
NOTE:
1. ALL DIMENSIONS ARE IN MM.
150 2. ENCLOSURE SHALL BE WITH 16SWG MS. SHEET. (STANDARD TOLERANCE LIMITS APPLIED).
100 3. PAINT OF ENCLOSURE SHOULD BE 7035 WHITE TEXTURE PAINT.
CABLING AREA 4.
5. INCOMING BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
QTY: 12 NOS
0
PHASE DISTRIBUTION BOARD
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
TOP & BOTTOM VIEW 7. PROTECTION CLASS IP44 (INDOOR CONCEALED TYPE) RED YELLOW BLUE
8. ENCLOSURE SHALL BE : WELDED TYPE. 20Ax3 (SP) 20Ax3 (SP) 20Ax3 (SP)
400
400
400
200
300
500
600
700
200
300
500
600
700
200
300
500
600
700
100
100
100
0
100
175
0
900 900 900 900
LABEL
LIVE PHASE Earth
800 R Y B 800 800 CU. (15x3)
800
C.T
500 500 500 500
A.S.S V.S.S
C.T C.T
DOOR Schneider
Electric
0 0 0 0
300
500
600
700
100
0
NOTE:
175
1. ALL DIMENSIONS ARE IN MM.
2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
100
CABLING AREA 3.
0 3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP & BOTTOM.
TOP & BOTTOM VIEW 6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
QTY: 01NOS
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B. PHASE DISTRIBUTION BOARD
8. ENCLOSURE SHALL BE : WELDED TYPE.
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. RED YELLOW BLUE
10. COPPER TINED. 20Ax3 (SP) 20Ax3 (SP) 20Ax3 (SP)
10Ax1 (SP) 10Ax1 (SP) 10Ax1 (SP)