Manufacturing Order

M.O No. MO-412311222 M.O Date : 01-Jun-22


Customer Name: Naseem Exports Pvt. Ltd. Project ID : GTD-570341221-REV05
Project Name: Delivery Terms: Ex- Factory
P.O No. NEL-001 P.O Dated : 18-Feb-22
Delivery Date: 05-Jun-22 Delivery Urgency: Urgent
Insurance: Not Applicable Testing & Commissioning : Not Included
Commissioning Cost: Not Included Installations : Not Included

Sr. Particulars Consist of Make Unit Qty Remarks


1 GM House DB 1 Box Green T&D No. 1
2 Guest House DB 1 Box Green T&D No. 1
3 Grid End Panel 1 Panel Green T&D No. 1 From PEL
4 Wapda Metering Panel 1 Panel Green T&D No. 1 From PEL
5 Wapda Protection Panel 1 Panel Green T&D No. 1 UnHold
6 Incoming Panel HT Client End 1 Panel Green T&D No. 1 UnHold
7 Transformer Proctection Panel 1 Panel Green T&D No. 2 UnHold
Transformer LT Panel & Solar Provision, Sync
8 + Bus Coupler with PFI, Outgoing Panels, As 10 Panels Green T&D No. 1 UnHold
per SLD (LT-01)
Transformer LT Panel & Solar Provision, Sync
9 with PFI, Outgoing Panels, As per SLD (LT-02) 11 Panels + 1 Ally Green T&D No. 1 UnHold

10 Lighting DB for Mills, Workshop, Office 1 Box Green T&D No. 12 UnHold
11 Main Lighting DB 2 Boxes Green T&D No. 1 UnHold
12 LAB DB 1 Box Green T&D No. 1 UnHold
Blow Room DB & 1 Box+ 1 Ally Green T&D
13 No. 2 UnHold
Waste Room DB 1 Panel+ 1 Ally Green T&D
14 Packing DB 1 Box+ 1 Ally Green T&D No. 1 UnHold
15 Compressor DB 2 Boxes Green T&D No. 1 UnHold
16 Labour Colony Main DB 1 Panel+ 1 Ally Green T&D No. 1 UnHold
17 Labour Color Sub DB 1 Box Green T&D No. 10 UnHold
18 Masjid DB 1 Box Green T&D No. 1 UnHold
19 Junior Staff Hostel DB G1-G6,F1-F6,S1-S6 1 Box Green T&D No. 7 UnHold
20 Senior and Guest House Main DB 1 Panel+ 1 Ally Green T&D No. 1 UnHold
21 Senior Staff DB 1 Box Green T&D No. 1 UnHold
22 Senior Staff DB 2 1 Box Green T&D No. 1 UnHold
BTD 6300A for LT-01 & LT-02 for neutral as
23 Green T&D Job. 1 UnHold
per Drawing Std 2.5M with fitting
24 Flexible Link for BTD for LT-01 & LT-02 Green T&D No. 2 UnHold

Special Instructions:
Copper LOCAL - IMPORTED √
Sleeves TINNED √ Color SLEEVES -
Paint RAL-7035 √ RAL-7032 -
Packing Normal √ Wooden -

Sales Mngr/Engr
Mr. Hamad Gul

ATTACHMENT
PO Attached
GA Drawings Attached

Prepared By:
Syed Ahmed Hassan
SPECIAL-NOTE
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF OF

POWER HOUSE PANEL (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED,
DUPLICATED,REPRODUCED TO THE THIRD PARTY IN
ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION
OF GREEN T&D (PVT) LTD.

SPECIAL INSTRUCTIONS

-
-

FOR APPROVAL

FOR MANUFACTURING

AS BUILT
DESCRIPTION
-

NG
11KV,630A 25KA VCB PANEL

R I CLIENT
NASEEM TEXTILE MILLS

TU PROJECT

AC
NASEEM TEXTILE MILLS

UF
CONSULTANT

N/A

A N PROJECT-NO

M GTD-570341221-REV04

O R DRAWING-NO

F MO-NUMBER
SGA-570341221

MO-412311222

REVISION

REV DATE DESCRIPTIONS OF MODIFICATIONS BY

- - -

- - - -

- - -

DESIGN-BY M.A DRAWN-DATE 12.08.2022

CHECKED-BY M.A SCALE N.T.S

C.CHECKED-BY S.A QTY 01

APPROVED-BY M.A.A SHEET-NO 01 OF 08

T & D (PVT) Ltd

104 J-BLOCK Johar Town, Near Mughal Eye Hospital,


Lahore Pakistan.
Tel: +924235458591-93 Fax: +924235458590
Web Site: www.greentnd.com E-mail: info@greentnd.com
POWER HOUSE PANEL

DRAWING INDEX
Ser.
No DRAWING NO Description SHEET NO REV REMARKS

1 SGA-570341221 COVERING PAGE SHEET NO. 1 OF 08 00


2 SGA-570341221 DRAWING INDEX SHEET NO. 2 OF 08 00
3 SGA-570341221 TECHNICAL SPECIFICATIONS SHEET NO. 3 OF 08 00
4 SGA-570341221 SINGLE LINE DIA GRAM SHEET NO. 4 OF 08 00
5 SGA-570341221 FRONT SIDE EXTERNAL VIEW & FRONT SIDE INTERNAL VIEW SHEET NO. 5 OF 08 00
6 SGA-570341221 REAR SIDE EXTERNAL VIEW & BOTTOM VIEW & REAR SIDE INTERNAL VIEW & TOP VIEW SHEET NO. 6 OF 08 00
7 SGA-570341221 SIDE VIEW BUS PT PANEL SIDE VIEW SHEET NO. 7 OF 08 00
8 SGA-570341221 OUTGOING PANEL SIDE VIEW SHEET NO. 8 OF 08 00

REVISION DRAWING INDEX


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 12.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY 11KV,630A 25KA VCB PANEL
T & D (PVT) Ltd CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S
FOR PROJECT NASEEM TEXTILE MILLS
- - - - MANUFACTURING C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan. APPROVED BY M.A.A SHEET NO 02 OF 08
DRAWING NO SGA-570341221
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO-412311222 REV NO 00
MO NUMBER
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
TECHNICAL SPECIFICATIONS

RATED VOLTAGE 17.5KV


RATED POWER FREQUENCY WITHSTAND VOLTAGE 38KV
RATED IMPLUSE WITHSTAND VOLTAGE 95KV
RATED SHORT CIRCUIT BREAKING CURRENT 25KA
RATED FREQUENCY 50Hz.
IP PROTECTION IP4X
RATED MAIN BUSBAR
VCB INTERCONNECTION 630 AMP 1(60x5)
EARTH BUSBAR COPPER 1(25x5)
POLE TO POLE DISTANCE 210 mm
PANEL DESIGN TYPE. BOLTED (Schneider Standard)
MANUFACTURING TOLERANCE
COPPER 99.9% Imported With Tined & Sleeved
COLOUR RAL 7035
CUBICAL DIMENSION (HxWxD) As per Drawings
CABLE ENTRY FROM BOTTOM
MS SHEET THICKNESS 2.5 mm & 2.mm (standard tolerance limits applied)

REVISION TECHNICAL SPECIFICATIONS OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 12.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY 11KV,630A 25KA VCB PANEL
T & D (PVT) Ltd CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S
FOR PROJECT NASEEM TEXTILE MILLS
- - - - MANUFACTURING C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan. APPROVED BY M.A.A SHEET NO 03 OF 08
DRAWING NO SGA-570341221
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO-412311222 REV NO 00
MO NUMBER
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
3-PHASE, 11KV, 1250A, 50HZ, 25KA, 95KV BIL

ES HEATER CB CB CB CB CB ES HEATER CB CB CB CB CB HEATER CB CB CB CB CB


ON ON SERVICE TEST TRIP OFF ON ON ON SERVICE TEST TRIP OFF ON ON SERVICE TEST TRIP OFF ON

G R B W Y R G G R B W Y R G R B W Y R G

E.M OFF ON
E.M OFF ON E.M OFF ON
PB PB PB
PB PB PB PB PB PB

-S2 -S1B -S1A


-S2 -S1B -S1A -S2 -S1B -S1A

HSS HSS HSS


-LS1 -LS1 -LS1
-Q2 -Q1 -QM
17.5KV,630A M 17.5KV,630A M 17.5KV,630A M
25KA, VCB 25KA, VCB 25KA, VCB

INTERLOCKED
INTERLOCKED

MECHANICAL
MECHANICAL
EARTH EARTH
SWITCH SWITCH

PHASE INDICATION PHASE INDICATION PHASE INDICATION


Y-Y PT
T11~T13 B Y R
B Y R B Y R 200VA, CL-0.5
MCB, MCB, PT MCB,
10ATP -S70 -P16 10ATP -S70 -P16 FUSE 11KV/ 3 / 110VAC/ 3 10ATP -S70 -P16

V/SS V/M V/SS V/M Y Y V/SS V/M

-F26 -F26
T/F STATUS T/F STATUS
-1T1~1T3 RELAY -1T1~1T3 RELAY -1T1~1T3
200/ 5A -F50/51N 200/ 5A -F50/51N 400/ 5A -F50/51N
O/C & E/F O/C & E/F O/C & E/F
PROTECTION CT PROTECTION CT PROTECTION CT
RELAY RELAY RELAY
CL-5P20, 15VA CL-5P20, 15VA CL-5P20, 15VA

-S69 -P1 -S69 -P1 -S69 -P1


-2T1~2T3 E/A A/SS A/M -2T1~2T3 E/A A/SS A/M -2T1~2T3 E/A A/SS A/M
200/ 5A 200/ 5A 400/ 5A

METERING CT METERING CT METERING CT


CL-0.5M5, 10VA CL-0.5M5, 10VA CL-0.5M5, 10VA

SURGE
ARRESTOR

OUTGOING-2 OUTGOING-1 INCOMING

REVISION SINGLE LINE DIAGRAM


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 12.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY 11KV,630A 25KA VCB PANEL
T & D (PVT) Ltd CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S
FOR PROJECT NASEEM TEXTILE MILLS
- - - - MANUFACTURING C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan. APPROVED BY M.A.A SHEET NO 04 OF 08
DRAWING NO SGA-570341221
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO-412311222 REV NO 00
MO NUMBER
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
OUTGOING PANEL OUTGOING PANEL INCOMING PANEL OUTGOING PANEL OUTGOING PANEL INCOMING PANEL
PENAL NO : CUBICAL NO 01 CUBICAL NO 02 CUBICAL NO 03 PENAL NO : CUBICAL NO 01 CUBICAL NO 02 CUBICAL NO 03 POWER HOUSE
HOOTER HOOTER HOOTER HOOTER

PANEL

185
-H1 -H2 -H3 -H4 -H5 -H6 -H7 -H8 -H9 -H10 -H1 -H2 -H3 -H4 -H5 -H6 -H7 -H8 -H9 -H10 -H1 -H2 -H3 -H4 -H5 -H6 -H7 -H8 -H9
PANEL LIMIT PANEL LIMIT PANEL LIMIT
RED YELLOW BLUE ON OFF TRIP
RED YELLOW BLUE ON OFF TRIP VCB TEST VCB SERVICE HEATER ON E.S ON RED YELLOW BLUE ON OFF TRIP VCB TEST VCB SERVICE HEATER ON E.S ON VCB TEST VCB SERVICE HEATER ON
LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH

-F51 -P1 -P16 -F51 -P1 -P16 -F51 -P1 -P16


P111 P111 P111

A V 8888 A V 8888 A V 8888 MCB, s


AUX. RELAY
MCB, s
AUX. RELAY
MCB, s
AUX. RELAY

565
615
E/A E/A E/A

365
AMP-METER VOLT-METER ENERGY ANALYZER AMP-METER VOLT-METER ENERGY ANALYZER AMP-METER VOLT-METER ENERGY ANALYZER

-F26 -S69 -S70 -S3 -F26 -S69 -S70 -S3 -S69 -S70 -S3
TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK
AMP-SELECTOR VOLT-SELECTOR M/O/A SELECTOR AMP-SELECTOR VOLT-SELECTOR M/O/A SELECTOR AMP-SELECTOR VOLT-SELECTOR M/O/A SELECTOR
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH

-S1 -S2 -S1 -S2 -S1 -S2

ON-PB OFF-PB E.-PB ON-PB OFF-PB E.-PB ON-PB OFF-PB E.-PB

SIDE DISH
293

COVER
OUTGOING OUTGOING INCOMING

SIDE DISH

SIDE DISH
PANEL PANEL PANEL

COVER

COVER
SIDE DISH

Schneider Electric Schneider Electric Schneider Electric


Withdraw out Metal-Clad & Metal-Enclosed Switchgear Withdraw out Metal-Clad & Metal-Enclosed Switchgear Withdraw out Metal-Clad & Metal-Enclosed Switchgear
COVER

VCB 630A VCB 630A VCB 630A


295

295

295
GREEN T&D (PVT.) LTD. GREEN T&D (PVT.) LTD. GREEN T&D (PVT.) LTD.
300
2200

2200
110

110

110
GLASS WINDOW GLASS WINDOW GLASS WINDOW
850

! ! !
300

300 300 300


340

340

340
HVX HVX HVX
128

128

128
68

68

68

140
295

PT COMPARTMENT PT COMPARTMENT PT COMPARTMENT

675
262
540

PT 1 PT 2 PT 3
200

750 750 750


800 800 800
800 800 800
2400
2400
OUTGOING PANEL OUTGOING PANEL INCOMING PANEL OUTGOING PANEL OUTGOING PANEL INCOMING PANEL
TRAFO PANEL 01 TRAFO PANEL 02 TRAFO PANEL 01 TRAFO PANEL 02

FRONT SIDE EXTERNAL VIEW NOTE: FRONT SIDE INTERNAL VIEW

1. ALL DIMENSIONS ARE IN MM.


PANEL LABEL. OUTGOING PANEL OUTGOING PANEL INCOMING PANEL 2. ENCLOSURE SHALL BE WITH 12 SWG MS. SHEET.
PANEL NO. Q Q Q
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR TYPE.
CIRCUIT BREAKER VCB 630A 25KA 1 No VCB 630A 25KA 1 No VCB 630A 25KA 1 No
SHUNT OPENING COIL 110VAC 110VAC 110VAC 4.
SHUNT CLOSING COIL 110VAC 110VAC 110VAC 5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM BOTTOM.
UVT ---------------- ---------------- 110VAC
MOTOR MACHANISM 220VAC 220VAC 220VAC
6. PANELS SHALL BE FRONT & REAR ACCESS.
PROTECTION, METERING C.T,S 200/5/5A 3 No 200/5/5A 3 No 400/5/5A 3 No 7. PROTECTION CLASS IP4X (INDOOR TYPE FLOOR STANDING).
11000 / 110V
POTENTIAL TRANSFORMER. ---------------- ---------------- S.P.
3 3 3 No 8. ENCLOSURE SHALL BE : BOLTED TYPE.
MAIN CABLE. ---------------- ---------------- ---------------- 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET.
11. COPPER SHOULD BE TINNED & SLEEVED.

REVISION FRONT SIDE EXTERNAL VIEW OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 12.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY 11KV,630A 25KA VCB PANEL
T & D (PVT) Ltd CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S
FOR PROJECT NASEEM TEXTILE MILLS
- - - - MANUFACTURING C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan. APPROVED BY M.A.A SHEET NO 05 OF 08
DRAWING NO SGA-570341221
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO-412311222 REV NO 00
MO NUMBER
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
OUTGOING PANEL OUTGOING PANEL INCOMING PANEL PENAL NO : OUTGOING PANEL OUTGOING PANEL INCOMING PANEL
PENAL NO : CUBICAL NO 01 CUBICAL NO 02 CUBICAL NO 03 CUBICAL NO 01 COUPLING CUBICAL NO 02 CUBICAL NO 03 POWER HOUSE
PIECE
PANEL
560 560 560
210 210 210

60

60

60
235

175

175

175
210 210 210

1040

60

60

60
HANDLE HANDLE HANDLE

235

175

175

175
210 210 210

REAR COVER REAR COVER REAR COVER

60

60

60

SIDE DISH
SIDE DISH

COVER
COVER

SIDE DISH
DISH

COVER
COVER
MONO MONO MONO
2200 SIDE

BLOCK BLOCK BLOCK

2200
210 210 210 210 210 210
REAR DOOR REAR DOOR REAR DOOR

C.T,S

C.T,S

C.T,S
240
1040

180

180

180
GLASS WINDOW GLASS WINDOW GLASS WINDOW

680
OUTGOING CABLE OUTGOING CABLE INCOMING CABLE
300 300 300

800 800 800 800 800 800


OUTGOING PANEL OUTGOING PANEL INCOMING PANEL OUTGOING PANEL OUTGOING PANEL INCOMING PANEL
2400 2400

REAR SIDE INTERNAL VIEW REAR SIDE INTERNAL VIEW

MESH MESH MESH


OUTGOING CABLING PLATE OUTGOING CABLING PLATE INCOMING CABLING PLATE
1600

1600
LIFTING LIFTING LIFTING
BOLT BOLT BOLT

800 800 800 800 800 800


BOTTOM VIEW TOP VIEW

REVISION FRONT SIDE INTERNAL VIEW OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 12.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY 11KV,630A 25KA VCB PANEL
T & D (PVT) Ltd CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S
FOR PROJECT NASEEM TEXTILE MILLS
- - - - MANUFACTURING C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan. APPROVED BY M.A.A SHEET NO 06 OF 08
DRAWING NO SGA-570341221
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO-412311222 REV NO 00
MO NUMBER
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
INCOMING PANEL

WALL WALL
1000 1600 1800
Explosion vent
FROM REAR WALL BUSHING PLATE FROM FRONT

METERING
BUS BAR

235
COMPARTMENT
COMPARTMENT

235
FRONT

60
VCB COMPARTMENT

VCB 630A
VCB TEST & SERVICE
240 POSITION
C.T,s

CT & INCOMING PT COMPARTMENT


COMPARTMENT VCB TROLLEY FOR
HT FUSE
RACK IN & OUT
680

INCOMING

VCB TROLLEY
575
CABLE

ARRESTER
SURGE
P.T,S

FLOOR LEVEL FLOOR LEVEL

1000 1600 1800

SIDE VIEW INCOMING PANEL

REVISION SIDE VIEW OF OUTGOING PANEL


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 12.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY 11KV,630A 25KA VCB PANEL
T & D (PVT) Ltd CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S
FOR PROJECT NASEEM TEXTILE MILLS
- - - - MANUFACTURING C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan. APPROVED BY M.A.A SHEET NO 07 OF 08
DRAWING NO SGA-570341221
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO-412311222 REV NO 00
MO NUMBER
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
OUTGOING PANEL

WALL WALL
1000 1600 1800
Explosion vent
FROM REAR WALL BUSHING PLATE FROM FRONT

METERING
BUS BAR

235
COMPARTMENT
COMPARTMENT

235
FRONT

60
VCB COMPARTMENT

2200
VCB 630A
VCB TEST & SERVICE
240 POSITION
C.T,s EARTH
SWITCH

CT & OUTGOING PT COMPARTMENT


COMPARTMENT VCB TROLLEY FOR
RACK IN & OUT
680

OUTGOING

VCB TROLLEY

575
CABLE

FLOOR LEVEL FLOOR LEVEL

SIDE VIEW
OUTGOING PANEL

REVISION SIDE VIEW OF OUTGOING PANEL


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 12.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY 11KV,630A 25KA VCB PANEL
T & D (PVT) Ltd CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S
FOR PROJECT NASEEM TEXTILE MILLS
- - - - MANUFACTURING C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan. APPROVED BY M.A.A SHEET NO 08 OF 08
DRAWING NO SGA-570341221
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO-412311222 REV NO 00
MO NUMBER
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
SPECIAL-NOTE
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF OF
(GREEN T&D) AND MAY NOT BE COPIED, EXPLODED,
DUPLICATED,REPRODUCED TO THE THIRD PARTY IN
ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION
OF GREEN T&D (PVT) LTD.

SPECIAL INSTRUCTIONS

-
-

FOR APPROVAL

FOR MANUFACTURING

AS BUILT
DESCRIPTION

LT & PFI PANELS

CLIENT
NASEEM TEXTILE MILLS

IN G PROJECT

UR
N/A

T
CONSULTANT

C N/A

UFA PROJECT-NO

GTD-570341221-REV04

AN DRAWING-NO

R M M.O-NUMBER
SGA-570341221

F O MO-412311222

REVISION

REV DATE DESCRIPTIONS OF MODIFICATIONS BY

- - -

DESIGN-BY M.A DRAWN-DATE 11.08.2022

CHECKED-BY M.A SCALE N.T.S

C.CHECKED-BY S.A REV NO 00

APPROVED-BY M.A.A SHEET-NO 01 OF 30

T & D (Pvt) Ltd


104 J-BLOCK Johar Town, Near Mughal Eye Hospital,
Lahore Pakistan.
Tel: +924235458591-93 Fax: +924235458590
Web Site: www.greentnd.com E-mail: info@greentnd.com
15350
2
140
ALD2
W1 W1 1050 X 2100

1800 X 1200

1000
1200
DN.

PFI PANEL
300KVAR

700
CUBICAL 1

WINDING A/C PLANT

230

RING A/C PLANT


PFI PANEL
OPERATOR DESK

300KVAR

700
CUBICAL 2

2800

REAR SIDE
PFI PANEL
FRONT SIDE
PFI PANEL
MAIN L. T. ROOM

700

5880
3700
CUBICAL 3

PFI PANEL
300KVAR
6000

900

PFI PANEL
300KVAR

700
650 12500 CUBICAL 4
PFI PANEL FRONT SIDE LT PANEL FRONT SIDE LT PANEL FRONT SIDE LT PANEL FRONT SIDE
CUBICAL 10 CUBICAL 9 100
CUBICAL 14 CUBICAL 13 CUBICAL 11
700 700 CUBICAL 8 CUBICAL 7
CUBICAL 21 CUBICAL 20 CUBICAL 19 CUBICAL 18 CUBICAL 17 CUBICAL 16 CUBICAL 15 CUBICAL 12

BUS BAR CHAMBER


OUTGOING OUTGOING
100

PANEL 2500A ACB


OUTGOING OUTGOING

DUMMY PANEL
CUBICAL 5

PFI INCOMING
FLANGE 2500A FLANGE 2500A

PFI ACB PANEL


FRONT SIDE
FLANGE 3200A FLANGE 3200A
PFI PANEL PFI PANEL PFI PANEL PFI PANEL BUS
300KVAR 300KVAR 300KVAR 300KVAR PFI INCOMING 1600A MCCB OUT INCOMING 01 1600A MCCB OUT INCOMING 02
OUTGOING BUS WAY OUTGOING SOLAR PANEL COUPLER 5000A TP ACB OUTGOING BUS WAY OUTGOING SOLAR PANEL
PANEL 2500A ACB 5000A TP ACB 5000A TP ACB
CONNECTION TOP SIDE CONNECTION 3200A CONNECTION TOP SIDE CONNECTION 3200A
THROUGH BUS WAY THROUGH BUS WAY THROUGH BUS WAY THROUGH BUS WAY
FROM TOP FROM TOP FROM TOP FROM TOP 100
2500A 3200A 2500A 3200A CUBICAL 6

400
700 700 OTHER MCCB OUT 700 700 1000 1000 400 OTHER MCCB OUT 700 700 1000 1200
FROM BOTTOM FROM BOTTOM
400

1180
700 700 700 700

780

780

780
ALD1 DOOR 700
PFI PANEL REAR SIDE
13800
1500 X 2700

5000

5000
710

BTD 5000A

BTD 5000A
FUTURE SPACE
OUTGIONG PANEL
BOTTOM

800
VIEW

PANEL
OUTGIONG PANEL
6000

BOTTOM

OUTGIONG PANEL

800
VIEW

1
OUTGIONG PANEL
BOTTOM

OUTGIONG PANEL

800

5710
VIEW

1300 900
CABLING PLATE
INCOMING CABLING PLATE

INCOMING
BOTTOM

800
VIEW

3000 KVA 3000 KVA


TRANSFORMER 01 TRANSFORMER 02
LT PANEL 01 & 02
WAPDA
PANEL
900

900

2380 1600 1550 230


ROOM LAYOUT
800

LOUVERED DOOR LOUVERED DOOR LOUVERED DOOR


2400 X 2700 3000 X 3000 3000 X 3000
MANHOLE 900X900
FOR OIL COLLECTING

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LT PANEL LAYOUT

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 02 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
AIR OUT AIR OUT AIR OUT AIR OUT AIR OUT

EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 6"
WITH COVER WITH COVER WITH COVER WITH COVER WITH COVER

PFI INCOMING
PFI PANEL PFI PANEL PFI PANEL PFI PANEL
40M PANEL

ON OFF TRIP

EARTH BUS BAR

NEUTRAL BUS BAR


PFI
R 8888
E
L
A
Y
P/F
PFI RELAY

CONTINUE SWITCHBOARD
TO NEXT SHEET 04 OF 30
ON ON ON ON ON ON ON ON ON ON ON ON

ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB

PFI INCOMING PANEL


OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB

SIDE DISH COVER

SIDE DISH COVER

SIDE DISH COVER


DUMMY PANEL
2500A ACB
A.O.M

2200

2200
LOUVERS LOUVERS LOUVERS LOUVERS
WITH FAN 8" WITH FAN 8" WITH FAN 8" WITH FAN 8"

BLUE YELLOW RED


PHASE PHASE PHASE

DOOR DOOR DOOR DOOR DOOR


EARTHING EARTHING EARTHING EARTHING EARTHING
BLUE YELLOW RED
PHASE PHASE PHASE

CUBICAL 01 CUBICAL 02 CUBICAL 03 CUBICAL 04 CUBICAL 05


700 700 700 700 900 800
2800 900
PFI INCOMING 2000A ACB
PFI PANEL PFI PANEL PFI PANEL PFI PANEL DUMMY PANEL REAR VEIW DUMMY PANEL

FRONT SIDE EXTERNAL VIEW


600
1200

600

700 700 700 700 900


3700

BOTTOM VIEW

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LT-01&02 (OPTION 01;WITH CIRCUTOR PFI)

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 03 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
INCOMING 02 OUTGOING OUTGOING OUTGOING INCOMING 01
THROUGH BUS WAY THROUGH BUS WAY THROUGH BUS WAY
THROUGH BTD FROM TOP FROM TOP FROM TOP
THROUGH BTD

TRANSFORMER INCOMING SOLAR INCOMING BUS COUPLER TRANSFORMER INCOMING SOLAR INCOMING
OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL BUS BAR CHAMBER
14M PANEL 01

14M PANEL 01
14M 40M 14M 14M PANEL
14M PANEL 01

14M PANEL 01

LIVE PHASE LIVE PHASE LIVE PHASE LIVE PHASE


R Y B ON OFF TRIP R Y B ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP R Y B ON OFF TRIP R Y B ON OFF TRIP

ON P/B OFF P/B ON P/B OFF P/B ON P/B OFF P/B ON P/B OFF P/B ON P/B OFF P/B

8888 8888 8888


E/A P/M E/A
8888 8888 8888 8888
E/A SPACE ONLY E/A E/A SPACE ONLY E/A

DEEP SEA ELECTRONICES


DSE8660
SPACE ONLY DOOR DEEP SEA ELECTRONICES
DSE8660

EARTHING
E/Stop A/O/M E/Stop A/O/M

DOOR DOOR DOOR DOOR DOOR DOOR SPACE ONLY


EARTHING EARTHING EARTHING EARTHING EARTHING EARTHING
TO PREVIOUS SHEET 04 OF 30

CONTINUE SWITCHBOARD
TO NEXT SHEET 05 OF 30
CONTINUE SWITCHBOARD

12M 12M 12M 12M 12M 12M 12M

DOOR
EARTHING

DOOR DOOR DOOR DOOR DOOR DOOR


EARTHING EARTHING SPACE ONLY EARTHING EARTHING EARTHING EARTHING SPACE ONLY

14M INCOMING 14M INCOMING 14M OUTGOING 14M OUTGOING 14M BUS COUPLER 14M INCOMING 14M INCOMING
ACB 5000A TP ACB 3200A TP ACB 3200A TP ACB 2500A TP ACB 5000A TP ACB 5000A TP ACB 3200A TP

DOOR POCKET
DOOR POCKET

DOOR
EARTHING
LOUVER DOOR
EARTHING
LOUVER DOOR
EARTHING
LOUVER DOOR
EARTHING
DOOR
EARTHING
LOUVER DOOR DOOR
EARTHING
LOUVER DOOR
EARTHING
LOUVER DOOR
EARTHING
LOUVER
EARTHING
LOUVERS

CUBICAL 06 CUBICAL 07 CUBICAL 08 CUBICAL 09 CUBICAL 10 CUBICAL 11 CUBICAL 12 CUBICAL 13


1000 700 700 700 700 400 1000 1000 700
6900
INCOMING FROM INCOMING FROM COPPER BUS COUPLER INCOMING FROM INCOMING FROM
TRANSFORMER 02 SOLAR 01 OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL CHAMBER ACB 5000A TP TRANSFORMER 01 SOLAR 01

FRONT SIDE EXTERNAL VIEW

OTHER MCCB OUT

400
FROM BOTTOM

1600A MCCB OUT


800

800
BUS WAY
TOP SIDE

1000 700 700 700 700 400 1000 1000 700


6900

BOTTOM VIEW

REVISION GA OF LT & PFI PANEL


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LT-01&02 (OPTION 01;WITH CIRCUTOR PFI)

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 00
104 J-BLOCK Johar Town, Near Mughal Eye PROJECT NO GTD-570341221-REV04
Hospital,
STD-570341221 APPROVED BY M.A.A SHEET NO 04 OF 30
Lahore Pakistan. DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: MO NUMBER MO-412311222 REV NO 00
info@greentnd.com THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
AIR OUT AIR OUT AIR OUT AIR OUT AIR OUT
OUTGOING OUTGOING OUTGOING
THROUGH BUS WAY THROUGH BUS WAY THROUGH BUS WAY EXHAUST FAN 6" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8"
WITH COVER WITH COVER WITH COVER WITH COVER WITH COVER
FROM TOP FROM TOP FROM TOP

PFI INCOMING
OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL PFI PANEL PFI PANEL PFI PANEL PFI PANEL
14M 40M 14M 14M PANEL

ON OFF TRIP ON OFF TRIP ON OFF TRIP

8888 8888 8888


E/A P/M E/A

PFI
R 8888
E
L
A P/F
Y

PFI RELAY

DOOR DOOR DOOR


EARTHING EARTHING EARTHING ON ON ON ON ON ON ON ON ON ON ON ON

TO PREVIOUS SHEET 04 OF 30
CONTINUE SWITCHBOARD
ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB ON PB

OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB OFF PB

12M 12M 12M

SIDE DISH COVER


A.O.M

DOOR DOOR DOOR


EARTHING EARTHING EARTHING

14M 14M 14M LOUVERS LOUVERS LOUVERS LOUVERS


OUTGOING PFI INCOMING
OUTGOING WITH FAN 8" WITH FAN 8" WITH FAN 8" WITH FAN 8"
ACB 2500A TP ACB 2000A TP
ACB 3200A TP

DOOR POCKET

DOOR
EARTHING
LOUVER DOOR
EARTHING
DOOR
EARTHING
LOUVER DOOR
EARTHING
LOUVER DOOR
EARTHING
DOOR
EARTHING
DOOR
EARTHING
DOOR
EARTHING
LOUVERS

CUBICAL 14 CUBICAL 15 CUBICAL 16 CUBICAL 17 CUBICAL 18 CUBICAL 19 CUBICAL 20 CUBICAL 21


700 700 700 700 700 700 700 700
5600
OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL PFI INCOMING PANEL PFI PANEL PFI PANEL PFI PANEL PFI PANEL

FRONT SIDE EXTERNAL VIEW


400

OTHER MCCB OUT


FROM BOTTOM

600
1600A MCCB OUT
800

BUS WAY

600
TOP SIDE

700 700 700 700 700 700 700 700


5600

BOTTOM VIEW

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LT-01 & 02 (OPTION 01;WITH CIRCUTOR PFI)

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 05 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
AIR OUT AIR OUT AIR OUT AIR OUT AIR OUT

EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 6"
WITH COVER WITH COVER WITH COVER WITH COVER WITH COVER

PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL


LIGHT LIGHT LIGHT LIGHT LIMIT
SWITCH SWITCH SWITCH SWITCH LIGHT SWITCH

EARTH BUS BAR


Earth

NEUTRAL BUS BAR

H.R.C FUSE H.R.C FUSE H.R.C FUSE H.R.C FUSE


11K3 11K2 11K1 9K3 9K2 9K1 7K1 6K2 6K1 3K1 2K1 1K1
CT/S/L TH F1

CONTINUE SWITCHBOARD
TO NEXT SHEET 07 OF 30
50 KVR 50 KVR 50 KVR 150 KVR 100 KVR 50 KVR 50 KVR 50 KVR

PFI INCOMING PANEL


SIDE DISH COVER

SIDE DISH COVER

SIDE DISH COVER


DUMMY PANEL
2500A ACB
2200

2200
H.R.C FUSE H.R.C FUSE H.R.C FUSE H.R.C FUSE
12K3 12K2 12K1 10K3 10K2 10K1 8K2 8K1 7K2 5K2 5K1 4K1

PFI INCOMING
150 KVR 150 KVR 100 KVR 100 KVR 100 KVR 50 KVR ACB 2000TP

Auxiliary Auxiliary
TERMINAL TERMINAL
F1~F5 TH TH Contactor F1 TH BLOCK
F1TH BLOCK
F1~F5 TH TH Contactor
30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR
RED YELLOW BLUE
PHASE PHASE PHASE

RED YELLOW BLUE


PHASE PHASE PHASE

CUBICAL 01 CUBICAL 02 CUBICAL 03 CUBICAL 04 CUBICAL 05


700 700 700 700 900 800
3700
PFI INCOMING 2000A ACB
PFI PANEL PFI PANEL PFI PANEL PFI PANEL DUMMY PANEL REAR VEIW DUMMY PANEL

FRONT SIDE INTERNAL VIEW

DUMMY COPPER SIZES


MAIN BUSBAR 5000A 8(100x5)
PANEL NEUTRAL BUS BAR 4(100x5)
EARTH BUS BAR 2(100x5)
INTERCONNECTION
ACB 5000A TP 8(100x5)
DUMMY ACB 3200A TP 4(100x5)
ACB 2500A TP 3(100x5)
PANEL MCCB 1600A TP 2(80x5)
MCCB 400A TP 1(30x5)
MCCB 200A TP 1(20x5)

700 700 700 700 900 800 DROPPER BUS BARS


PANEL NO 09 & 15 1(30x5)
TOP VIEW PFI PANEL BUS BAR
MAIN BUSBAR 2500A 3(100x5)
EARTH BUS BAR 1(100x5)
ACB 2500A TP 3(100x5)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LT-01 & 02 (OPTION 01;WITH CIRCUTOR PFI)

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 06 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
INCOMING 02 OUTGOING OUTGOING OUTGOING INCOMING 01
THROUGH BUS WAY THROUGH BUS WAY THROUGH BUS WAY
THROUGH BTD FROM TOP FROM TOP FROM TOP
THROUGH BTD

PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT
LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH

Earth Earth Earth Earth Earth Earth Earth Earth

Neutral Neutral Neutral Neutral Neutral Neutral Neutral Neutral

H.R.C FUSE H.R.C FUSE

SPD FP O/G 200A X 2 SPD FP


F1~F4 TH 1 R1 MCB TP Timer CT/S/L R1
F1~F4 CT/S/L TH F1~F3 CT/S/L TH F1~F3 F1~F3 TH 1 R1 F1~F4 TH 1 R1 MCB TP Timer CT/S/L R1
F1~F4
C/S.LINK C/S.LINK C/S.LINK
TO PREVIOUS SHEET 06 OF 30

CONTINUE SWITCHBOARD
TO NEXT SHEET 08 OF 30
CONTINUE SWITCHBOARD

UV/OV Relay UV/OV Relay


SAPCE ONLY SAPCE ONLY

ACRYLIC
Schneider
Electric
Schneider
Electric

SHEET
2200

2200
O/G 1600A
O/G 400A
SPACE ONLY OUTGOING OUTGOING SPACE ONLY
INCOMING ACB 5000A TP ACB 5000A TP INCOMING ACB 5000A TP
INCOMING ACB 3200A TP ACB 3200TP ACB 2500TP INCOMING ACB 3200A TP

F1~F3
Schneider
Electric

NSX 400-630A

C.T Schneider C.T C.T


Electric

C.T C.T C.T C.T C.T C.T C.T C.T


5000/5A C.T C.T C.T
5000/5A C.T C.T C.T
5000/5A C.T C.T C.T
PFI C.T C.T,S C.T,S C.T C.T
C.T,S PFI C.T PFI C.T C.T,S
C.T C.T C.T C.T
3200/5A 3000/5A C.T
2500/5A 5000/5A 3200/5A
C.T,S

CUBICAL 06 CUBICAL 07 CUBICAL 08 CUBICAL 09 CUBICAL 10 CUBICAL 11 CUBICAL 12 CUBICAL 13


1000 700 700 700 700 400 1000 1000 700
6900
INCOMING FROM INCOMING FROM COPPER BUS COUPLER INCOMING FROM INCOMING FROM
TRANSFORMER 02 ACB 5000A TP SOLAR ACB 3200A TP OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL CHAMBER ACB 5000A TP TRANSFORMER 01 ACB 5000A TP SOLAR ACB 3200A TP

FRONT SIDE INTERNAL VIEW

400
OTHER MCCB OUT
FROM BOTTOM

OUTGOING
CONNECTION 1600A MCCB OUT
800

BUS WAY
THROUGH BUS WAY TOP SIDE
FROM TOP
3200A

1000 700 700 700 700 400 1000 1000 700

TOP VIEW
REVISION GA OF LT & PFI PANEL
FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LT-01&02 (OPTION 01;WITH CIRCUTOR PFI)

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 00
104 J-BLOCK Johar Town, Near Mughal Eye PROJECT NO GTD-570341221-REV04
Hospital,
STD-570341221 APPROVED BY M.A.A SHEET NO 07 OF 30
Lahore Pakistan. DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: MO NUMBER MO-412311222 REV NO 00
info@greentnd.com THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
AIR OUT AIR OUT AIR OUT AIR OUT AIR OUT
OUTGOING OUTGOING OUTGOING
THROUGH BUS WAY THROUGH BUS WAY THROUGH BUS WAY EXHAUST FAN 6" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8" EXHAUST FAN 8"
WITH COVER WITH COVER WITH COVER WITH COVER WITH COVER
FROM TOP FROM TOP FROM TOP

PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT PANEL LIMIT
LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH LIGHT SWITCH

Earth Earth Earth Earth

Neutral Neutral Neutral


H.R.C FUSE H.R.C FUSE H.R.C FUSE H.R.C FUSE
1K1 2K1 3K1 6K1 6K2 7K1 9K1 9K2 9K3 11K1 11K2 11K3
CT/S/L TH F1~F3 O/G 200A X 2
CT/S/L TH F1~F3 CT/S/L TH F1
TO PREVIOUS SHEET 07 OF 30
CONTINUE SWITCHBOARD

50 KVR 50 KVR 50 KVR 100 KVR 150 KVR 150 KVR

SIDE DISH COVER


Schneider Schneider
Electric Electric
2200

H.R.C FUSE H.R.C FUSE H.R.C FUSE H.R.C FUSE


4K1 5K1 5K2 7K2 8K1 8K2 10K1 10K2 10K3 12K1 12K3 12K3
O/G 1600A
O/G 400A
OUTGOING OUTGOING PFI INCOMING
ACB 3200TP ACB 2500TP ACB 2000TP 50 KVR 100 KVR 100 KVR 100 KVR 150 KVR 150 KVR

F1~F3 Auxiliary
TERMINAL TERMINAL TERMINAL
F1~F5 TH TH Contactor F1TH BLOCK
F1TH BLOCK
F1 TH BLOCK
Schneider
Electric

NSX 400-630A

Schneider
Electric

C.T C.T C.T C.T

C.T,S C.T C.T


C.T,S
C.T C.T
3000/5A C.T
2500/5A

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR

30 KVR CAPACITOR
CUBICAL 14 CUBICAL 15 CUBICAL 16 CUBICAL 17 CUBICAL 18 CUBICAL 19 CUBICAL 20 CUBICAL 21
700 700 700 700 700 700 700 700
5600
PFI INCOMING
OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL PANEL PFI PANEL PFI PANEL PFI PANEL PFI PANEL

FRONT SIDE INTERNAL VIEW


400

OTHER MCCB OUT


FROM BOTTOM

600
OUTGOING
CONNECTION
THROUGH BUS WAY 1600A MCCB OUT
BUS WAY

600
FROM TOP TOP SIDE
3200A

700 700 700 700 700 700 700 700

TOP VIEW

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LT-01 & 02 (OPTION 01;WITH CIRCUTOR PFI)

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 08 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
AIR OUT AIR OUT AIR OUT

INCOMING BUS EXHAUST FAN 8"


WITH COVER
EXHAUST FAN 8"
WITH COVER

TIE DUCT

HANDLE
DOOR
WITH LOUVERS 10"

WITH LOUVERS 10"


Earth

VENTILATION

VENTILATION

VENTILATION
EXHAUST FAN 8"

EXHAUST FAN 8"


DETUNED
REACTOR 50KVAR

Neutral Neutral O/G MCB


CABLES

WITH FAN 8" WITH FAN 8"


MCB

LOUVER

FRONT DOOR
FRONT DOOR

FRONT DOOR

FRONT DOOR

BACK DOOR
BTD
BACK DOOR

BACK DOOR
CONNECTION
FROM TOP
DETUNED

LOUVER
REACTOR 50KVAR

O/G

2200
2200

2200
ACB 5000A CABLES
TP

WITH FAN 8" BACK DOOR

30 KVR CAPACITOR

30 KVR CAPACITOR
DETUNED
LOUVERS

LOUVER
LOUVERS

LOUVERS
REACTOR 50KVAR

LOUVERS
C.T

C.T C.T C.T

30 KVR CAPACITOR

30 KVR CAPACITOR
VENTILATION

VENTILATION

VENTILATION

VENTILATION
Earth

800
800 800 600
1200
LEFT SIDE VIEW LEFT SIDE VIEW PFI PANEL SIDE VIEW
INCOMING PANELS OUTGOING PANELS SIDE VIEW WITH DISH COVER

NOTE: MAIN BUSBAR 5000A


COPPER SIZES
8(100x5)
1. ALL DIMENSIONS ARE IN MM. NEUTRAL BUS BAR 4(100x5)
EARTH BUS BAR 2(100x5)
2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET. INTERCONNECTION
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR TYPE PAINT. ACB 5000A TP 8(100x5)
ACB 3200A TP 4(100x5)
4. ACB 2500A TP 3(100x5)
5. INCOMING THROUGH BTD FROM TOP & OUTGOING SHALL BE FROM TOP & BOTTOM THROUGH BUS WAY & CABLE . MCCB 1600A TP 2(80x5)
MCCB 400A TP 1(30x5)
6. PANELS SHALL BE FRONT & REAR ACCESS. MCCB 200A TP 1(20x5)

7. PROTECTION CLASS IP42 (INDOOR TYPE FLOOR STANDING) FORM 1. DROPPER BUS BARS
PANEL NO 09 & 15 1(30x5)
8. ENCLOSURE SHALL BE : BOLTED TYPE. PFI PANEL BUS BAR
MAIN BUSBAR 2500A 3(100x5)
9. LIVE PARTS COVERED WITH THE PROTECTION SHEET. EARTH BUS BAR 1(100x5)
ACB 2500A TP 3(100x5)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LT-02 (OPTION 01;WITH CIRCUTOR PFI)

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 09 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
LIGHTING DB

200

400

200

400

200

400
300

500

600

300

500

600

300

500

600
100

100

100

100
150
0

0
900
900 900 900
LABEL
800
800 LIVE PHASE
800 800
R Y B

700
700 700 700
CAPS LOCK Neutral CU. (30x3)
600
600 600 600
EZC 100F EZC 100F
Earth CU. (15x3)

Schneider
Electric
500
500 500 500
I/C MCCB
50A
400
400 400 400 F1~F3

300
300 300 300 O/G MCB SP O/G MCB
CAPS LOCK 20A 10A SP

32A 3PIN
SOCKET DOOR 200
200 EARTHING 200 200 O/G MCB SP 20A

100
100 100 100

0
0 0 0

EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW


WITH SHROUDING SHEET WITHOUT SHROUDING SHEET
200

400
300

500

600
100

NOTE:
0

150 1. ALL DIMENSIONS ARE IN MM.


100 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
CABLING AREA
3.
3. PAINT OF ENCLOSURE SHOULD BE 7035.
QTY: 12 NOS
0

4. ALL INCOMING & OUTGOING CABLES SHALL BE FROM TOP.


TOP & BOTTOM VIEW 6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS. PHASE DISTRIBUTION BOARD
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
8. ENCLOSURE SHALL BE : WELDED TYPE. RED YELLOW BLUE
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. 20Ax7 (SP) 20Ax7 (SP) 20Ax8 (SP)
10. COPPER TINED.

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LIGHTING DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 12
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 10 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
MAIN LIGHTING DB
1400 1400 250
700 700 700 700

LABEL LABEL COUPLE WITH

DOOR
Neutral

LOCK
CABLE

Neutral
LIVE PHASE
O/G 50A x 5
R Y B

EARTH (20x5)

CU. (20x5)
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F

CAPS LOCK R Y B CAPS LOCK


Schneider Schneider Schneider Schneider Schneider
Electric Electric Electric Electric Electric

KING
LOC
.IN TER
H
MEC
8888 8888 I/C MCCB I/C MCCB
400A 400A
P/M P/M
O/G MCCB O/G 50A x 5
125A

EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F

Schneider Schneider Schneider Schneider Schneider


Electric Electric Electric Electric Electric

F1~F3 F1~F3

CABLE DUCT SIZE

1300
1300

1300
EZC 250F

(60X80)
NSX 400-630A NSX 400-630A

Schneider Schneider
Electric Electric O/G 50A x 4

EZC 100F EZC 100F EZC 100F EZC 100F

DOOR
LOCK
Schneider Schneider Schneider Schneider
Electric Electric Electric Electric

C.T C.T C.T C.T

C.T C.T

DOOR POCKET

DOOR DOOR
CAPS LOCK EARTHING CAPS LOCK EARTHING

EXTERNAL VIEW INTERNAL VIEW SIDE VIEW

NOTE:
1. ALL DIMENSIONS ARE IN MM.
2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET.
1400 3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT.
700 700 4. QTY: 01 NOS
5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM TOP. COPPER SIZES
CABLING CABLING 6. PANELS SHALL BE FRONT & REAR ACCESS.
250

MAIN BUS BAR 400A 1(30x5)


AREA AREA
7. PROTECTION CLASS IP42 (INDOOR TYPE SEMI CANCELLED).FORM 1 NEUTRAL BUS BAR 1(20x5)
EARTH BUS BAR 1(20x5)
8. ENCLOSURE SHALL BE : WELLDED TYPE.
INTERCONNECTION
BOTTOM VIEW 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET. MCCB 400A 3P 1(30x5)
MCCB 125A 3P 1(20x5)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY MAIN LIGHTING DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 11 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
LAB DB

200

400

200

400

200

400
300

500

600

700

300

500

600

700

300

500

600

700
100

100

100

100

175
0

0
800
800 800 800
LABEL
700
700 LIVE PHASE
B 700 700 I/C MCCB 125A
R Y

Neutral CU. (30x3)

600
600 600 600 Earth CU. (15x3)
8888 8888 F1~F3
A/M V/M EZC 250F
500
500 500 500

400
400 400 EZC 100F EZC 100F EZC 100F 400 EZC 100F EZC 100F EZC 100F

A.S.S V.S.S
Schneider Schneider Schneider
Electric Electric Electric

CAPS LOCK
300
300 300 300 O/G MCCB 50A X 3

DOOR 200
200 EARTHING 200 200

100
100 100 100 O/G MCB 20&10A

0
0 0 0

EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW


WITH SHROUDING SHEET WITHOUT SHROUDING SHEET

NOTE:
700
200

400

600
300

500
100

1. ALL DIMENSIONS ARE IN MM.


0

2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
175 3.
100
CABLING AREA 3. PAINT OF ENCLOSURE SHOULD BE 7035.
0
4.
6.
INCOMING FROM TOP & OUTGOING CABLES SHALL BE FROM TOP & BOTTOM.
DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
QTY: 01 NOS
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B. PHASE DISTRIBUTION BOARD
TOP & BOTTOM VIEW 8. ENCLOSURE SHALL BE : WELDED TYPE.
RED YELLOW BLUE
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET.
20Ax3 (SP) 20Ax3 (SP) 20Ax3 (SP)
10. COPPER TINED.
10Ax1 (SP) 10Ax1 (SP) 10Ax1 (SP)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LAB DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 12 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
BLOW ROOM DB
1400 1400 250
450 950 450 950

LABEL LABEL

DOOR
LOCK
LIVE PHASE
R Y B

CAPS LOCK

8888 8888

A/M V/M
C.T C.T

C.T

A.S.S V.S.S
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F

Schneider Schneider Schneider Schneider Schneider Schneider Schneider


Electric Electric Electric Electric Electric Electric Electric

O/G MCB 20A

CABLE DUCT SIZE


O/G 50A x 3 O/G 30A x 4

1300
1300

1300

(60X80)
EZC 250F

NSX 400-630A

O/G MCB
F1~F3 Schneider
Electric 20A

DOOR
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F

LOCK
Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider
Electric Electric Electric Electric Electric Electric Electric Electric

O/G MCCB
125A O/G 50A x 8

I/C MCCB

EARTH (20x5)
400A
O/G MCB
DOOR POCKET 20A

CU. (20x5)
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F

DOOR DOOR Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider

Neutral
Electric Electric Electric Electric Electric Electric Electric Electric

CAPS LOCK EARTHING CAPS LOCK EARTHING


O/G 30A x 8

Neutral CU. (20x5)

EXTERNAL VIEW INTERNAL VIEW SIDE VIEW

NOTE:
1. ALL DIMENSIONS ARE IN MM.
1400
2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET.

450 950
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT. QTY: 01 NOS
4.
COPPER SIZES
5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM BOTTOM.
CABLING MAIN BUS BAR 400A 1(30x5)
CABLING
250

6. PANELS SHALL BE FRONT & REAR ACCESS.


AREA AREA NEUTRAL BUS BAR 1(20x5)
7. PROTECTION CLASS IP42 (INDOOR TYPE SEMI CANCELLED).FORM 1
EARTH BUS BAR 1(20x5)
8. ENCLOSURE SHALL BE : WELLDED TYPE.
INTERCONNECTION
BOTTOM VIEW 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET.
MCCB 400A 3P 1(30x5)
MCCB 125A 3P 1(20x5)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY BLOW ROOM D

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 13 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
WASTE ROOM DB

INCOMING PANEL OUTGOING PANEL


PANEL
EARTH

VENTILATION
LIGHT

NEUTRAL

LIVE PHASE
R Y B

BACK DISH COVER


O/G 30A x 2 O/G 60A O/G 30A x 2 O/G 30A x 3

SIDE DISH COVER


8888 8888
SIDE DISH COVER

SIDE DISH COVER

SIDE DISH COVER


A/M V/M EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F

Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider


Electric Electric Electric Electric Electric Electric Electric Electric

A.S.S V.S.S

FRONT DOOR
I/C MCCB 400A O/G 60A x 3 O/G 30A x 3
1800

1800

1800
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F

Schneider Schneider Schneider Schneider Schneider Schneider


Electric Electric Electric Electric Electric Electric

M.S DOOR
POCKET
F1~F3

O/G 60A x 3 O/G 30A x 3


NSX 400-630A

Schneider
Electric EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F

Schneider Schneider Schneider Schneider Schneider Schneider


Electric Electric Electric Electric Electric Electric

C.T C.T

C.T O/G 60A x 4 O/G 100A x 2

VENTILATION
EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F

Schneider Schneider Schneider Schneider Schneider Schneider

DOOR DOOR Electric Electric Electric Electric Electric Electric

EARTHING EARTHING

LOUVER

CUBICAL 1 CUBICAL 2 CUBICAL 1 CUBICAL 2


400 800 400 800 400
1200 1200
INCOMING PANEL OUTGOING PANEL INCOMING PANEL OUTGOING PANEL SIDE VIEW

FRONT SIDE EXTERNAL VIEW FRONT SIDE INTERNAL VIEW

NOTE:
1. ALL DIMENSIONS ARE IN MM.
CABLING

CABLING

CABLING
AREA

AREA

AREA

2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
400

3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT


4. QTY: 01 NOS
COPPER SIZES
5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM TOP.
400 800 MAIN BUS BAR 400A 1(30x5)
1200 6. PANELS SHALL BE FRONT & REAR ACCESS.
NEUTRAL BUS BAR 1(20x5)
7. PROTECTION CLASS IP42 ( SEMI CANCELLED FLOOR STANDING).
FOUNDATION VIEW 8. ENCLOSURE SHALL BE : BOLTED TYPE.
EARTH BUS BAR
INTERCONNECTION
1(20x5)

9. LIVE PARTS COVERED WITH THE PROTECTION SHEET. MCCB 400A 3P 1(30x5)
MCCB 125A 3P 1(20x5)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY WASTE ROOM DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 14 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
PACKING DB
1100 1100 250
500 600 500 600

LABEL LABEL

DOOR
LOCK
LIVE PHASE
R Y B

CAPS LOCK

8888 8888

A/M V/M
C.T C.T

C.T

A.S.S V.S.S
EZC 100F EZC 100F EZC 100F EZC 100F

Schneider Schneider Schneider Schneider


Electric Electric Electric Electric

CABLE DUCT SIZE


O/G 16A x 4

1300
1300

1300
F1~F3

(60X80)
EZC 250F

NSX 400-630A

Schneider
Electric

DOOR
EZC 100F EZC 100F EZC 100F EZC 100F

LOCK
Schneider Schneider Schneider Schneider
Electric Electric Electric Electric

O/G MCCB
320A O/G 30A x 4

I/C MCCB

EARTH (20x5)
400A

DOOR POCKET

CU. (20x5)
EZC 100F EZC 100F

DOOR DOOR Schneider Schneider

Neutral
Electric Electric

CAPS LOCK EARTHING CAPS LOCK EARTHING


O/G 40A x 2

EXTERNAL VIEW INTERNAL VIEW SIDE VIEW

NOTE:
1100 1. ALL DIMENSIONS ARE IN MM.
500 600 2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET. QTY: 01 NOS
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT. COPPER SIZES
4. MAIN BUS BAR 400A 1(30x5)
CABLING CABLING
250

AREA
5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM BOTTOM. 1(20x5)
AREA NEUTRAL BUS BAR
6. PANELS SHALL BE FRONT & REAR ACCESS.
EARTH BUS BAR 1(20x5)
7. PROTECTION CLASS IP42 (INDOOR TYPE SEMI CANCELLED).FORM 1
INTERCONNECTION
8. ENCLOSURE SHALL BE : WELLDED TYPE.
BOTTOM VIEW 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET.
MCCB 400A 3P 1(30x5)
MCCB 125A 3P 1(20x5)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY PACKING DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 15 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
COMPRESSOR DB
1200 1200 250
600 600 600 600

LABEL LABEL

DOOR
LOCK
EARTH (20x5)
LIVE PHASE
R Y B

O/G 30A x 4
CU. (20x5)
CAPS LOCK

Neutral
8888
P/M I/C MCCB
600A

8888 8888
A/M V/M

CABLE DUCT SIZE

1300
1300

1300
A.S.S V.S.S
F1~F3

(60X80)
O/G MCCB
200A X 4
NSX 400-630A

Schneider
Electric

DOOR
LOCK
C.T C.T

C.T

DOOR POCKET

DOOR DOOR
CAPS LOCK EARTHING CAPS LOCK EARTHING

EXTERNAL VIEW INTERNAL VIEW SIDE VIEW

NOTE:
1200 1. ALL DIMENSIONS ARE IN MM.
600 600 2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET.
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT.
QTY: 01 NOS
4. COPPER SIZES
CABLING CABLING
250

AREA
5. INCOMING FROM TOP & OUTGOING CABLES SHALL BE FROM BOTTOM. 2(30x5)
AREA MAIN BUS BAR 630A
6. PANELS SHALL BE FRONT & REAR ACCESS. NEUTRAL BUS BAR 1(30x5)

7. PROTECTION CLASS IP42 (INDOOR TYPE SEMI CANCELLED).FORM 1 EARTH BUS BAR 1(25x5)
INTERCONNECTION
8. ENCLOSURE SHALL BE : WELLDED TYPE.
BOTTOM VIEW 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET.
MCCB 630A 3P 2(30x5)
MCCB 200A 3P 1(20x5)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY COMPRESSER DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 16 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
LABOUR COLONY MAIN(FEEDER PILLAR)

R Y B R Y B

8888 8888
P/M P/M O/G MCCB O/G MCCB
60A 60A

8888 8888 8888 8888


EZC 250F EZC 250F EZC 250F EZC 250F

A/M V/M A/M V/M EZC 100F

C.T C.T
EZC 100F

Schneider Schneider
Electric Electric

C.T

A.S.S V.S.S A.S.S V.S.S

C.T
O/G MCCB O/G MCCB O/G MCCB O/G MCCB
GLASS 125A 125A 125A 125A

WINDOW F1~F3 F1~F3


EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
1500

1500

1500
Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider
Electric Electric Electric Electric Electric Electric Electric Electric Electric Electric

NSX 400-630A NSX 400-630A


1600

1600

1600
Schneider O/G MCCB X 2 O/G MCCB 100A X 3 Schneider O/G MCCB X 2 O/G MCCB 100A X 3
Electric Electric

DOOR LOCK DOOR LOCK

I/C 600A EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
I/C 600A EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F

Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider
Electric Electric Electric Electric Electric Electric Electric Electric Electric Electric

O/G MCCB 100A X 5 O/G MCCB 100A X 5


DOOR POCKET

N N N N

PE PE PE PE

DOOR DOOR
EARTHING EARTHING
100

100

100
400 600 400 600 400 600 400
CUBICAL -01 CUBICAL -02 CUBICAL -01 CUBICAL -02 CUBICAL -01 CUBICAL -02
1000 1000 1000
SIDE VIEW
EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW
WITH METERING DOOR WITHOUT METERING DOOR

NOTE:
1000
400 600 1. ALL DIMENSIONS ARE IN MM.
2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET.
QTY: 01 NOS
COPPER SIZES
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT.
MAIN BUS BAR 630A 2(30x5)
4. NEUTRAL BUS BAR 1(30x5)
400

5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM BOTTOM. EARTH BUS BAR 1(25x5)
6. PANELS SHALL BE FRONT & REAR ACCESS. INTERCONNECTION
MCCB 630A 3P 2(30x5)
7. PROTECTION CLASS IP65 (INDOOR TYPE FLOOR STANDING).FORM 1
MCCB 200A 3P 1(20x5)
8. ENCLOSURE SHALL BE : WELLDED TYPE. DROPPERS BUS BAR
BOTTOM VIEW 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET. CUBICAL 02 1(30x5)

REVISION GENERTAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 22.03.2018
REV. DATE DESCRIPTION OF MODIFICATION BY LABOUR COLONY MAIN(FEEDER PILLAR)

CLIENT NASEEM TEXTILE MILLS CHECKED BY S.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A
PEC QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A
00 SHEET NO 17 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
LABOUR COLONY SUB DB

200

400

200

400

200

400
300

500

600

300

500

600

300

500

600
100

100

100

100
150
0

0
900
900 900 900
LABEL
800
800 LIVE PHASE 800 800
R Y B
CAPS LOCK
700
700 700 700
8888 8888
600
600 A/M V/M 600 600 O/G MCB SP 10A

500
500 500 500
A.S.S V.S.S

400
400 400 400

C.T C.T C.T 300


300 300 300
CAPS LOCK
F1~F3

DOOR 200
200 EARTHING 200 EZC 100F
200 EZC 100F

Schneider
Electric
Earth CU. (15x3)

I/C Neutral CU. (15x3) 100


100 100 100 MCCB 100A

0
0 0 0

EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW


WITH SHROUDING SHEET WITHOUT SHROUDING SHEET

NOTE:
200

400
300

500

600
100
0

1. ALL DIMENSIONS ARE IN MM.


150 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
100
CABLING AREA 3.
3. PAINT OF ENCLOSURE SHOULD BE 7035.
QTY: 08 NOS
0
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
TOP & BOTTOM VIEW 7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
PHASE DISTRIBUTION BOARD

8. ENCLOSURE SHALL BE : WELDED TYPE. RED YELLOW BLUE


9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. 10Ax4 (SP) 10Ax3 (SP) 10Ax3 (SP)
10. COPPER TINED. 20Ax1 (SP) 20Ax1 (SP)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LABOUR COLONY SUB DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 08
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 18 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
LABOUR COLONY SUB DB

200

400

200

400

200

400
300

500

600

700

300

500

600

700

300

500

600

700
100

100

100

100

175
0

0
800
800 800 800
LABEL
LIVE PHASE
700
700 R Y B 700 700

600
600 600 600 C.T O/G MCB 16A X 10
8888 8888 C.T C.T

A/M V/M 500


500 500 500

400
400 400 400
A.S.S V.S.S
O/G MCB 100A X 5
CAPS LOCK F1~F3
EZC 250F EZC 250F
300
300 300 300

DOOR 200
200 EARTHING 200 200 Neutral CU. (30x3)

Earth CU. (15x3)


100
100 100 100 I/C MCCB 200A

0
0 0 0

EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW


WITH SHROUDING SHEET WITHOUT SHROUDING SHEET
700
200

400

600
300

500
100

NOTE:
0

1. ALL DIMENSIONS ARE IN MM.


175
2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
100
CABLING AREA 3.

0
3.
4.
PAINT OF ENCLOSURE SHOULD BE 7035.
INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
QTY: 02 NOS
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS. PHASE DISTRIBUTION BOARD
TOP & BOTTOM VIEW 7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
8. ENCLOSURE SHALL BE : WELDED TYPE. RED YELLOW BLUE
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. 20Ax3 (SP) 20Ax3 (SP) 20Ax3 (SP)
10. COPPER TINED. 10Ax1 (SP) 10Ax1 (SP) 10Ax1 (SP)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY LABOUR COLONY SUB DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 02
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 19 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
SENIOR&GUEST HOUSE(FEEDER PILLAR)

R Y B R Y B

8888 8888
P/M P/M

8888 8888 8888 8888


EZC 250F EZC 250F EZC 250F EZC 250F

A/M V/M A/M V/M C.T C.T

C.T

A.S.S V.S.S A.S.S V.S.S

C.T
O/G MCCB O/G MCCB O/G MCCB O/G MCCB
GLASS 150A 150A 150A 150A

WINDOW F1~F3 F1~F3


EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F EZC 100F
1500

1500

1500
Schneider Schneider Schneider Schneider Schneider Schneider
Electric Electric Electric Electric Electric Electric

NSX 400-630A NSX 400-630A


1600

1600

1600
Schneider O/G MCCB 100A X 3 Schneider O/G MCCB 100A X 3
Electric Electric

DOOR LOCK DOOR LOCK

I/C 400A EZC 100F EZC 100F EZC 100F


I/C 400A EZC 100F EZC 100F EZC 100F

Schneider Schneider Schneider Schneider Schneider Schneider


Electric Electric Electric Electric Electric Electric

O/G MCCB 60A X 3 O/G MCCB 60A X 3


DOOR POCKET

N N N N

PE PE PE PE

DOOR DOOR
EARTHING EARTHING
100

100

100
400 600 400 600 400 600 400
CUBICAL -01 CUBICAL -02 CUBICAL -01 CUBICAL -02 CUBICAL -01 CUBICAL -02
1000 1000 1000
SIDE VIEW
EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW
WITH METERING DOOR WITHOUT METERING DOOR

NOTE:
1000
1. ALL DIMENSIONS ARE IN MM.
400 600
2. ENCLOSURE SHALL BE WITH 14SWG MS. SHEET.
QTY: 01 NOS
COPPER SIZES
3. PAINT OF ENCLOSURE SHOULD BE 7035 OUTDOOR PAINT. 1(30x5)
MAIN BUS BAR 400A
4. NEUTRAL BUS BAR 1(20x5)
400

5. ALL INCOMING & OUTGOING CABLES SHALL BE FROM BOTTOM. EARTH BUS BAR 1(20x5)
6. PANELS SHALL BE FRONT & REAR ACCESS. INTERCONNECTION
MCCB 400A 3P 1(30x5)
7. PROTECTION CLASS IP65 (INDOOR TYPE FLOOR STANDING).FORM 1 MCCB 150A 3P 1(20x5)
8. ENCLOSURE SHALL BE : WELLDED TYPE. DROPPERS BUS BAR
BOTTOM VIEW 9. LIVE PARTS COVERED WITH THE PROTECTION SHEET. CUBICAL 02 1(30x5)

REVISION GENERTAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 22.03.2018
REV. DATE DESCRIPTION OF MODIFICATION BY SENIOR&GUEST HOUSE(FEEDER PILLAR)

CLIENT NASEEM TEXTILE MILLS CHECKED BY S.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A
PEC QTY 08
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REV04
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A
00 SHEET NO 20 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
A BLOCK STAFF

200

400

200

400

200

400
300

500

600

300

500

600

300

500

600
100

100

100

100
150
0

0
900
900 900 900
LABEL
800
800 LIVE PHASE 800 800
R Y B
CAPS LOCK
700
700 700 700
8888 8888
600
600 A/M V/M 600 600
O/G MCB 63A
C.T 500
500 500 500
A.S.S V.S.S
C.T C.T

400
400 400 400

F1~F3 300
300 300 EZC 250F
300 EZC 250F

CAPS LOCK

Earth
Neutral
DOOR 200
200 EARTHING 200 200

CU. (15x3)
CU. (15x3)
100
100 100 100
I/C MCCB 200A
0
0 0 0

EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW


WITH SHROUDING SHEET WITHOUT SHROUDING SHEET

NOTE:
200

400
300

500

600
100
0

1. ALL DIMENSIONS ARE IN MM.


150 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
100
CABLING AREA 3.
3. PAINT OF ENCLOSURE SHOULD BE 7035.
QTY: 01 NOS
0
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
TOP & BOTTOM VIEW 7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B. PHASE DISTRIBUTION BOARD
8. ENCLOSURE SHALL BE : WELDED TYPE.
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. RED YELLOW BLUE
10. COPPER TINED. 63Ax3 (SP) 63Ax2 (SP) 63Ax2 (SP)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY A BLOCK STAFF

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 21 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
B BLOCK STAFF

200

400

200

400

200

400
300

500

600

300

500

600

300

500

600
100

100

100

100
150
0

0
900
900 900 900
LABEL
800
800 LIVE PHASE 800 800
R Y B
CAPS LOCK
700
700 700 700
8888 8888
600
600 A/M V/M 600 600
O/G MCB 63A

C.T 500
500 500 500
A.S.S V.S.S
C.T C.T

400
400 400 400

F1~F3 300
300 300 EZC 250F
300 EZC 250F

CAPS LOCK

Earth
Neutral
DOOR 200
200 EARTHING 200 200

CU. (15x3)
CU. (15x3)
100
100 100 100
I/C MCCB 150A
0
0 0 0

EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW


WITH SHROUDING SHEET WITHOUT SHROUDING SHEET
200

400
300

500

600
100
0

NOTE:
150 1. ALL DIMENSIONS ARE IN MM.
100
CABLING AREA 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
3.
3. PAINT OF ENCLOSURE SHOULD BE 7035.
QTY: 01 NOS
0

4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.


TOP & BOTTOM VIEW 6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS. PHASE DISTRIBUTION BOARD
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
8. ENCLOSURE SHALL BE : WELDED TYPE. RED YELLOW BLUE
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. 63Ax3 (SP) 63Ax2 (SP) 63Ax2 (SP)
10. COPPER TINED.

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY B BLOCK STAFF

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 22 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
C BLOCK STAFF

200

400

200

400

200

400
300

500

600

300

500

600

300

500

600
100

100

100

100
150
0

0
900
900 900 900
LABEL
800
800 LIVE PHASE 800 800
R Y B
CAPS LOCK
700
700 700 700
8888 8888
600
600 A/M V/M 600 600 O/G MCB SP 40A X 13

500
500 500 500
A.S.S V.S.S

400
400 400 400
C.T C.T C.T

300
300 300 300
CAPS LOCK F1~F3

DOOR
EZC 100F EZC 100F

200
200 EARTHING 200 200 Schneider
Electric

I/C Earth CU. (15x3)


MCCB 100A 100
Neutral CU. (15x3)
100 100 100

0
0 0 0

INTERNAL VIEW INTERNAL VIEW SIDE VIEW


EXTERNAL VIEW
WITH SHROUDING SHEET WITHOUT SHROUDING SHEET

NOTE:
200

400
300

500

600
100
0

1. ALL DIMENSIONS ARE IN MM.


150
2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
100
CABLING AREA 3.
3. PAINT OF ENCLOSURE SHOULD BE 7035.
QTY: 01 NOS
0
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
TOP & BOTTOM VIEW 7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B. PHASE DISTRIBUTION BOARD
8. ENCLOSURE SHALL BE : WELDED TYPE.
RED YELLOW BLUE
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET.
10. COPPER TINED. 10Ax4 (SP) 10Ax3 (SP) 10Ax3 (SP)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY C BLOCK STAFF

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 23 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
GM HOUSE DB

200

400

200

400

200

400
300

500

600

700

800

300

500

600

700

800

300

500

600

700

800
100

100

100

100

175
0

0
1000 1000 1000
1000
Earth CU. (15x3)
LABEL
LIVE PHASE NEUTRAL FOR UPS CU. (15x3)
900 R Y B 900 900
900
Neutral CU. (30x3)

800 800 800


CAPS LOCK 800
8888 8888
A/M V/M R1
MCB TP O/G MCB 16A X 10
700 700 700
700
C.T
600 600 600 O/G UPS MCB 16A X 5
A.S.S V.S.S
C.T C.T 600

O/G MCB DP 20A & 32A X 7


500 500 500 Timer

500
F1~F3
400 400 400

G
EZC 250F EZC 250F
UV/OV Relay
400

300 300

I N 300 H.R.C FUSE


300

200
CAPS LOCK
DOOR
EARTHING 200

UR 200
SPD FP

200

T
I/C MCCB 200A

AC
100 100 100
100

0 0

U F
INTERNAL VIEW
0

INTERNAL VIEW
0

WITH N
EXTERNAL VIEW SIDE VIEW

M A SHROUDING SHEET WITHOUT SHROUDING SHEET

D Y
NOTE:
A
400

700

800
200

300

500

600
100

E
0

1. ALL DIMENSIONS ARE IN MM.


175
L R 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
100

0
CABLING AREA
A 3.
3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
TOP & BOTTOM VIEW
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
QTY: 01 NOS
8. ENCLOSURE SHALL BE : WELDED TYPE.
PHASE DISTRIBUTION BOARD
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. RED YELLOW BLUE
10. COPPER TINED. 16Ax3 (SP) 16Ax3 (SP) 16Ax4 (SP)
16Ax2 (SP) 16Ax2 (SP) 16Ax1 (SP)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY GM HOUSE DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 24 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
GUEST HOUSE DB

200

400

200

400

200

400
300

500

600

700

800

300

500

600

700

800

300

500

600

700

800
100

100

100

100

175
0

0
1000 1000 1000
1000
LABEL Earth CU. (15x3)

LIVE PHASE
900 R Y B 900 900 NEUTRAL FOR UPS CU. (15x3)
900
Neutral CU. (30x3)

800 800 800


CAPS LOCK 800
8888 8888
A/M V/M
700 700 700
O/G MCB DP 20A & 32A X 10 MCB TP
700
C.T
600 600 600
A.S.S V.S.S
C.T C.T 600

500 500 500


500
R1 Timer

F1~F3

G
400 400 EZC 250F 400 EZC 250F

400
UV/OV Relay

N
O/G & UPS MCB 16A X 14

300
CAPS LOCK
300

R I 300 H.R.C FUSE

SPD FP
300

U
DOOR
200 EARTHING 200 200
200

100 100
C T 100
I/C MCCB 200A

100

0 0
F A 0
0

EXTERNAL VIEW
WITH N
U
INTERNAL VIEW INTERNAL VIEW
SIDE VIEW

M A SHROUDING SHEET WITHOUT SHROUDING SHEET

DNOTE: Y
A 1. ALL DIMENSIONS ARE IN MM.
400

700

800
200

300

500

600
100

E
0

175
L R 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
100
CABLING AREA A 3.
0
3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
TOP & BOTTOM VIEW
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
QTY: 01 NOS
8. ENCLOSURE SHALL BE : WELDED TYPE. PHASE DISTRIBUTION BOARD
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. RED YELLOW BLUE
10. COPPER TINED. 16Ax3 (SP) 16Ax3 (SP) 16Ax3 (SP)
16Ax2 (SP) 16Ax2 (SP) 16Ax1 (SP)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY GUEST HOUSE DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 25 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
MAIN SB HOUSE DB

200

400

200

400

200

400
300

500

600

700

800

300

500

600

700

800

300

500

600

700

800
100

100

100

100

175
0

0
1000 1000 1000
1000
LABEL
LIVE PHASE
900 R Y B 900 900
900

800 800 800


CAPS LOCK 800
8888 8888
A/M V/M
700 700 700 Earth CU. (15x3)
700
C.T NEUTRAL FOR UPS CU. (15x3)
600 600 600
A.S.S V.S.S
C.T C.T 600
Neutral CU. (30x3)

500 500 500


500

400 400 EZC 250F 400 EZC 250F

R1 MCB TP
O/G MCB 16A X 10
400
F1~F3
300 300 300
O/G UPS MCB 16A X 5 300
CAPS LOCK
DOOR
200 EARTHING 200 200 O/G MCB DP 20A & 32A X 7

I/C MCCB 200A


Timer 200

100 100 100


UV/OV Relay 100

0 0 0
0

INTERNAL VIEW INTERNAL VIEW


EXTERNAL VIEW SIDE VIEW
WITH SHROUDING SHEET WITHOUT SHROUDING SHEET

NOTE:
400

700

800
200

300

500

600
100
0

1. ALL DIMENSIONS ARE IN MM.


175 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
100
CABLING AREA 3.
0
3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
TOP & BOTTOM VIEW
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
QTY: 01 NOS
8. ENCLOSURE SHALL BE : WELDED TYPE.
PHASE DISTRIBUTION BOARD
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. RED YELLOW BLUE
10. COPPER TINED. 16Ax3 (SP) 16Ax3 (SP) 16Ax4 (SP)
16Ax2 (SP) 16Ax2 (SP) 16Ax1 (SP)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY MAIN SB HOUSE DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 26 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
BLOCK A BOXES

200

400

200

400

200

400
300

500

600

300

500

600

300

500

600
100

100

100
0

100
150
0
700 700 700 700
LABEL

600 LIVE PHASE 600 600 600


R Y B

500 500 500 500


O/G MCB 20A
CAPS LOCK C.T
400 400 400 400
C.T C.T

300 300 300 300


O/G MCB 20A
DOOR
200 EARTHING 200 200 200
EZC 100F EZC 100F

Schneider
Earth CU. (15x3)
Electric

F1~F3
Neutral CU. (15x3)
100 100 100 I/C
100
MCCB 60A

0 0 0 0

EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW


WITH SHROUDING SHEET WITHOUT SHROUDING SHEET
200

400
300

500

600
100
0

NOTE:
150 1. ALL DIMENSIONS ARE IN MM.
100
CABLING AREA 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
3.
0
3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
TOP & BOTTOM VIEW 6.
7.
DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
QTY: 06 NOS
COPPER SIZES
8. ENCLOSURE SHALL BE : WELDED TYPE.
MAIN BUS BAR 63A 1(15x3)
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET.
NEUTRAL BUS BAR 1(15x3)
10. COPPER TINED.
EARTH BUS BAR 1(15x3)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY BLOCK A BOXES

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 06
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 27 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
BLOCK B BOXES

200

400

200

400

200

400
300

500

600

300

500

600

300

500

600
100

100

100
0

100
150
0
700 700 700 700
LABEL

600 LIVE PHASE 600 600 600


R Y B

500 500 500 500


O/G MCB 20A
CAPS LOCK C.T
400 400 400 400
C.T C.T

300 300 300 300


O/G MCB 20A
DOOR F1~F3
200 EARTHING 200 200 200
EZC 100F EZC 100F

Schneider
Earth CU. (15x3)
Electric

Neutral CU. (15x3)


100 100 100 I/C
100
MCCB 50A

0 0 0 0

EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW


WITH SHROUDING SHEET WITHOUT SHROUDING SHEET
200

400
300

500

600
100
0

NOTE:
150 1. ALL DIMENSIONS ARE IN MM.
100
CABLING AREA 2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
3.
0
3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
TOP & BOTTOM VIEW 6.
7.
DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B.
QTY: 06 NOS
COPPER SIZES
8. ENCLOSURE SHALL BE : WELDED TYPE.
MAIN BUS BAR 63A 1(15x3)
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET.
NEUTRAL BUS BAR 1(15x3)
10. COPPER TINED.
EARTH BUS BAR 1(15x3)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY BLOCK B BOXES

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 06
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 28 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
BLOCK C BOXES

400
450

400
450

400
450
200

300

200

300

200

300
100

100

100
0

100
150
0
400 400 400 400
BLOCK A BOXES
Neutral Earth

LIVE PHASE

DOOR LOCK
300 R Y B 300 300 300

F1~F3
200 200 200 200
EZC 100F EZC 100F

CAPS LOCK
Schneider
Electric

100 100 100 I/C MCB O/G


20&10A X 5 100
MCCB 50A

0 0 0 0

EXTERNAL VIEW INTERNAL VIEW INTERNAL VIEW


SIDE VIEW
WITH SHROUDING SHEET WITHOUT SHROUDING
400
450
200

300
100
0

NOTE:
1. ALL DIMENSIONS ARE IN MM.
150 2. ENCLOSURE SHALL BE WITH 16SWG MS. SHEET. (STANDARD TOLERANCE LIMITS APPLIED).
100 3. PAINT OF ENCLOSURE SHOULD BE 7035 WHITE TEXTURE PAINT.
CABLING AREA 4.
5. INCOMING BOTTOM & OUTGOING CABLES SHALL BE FROM TOP.
QTY: 12 NOS
0
PHASE DISTRIBUTION BOARD
6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
TOP & BOTTOM VIEW 7. PROTECTION CLASS IP44 (INDOOR CONCEALED TYPE) RED YELLOW BLUE

8. ENCLOSURE SHALL BE : WELDED TYPE. 20Ax3 (SP) 20Ax3 (SP) 20Ax3 (SP)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY BLOCK C BOXES

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 12
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 29 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.
MASJID DB

400

400

400
200

300

500

600

700

200

300

500

600

700

200

300

500

600

700
100

100

100
0

100

175
0
900 900 900 900
LABEL
LIVE PHASE Earth
800 R Y B 800 800 CU. (15x3)
800

700 700 700 Neutral CU. (30x3)


700
8888 8888
CAPS LOCK
A/M V/M
600 600 600 O/G MCB SP 16A & 6A 600

C.T
500 500 500 500
A.S.S V.S.S

C.T C.T

400 400 400 O/G MCB DP 20A&32A X 8 400

300 300 300 300


CAPS LOCK
EZC 100F EZC 100F

DOOR Schneider
Electric

200 EARTHING 200 200 F1~F3


O/G MCB DP 20A X 9 200
I/C 100A

100 100 100 100

0 0 0 0

INTERNAL VIEW INTERNAL VIEW SIDE VIEW


EXTERNAL VIEW
WITH SHROUDING SHEET WITHOUT SHROUDING SHEET
400
200

300

500

600

700
100
0

NOTE:
175
1. ALL DIMENSIONS ARE IN MM.
2. ENCLOSURE SHALL BE WITH 16SWG M.S. SHEET. (STANDARD TOLERANCE LIMITS APPLIED)
100
CABLING AREA 3.
0 3. PAINT OF ENCLOSURE SHOULD BE 7035.
4. INCOMING FROM BOTTOM & OUTGOING CABLES SHALL BE FROM TOP & BOTTOM.
TOP & BOTTOM VIEW 6. DISTRIBUTION BOARDS SHALL BE FRONT ACCESS.
QTY: 01NOS
7. PROTECTION CLASS IP42 (INDOOR CONCEALED TYPE) FORM 1B. PHASE DISTRIBUTION BOARD
8. ENCLOSURE SHALL BE : WELDED TYPE.
9. LIVE PARTS COVERED WITH THE M.S PROTECTION SHEET. RED YELLOW BLUE
10. COPPER TINED. 20Ax3 (SP) 20Ax3 (SP) 20Ax3 (SP)
10Ax1 (SP) 10Ax1 (SP) 10Ax1 (SP)

REVISION GENERAL ARRANGEMENT OF


FOR APPROVAL DESCRIPTION DESIGN BY M.A DRAWN DATE 11.08.2022
REV. DATE DESCRIPTION OF MODIFICATION BY MASJID DB

CLIENT NASEEM TEXTILE MILLS CHECKED BY M.A SCALE N.T.S


T & D (Pvt) Ltd FOR MANUFACTURING PROJECT N/A
C.CHECKED BY S.A QTY 01
104 J-BLOCK Johar Town, Near Mughal Eye Hospital, PROJECT NO GTD-570341221-REVO4
Lahore Pakistan.
SGA-570341221 APPROVED BY M.A.A SHEET NO 30 OF 30
DRAWING NO
Tel: +924235458591-93 Fax: +924235458590 AS BUILT
Web Site: www.greentnd.com E-mail: info@greentnd.com MO NUMBER MO-412311222 REV NO 00
THIS DRAWING IS THE EXCLUSIVE PROPERTY OF (GREEN T&D) AND MAY NOT BE COPIED, EXPLODED, DUPLICATED,REPRODUCED TO THE THIRD PARTY IN ANY FORM WITHOUT THE PRIOR WRITTEN AUTHORIZATION OF GREEN T&D (PVT) LTD.