Professional Documents
Culture Documents
Tan 2020
Tan 2020
Keywords: In this article, a control method which combines adaptive droop control with adaptive state of charge (SoC)
Battery energy storage system recovery control is proposed for battery energy storage system (BESS) to participate in primary frequency
Primary frequency regulation regulation (PFR), aiming to improve the system frequency dynamics and contribute to the long-term perfor-
Charging demand mance of BESS during PFR. Firstly, based on the frequency operation characteristics of power grid and the
Power system operation
economic operation requirements of BESS, an adaptive droop control function of BESS participating in PFR is
constructed. Secondly, the recovery power of BESS is determined by regarding SoC as feedback signal. Then,
according to the frequency signal of power grid with the operation characteristics of conventional generator
units (CGUs), the limiting coefficient of recovery power for BESS is designed. Furthermore, based on the re-
covery power and the recovery power limit coefficient, the adaptive recovery power of BESS is obtained, which
avoids the negative impact of BESS on the operation of CGUs when restoring SoC. Finally, according to the
adaptive droop control of BESS with the adaptive SoC recovery control, a comprehensive control method is
designed to maintain the proper SoC during the whole operation of BESS, which indirectly reduces the frequency
adjustment burden of CGUs. The performance of the proposed method is validated through case studies under
conditions of various power variation.
1. Introduction grid.
The frequency is one of the most important indexes to keep stability
With the increasing penetration of renewable energy sources (RESs), for power system. And the primary frequency regulation (PFR) features
the intermittent and difficulty in prediction have brought negative short-term process, fast speed requirement and high priority [14]. Thus
impact on power system stability [1,2]. To ensure the safety of system the BESS is suitable for PFR due to its fast response and relatively small
operation, the measure of the wind and photovoltaic curtailment is installed capacity compared with conventional generator units (CGUs).
often performed, which leads to at least 30% energy loss of RESs every Recently, some problems of BESS application in PFR have attracted the
year [2–4]. The battery energy storage system (BESS) is a good solution attention of experts and provided good solutions, such as the determi-
to reduce the power fluctuation and negative influence exerted by RESs nation of BESS type and location [15,16]; simulation model establish-
[5,6]. Recently, the decrease of cost and technology development of ment [17–19]; BESS control strategy [18–22] and the economic eva-
BESS have attracted much attention on its bulk implementation in luation methods [22,23]. Published literatures have investigated the
power system [7,8]. economic efficiency of BESS participating in PFR [24–28]. The control
As an important equipment to maintain power balance, the BESS is methods of maintaining or restoring SoC have a significant impact on
introduced to the medium and low voltage scenarios (i.e., microgrid the capacity allocation, the benefits of participating in PFR and the
and distribution network) in the early stage. The BESS unit features lifetime of BESS. As the demand for BESS to restore SoC often goes
large power density and fast response speed [9,10]. To reduce the against the demand for frequency regulation of power grid, the SoC
fluctuation of RESs power, the BESS technique is used to compensate recovery control strategies must consider both FR and charging de-
the net power variation between RES sources and local loads in mi- mands. Research on SoC maintaining strategies of BESS combining
crogrid [11,12]. As alternative, the BESS is used to track the high-fre- these two aspects has been largely missing in the literatures.
quency power variation, which is suitable for the low-installed capacity The coordinated control strategy for BESS and CGUs in PFR can be
of BESS [13]. The technology and development in the aforementioned the key for BESS maintaining SoC, which means that the charging and
scenarios can serve as the reference for BESS when deployed in utility discharging power of BESS needs to be aware of the output power state
⁎
Corresponding author.
E-mail addresses: tanzhuangxi@hnu.edu.cn (Z. Tan), 903177673@qq.com (X. Li).
https://doi.org/10.1016/j.ijepes.2019.105588
Received 22 April 2019; Received in revised form 20 August 2019; Accepted 30 September 2019
0142-0615/ © 2019 Elsevier Ltd. All rights reserved.
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
2
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
3
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
The BESS operates as a load in power system during recharging, and positive, which means that BESS will discharge in a planned time to
the power reserve of CGUs should be considered carefully to avoid release excess power. But when the SoC of BESS is lower than the ex-
overloading condition. Otherwise, the frequency drop (FD) will affect pected value, the Precharge is negative, then BESS will charge, so as to
the stability of system frequency when there is insufficient reserve achieve the desired SoC.
power of CGUs.
4. Proposed coordinated method for PFR with BESS
3. Existing BESS control method considering charging demands
4.1. Overview of the proposed method
As we discussed earlier, introducing BESS to participate in FR can
enhance the anti-interference ability of power system. However, the There are two operational requirements for BESS to participate in
need to restore SoC must be considered in the actual operation of BESS. primary frequency regulation: (1) to maintain SoC in the reference in-
Therefore, some strategies for considering BESS charging demands have tervals (SoCref); (2) to alleviate the frequency regulation burden of
been developed to deal with such question in [25,26,30,31]. In order to CGUs. It should be noted that the reference intervals of SoC is not fixed.
compare with the proposed method in Section 4, three representative In most researches, SoCref was set as a fixed point (0.5 or 0.7)
recovery SoC strategies of BESS, namely CRP, BSH and CFR, are spe- [22,25,27,30]. However, due to the diversity of SoC in BESS operation,
cially analyzed. the SoC of BESS will not operate at the set point, which leads to the
need for frequent charging and discharging of BESS to correct their SoC,
3.1. Constant recovery power control (CRP) which will shorten the lifetime of BESS, but also bring unstable factors
to the power grid. In order to make full use of the power response
The CRP control [25,26] is used to maintain the residual battery ability of BESS and reduce the number of start-ups for SoC recovery,
energy by recharging with a constant power (5% of rated power or here SoCref is set to 0.45–0.55.
maximum power) when the grid frequency falls into dead band. The two essential factors are the key elements to achieve the above
fundamental purpose. More specifically, BESS should respond on the
Precharge = 0.05Pn (| f | 0.033Hz) (10) basis of the operating status of CGUs. The outline of the proposed
where Precharge and Pn represent the recharging power in dead band and strategy is shown in Fig. 8.
the rated power or maximum power of BESS, respectively.
4.2. Control strategy flow
3.2. Battery SoC holder control (BSH) and charging with FR (CFR)
On the basis of the previous analysis, BESS participation frequency
There is only one difference between the control strategy BSH and regulation strategy and SoC recovery strategy are combined. The in-
CFR [30,31] in response frequency: CFR adds an additional charging tegrated control strategy flow is as shown in Table 1 and Fig. 9. The
power. Therefore, here we briefly introduce the adaptive droop coef- steps of BESS participating in PFR are designed as follows:
ficient of BSH and the droop control loop of CFR.
The calculation and specific results of adaptive charge-discharge (1) According to the dead band setting value of PFR to determine
coefficients in control strategy BSH can be seen in reference [20,30,31]. whether BESS participates in PFR. If BESS does not need to parti-
The characteristic of BSH control strategy is to reduce the discharge cipate in FR, the SoC of BESS is adjusted according to the restora-
power coefficient of BESS when SoC is low, so as to achieve the effect of tion limited power coefficient [i.e. λ(Δf) in Figs. 9 and 12 and Eqs.
maintaining SoC. When SoC is high, the charging power coefficient of (17)–(20)] and the adaptive recovery power of BESS (ΔPRSOC) in the
BESS is reduced (see Fig. 6), which prevents BESS from overcharging. dead band.
Power of BESS is described as (2) When the BESS participates in PFR, the adaptive droop control
(ΔPPFR) is adopted. Then Δf and SoC are obtained as feedback sig-
PBESS = K (SoC )· f | f | 0.033 (11) nals, and the adaptive recovery power is calculated (ΔPRSOC).
The control strategy CFR adds an additional charge power signal Finally, the actual output power of BESS is obtained by combining
based on BSH, as shown in Fig. 7. ΔPPFR and ΔPRSOC.
Additional scheduled charging power (Precharge) may be described as (3) Finally, check whether Δf return to the dead band and SoC recover
rate
to the reference intervals, and determine the deactivation timing of
Precharge = (SoC 0.5)· EBESS /(Tout Tin ) (12) BESS.
where EBESS
rate
, Tout and Tin represent the capacity of BESS, the completion
time of energy storage charging and the start time of charging, re- 4.3. Output power of BESS during PFR
spectively.
When the SoC of BESS is higher than expected, the Precharge is The operational scenario of BESS was divided into two parts, i.e., FR
stage and SoC recovery stage. Therefore, the output power of BESS is
defined as PFR power and SoC recovery power, which is described as
PRSOC (| f | 0.033Hz)
PBESS = PPFR + PRSOC (0.033Hz < | f | 0.1Hz)
PPFR (| f | > 0.1Hz) (13)
where ΔPPFR and ΔPRSOC represent the variable power of BESS parti-
cipating in PFR and the variable power of SoC recovery, respectively.
1) Determination of ΔPPFR: Based on (10), it can be seen that three
different power references of BESS in PFR are designed according to the
state of system frequency. More specifically,
• |Δf| < 0.033 Hz. It suggests that the BESS and CGUs do not need to
Fig. 6. Adaptive droop of the BSH for maintaining the initial SoC. participate in PFR, so BESS can restore SoC in the frequency dead
4
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
band of power grid. The restoring power of BESS cannot make the
frequency fall out of the dead band, otherwise CGUs will frequently
participate in frequency regulation, leading to the increase of me-
chanical and operating cost.
• 0.033 Hz < |Δf| < 0.1 Hz. It suggests that CGUs are involved in Fig. 9. Adaptively coordinated control strategy flow.
FR. Moreover, the reserve power of CGUs for PFR is sufficient.
Consequently, the SoC recovery of BESS can be performed in this
- K d (SoC )· f ( f < 0.033)
frequency intervals.
• |Δf| < 0.1 Hz. It suggests that the residual PFR support power of PPFR = 0 (| f | 0.033)
CGUs is insufficient, leading to the frequency drop with a lower - K c (SoC )· f ( f > 0.033) (14)
nadir. In this case, the activation of SoC recovery will add much
burden on CGUs’ power regulation, and indirectly deteriorate the where Kc and Kd are the adaptive charge and discharge coefficients of
frequency stability. BESS considering SoC, respectively.
Based on the analysis above and previous research (also known as
The PFR power is accordance with the droop principle of frequency BSH control strategy) [20,31], the focus of the strategy is designed to
regulation in power system, and is described as smooth output of BESS when SoC exceeds the limits. Therefore, the SoC
value should be involved in determining the PFR regulation coefficient.
More specifically, the charging and discharging coefficient of BESS
Table 1
Comparison of different scenarios.
|Δf| CGUs state SoC CGUs BESS Characteristics
< 0.033 No PFR demand Normal No action No action Preparing for BESS’s participation in FR
Abnormal No action Recover SoC
< 0.133 Remainder reserve Normal Suppress Δf Suppress Δf Utilizing the complementary advantages of CGUs and BESS
Abnormal Suppress Δf Suppress Δf and Recover SoC Realizing balance between FR task and maintaining SoC of BESS
> 0.133 None reserve Normal Can’t suppress Δf Suppress Δf Relieving power burden of CGUs and stop recovering SoC
Abnormal
5
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
( f > 0.033)
d2
d = (| f | < 0.033)
d1
1 ( f < 0.033) (20)
6
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
Table 2
Model parameters.
Parameter Value Parameter Value
variation.
5. Case studies
7
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
has a great impact on the operation economy of both BESS and CGUs.
And it will not only greatly improve the mechanical loss and operation
and maintenance costs of CGUs, but also will reduce the service life of
BESS and CGUs.
As can be seen from Fig. 17, when the frequency deviation ap-
proaches the dead band boundary, the restoration limited power coef-
ficient (λ) successfully suppresses the recovery power of BESS, that is,
the proposed method stops charging when the frequency deviation
exceeds −0.023 Hz (70%*0.033 Hz). The CRP control strategy will
cause the output power of CGUs to oscillate when the frequency de-
viation is at the dead-zone boundary. That is to say, BESS will con-
tinuously switch between the two tasks of frequency regulation and SoC Fig. 19. Simulation results of Pg variation with double step disturbances.
restoration, and restore the SoC of BESS at a lower speed.
In conclusion, the proposed method not only utilizes the advantages
of CPR strategy, but also improves the shortcomings of CPR to meet the
requirements of BESS and CGUs operating in dead band of power grid which is necessary for the operation of power grid.
frequency deviation. As can be seen from Fig. 19, under the first step disturbance con-
dition, the output power variation of CGUs under the proposed method
5.2. Step load disturbance 2 is 0.0137p.u., while that of CGUs under other methods is about
0.0082p.u. That is to say, compared with other control strategies (CRP,
In order to verify the proposed method will not increase the fre- CFR, BSH), the CGUs provides more FR support power for the proposed
quency regulation burden of CGUs when the system frequency devia- method under the first step disturbance, but less FR support power
tion is large, we set up a step power disturbance with amplitude with under the second step disturbance. However, under the second step
0.01p.u. at 20 s, then a step power disturbance with amplitude of disturbance condition, the situation is opposite. Due to the limitation of
0.02p.u. was set at 120 s. Under this condition, the shortcomings of CFR λ, the proposed method will prevent the recovery of SoC from ab-
and BSH can be clearly demonstrated. sorbing energy to the power grid when the frequency deviation worsens
As shown in Fig. 18, the proposed method and CRP did not cause the further. But the other three strategies do not take this important point
frequency to fall out of the dead band due to the effect of the restoration into account. In addition, it should be highlight that the other control
limited power coefficient (λ) in 0–20 s. In this scenario, the FR effect of strategies could barely provide FR support for CGUs when the SoC of
the proposed method is worse for the first step disturbance of 0.01p.u. BESS deteriorates.
occurred at 20 s, because the residual frequency regulation ability of As can be seen from Fig. 20, in the time scale of 6 min (360 s),
CGUs will be used to restore the SoC of BESS as far as possible without whether it is CRP control method or BSH and CFR control method, SoC
increasing the frequency regulation frequency of CGUs.. According to changes very little under this condition, which means that the energy
Fig. 5, it can be concluded that the residual PFR support capability of exchange between BESS and power grid is also very small. Put it an-
CGUs is sufficient in this frequency deviation state (when the absolute other way, when SoC deteriorates, the CRP, BSH and CFR control
value of frequency deviation is less than 0.1 Hz, CGUs' primary FR re- strategies can neither enable BESS to effectively restore SoC nor enable
serve capacity will be insufficient.). However, when the second step BESS to provide FR support power for power grid. Combining with
disturbance of 0.02p.u. occurred at 120 s, the FR effect of the proposed Figs. 18 and 19, the proposed method sacrifices the effect of FR under
method is much better than that of other control strategies (CRP, CFR, the first small step disturbance, but also utilizes the remaining PFR
BSH). This is because the proposed method will stop the BESS SoC re- support capability of CGUs to restore SoC for BESS. Under the second
covery task when the residual PFR capability of CGUs is insufficient. large step disturbance, the proposed method temporarily sacrifices the
Compared with the control methods of CFR, BSH and CRP, the proposed SoC maintenance effect, but it will greatly reduce the FR burden of
method can consider the operation status of CGUs for SoC recovery, CGUs under these extreme conditions.
In summary, when restoring SoC of BESS, the proposed method
takes into account the operation status of CGUs and BESS in an all-
round way.
Fig.18. Simulation results of frequency variation with double step dis- Fig. 20. Simulation results of SoC variation with double step disturbances.
turbances.
8
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
Table 3
Relevant indexes.
Index ECGUs (MWh) EBESS (MWh) Δfrms SoCref
rms
Fig. 23. Simulation results of output power of CGUs and SoC variation under
region of China was selected, as shown in Fig. 21. Under this condition, continuous load disturbance. (a) Pg variation, (b) SoC variation.
the advantages of the proposed method over other control methods will
be clearly demonstrated.
In order to analyze the dynamic performance of BESS and CGUs
more clearly, the evaluation indexes of FR effects and contribution for worse in the period of 0–140 s and 250–300 s, but the frequency
PFR were considered. The evaluation indexes, presented in Table 3, maintenance effect is better in the period of 140–250 s. The maximum
include the root mean square value of frequency deviation (Δfrms), the frequency deviation under the other three control strategies (CRP, CFR
root mean square error of the SoC and its reference value (SoCref rms ), the and BSH) is 0.1 Hz, while the maximum frequency deviation of the
total contribution energy of the battery storage for PFR (EBESS), the total proposed method is 0.09 Hz. That means the SoC recovery power will
output energy of the CGUs to PFR (ECGUs). be effectively limited when large disturbance occurs in 0–300 s and the
As illustrated in Fig. 22, the FR effect of the proposed method is reserve capacity of PFR of CGUs is insufficient. Then all the control
strategies have almost the same FR effect during the period of
400–700 s. However, after 2300 s, the FR effect of the proposed method
is better than that of other control strategies. To summarize, the FR
effect of proposed method will get better with the increase of time.
As can be seen from Fig. 23, the proposed method makes the total
output power of CGUs change more greatly, but the changes of max-
imum output power of CGUs are the least, during the period of 0–400 s.
Thereafter, the FR power variation of CGUs in the proposed method is
relatively small. The dynamic changes of SoC are clearly shown in
Fig. 23(b). The proposed method only takes about 1000 s to restore SoC
to 0.5, while other methods do not make SoC back to 0.5 in 1 h.
In Table 3, the specific values of the evaluation indicators are pre-
sented. The proposed method shows some advantages in the evaluation
results of various indexes. The root mean square value of frequency
deviation (Δfrms) of the proposed method is 6.56% and 8.06% lower
than that in CRP and CFR control strategy, respectively. The result of
rms under proposed method is 72.8%, 73.5% and 67.9% lower than
SoCref
that under CRP, BSH and CFR control strategy.
The contribution of CGUs with the proposed method is 5.67% and
32.3% lower than that in the CRP and without BESS, respectively,
which implies that the proposed method reduces the frequency reg-
ulation burden of CGUs. Meanwhile, the contribution of BESS with the
proposed method is 78.1% and 84.7% higher than that in the CRP and
CFR control strategy, respectively, which implies that the proposed
method improves the utilization rate of BESS.
In summary, compared with the classical intelligent charging
methods BSH and CFR, the proposed method makes full use of the PFR
reserve capacity and dead band.
9
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
Appendix A
When the reference intervals of SoC are different, the corresponding adaptive output coefficient and adaptive recovery power will change. Here
we give two different case (SoCref ∈ 0.45–0.55 and SoCref ∈ 0.55–0.65) of curve graphics shown in Figs. 24 and 25.
As shown in Figs. 24 and 25, the corresponding SoCref can be selected according to different types of BESS and different operation requirements.
As shown in Figs. 26 and 27, the larger value of n is, the faster function values will change, which means the faster the function changes from
initial value to final value.
Fig. 24. Charging and discharging coefficient of BESS participating in PFR corresponding to different SoCref.
10
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
Fig. 26. Charging and discharging coefficient of BESS participating in PFR corresponding to different n values.
Fig. 27. Recovery power of BESS participating in PFR corresponding to different n values.
References diesel system with a Ni–Cd battery energy storage. Renewable Energy
2010;35:952–65.
[13] Liu B, Zhuo F, Zhu Y, Yi H. System operation and energy management of a re-
[1] Aziz A, Oo AT, Stojcevski A. Analysis of frequency sensitive wind plant penetration newable energy-based DC nano-grid for high penetration depth application. IEEE
effect on load frequency control of hybrid power system. Int J Electr Power Energy Trans Smart Grid 2015;6:1147–55.
Syst 2018;99:603–17. [14] Kundur P. Power system stability and control. New York: Electric Power Research
[2] Ruiz-Rodriguez FJ, Bueno PG, Hernández Jesus C. Stability assessment for trans- Institute, (McGraw-Hill, Inc.); 1994. p. 581–623.
mission systems with large utility-scale photovoltaic units. IET Renew Power Gener [15] Hosseini S, Sarder MD. Development of a Bayesian network model for optimal site
2016;10:584–97. selection of electric vehicle charging station. Int J Electr Power Energy Syst
[3] Nguyen N, Mitra J. An analysis of the effects and dependency of wind power pe- 2019;105:110–22.
netration on system frequency regulation. IEEE Trans Sustainable Energy [16] Świerczyński M, Stroe DI, Stan A, Teodorescu R, Sauer DU. Selection and perfor-
2016;7:354–63. mance-degradation modeling of LiMO/Li Ti O and LiFePO /C battery cells as sui-
[4] Gu Y, Xie L. Fast sensitivity analysis approach to assessing congestion induced wind table energy storage systems for grid integration with wind power plants: An ex-
curtailment. IEEE Trans Power Syst 2014;29:101–10. ample for the primary frequency regulation service. IEEE Trans Sustainable Energy
[5] Abbey C, Li W, Joos G. An online control algorithm for application of a hybrid ESS 2014;5:90–101.
to a wind–diesel system. IEEE Trans Ind Electron 2010;57:3896–904. [17] Zhai Q, Meng K, Dong ZY, Ma J. Modeling and analysis of lithium battery opera-
[6] Peng B, Zhang F, Liang J, Ding L, Liang ZL, Wu QW. Coordinated control strategy for tions in spot and frequency regulation service markets in Australia electricity
the short-term frequency response of a DFIG-ES system based on wind speed zone market. IEEE Trans Ind Inf 2017;13:2576–86.
classification and fuzzy logic control. Int J Electr Power Energy Syst [18] Hernández Jesus C, Bueno PG, Sanchez-Sutil F. Enhanced utility-scale photovoltaic
2019;107:363–78. units with frequency support functions and dynamic grid support for transmission
[7] Chen S, Zhang T, Gooi HB, Masiello RD, Katzenstein W. Penetration rate and ef- systems. IET Renew Power Gener 2017;11:361–72.
fectiveness studies of aggregated BESS for frequency regulation. IEEE Trans Smart [19] Hernández Jesus C, Sanchez-Sutil F, Vidal PG, Rus-Casas C. Primary frequency
Grid 2016;7:167–77. control and dynamic grid support for vehicle-to-grid in transmission systems. Int J
[8] Zidar M, Georgilakis PS, Hatziargyriou ND, Capuder T, Škrlec D. Review of energy Electr Power Energy Syst 2018;100:152–66.
storage allocation in power distribution networks: applications, methods and future [20] Serban I, Marinescu C. Control strategy of three-phase battery energy storage sys-
research. IET Gener Transm Distrib 2016;10:645–52. tems for frequency support in microgrids and with uninterrupted supply of local
[9] Oudalov A, Chartouni D, Ohler C. Optimizing a battery energy storage system for loads. IEEE Trans Power Electron 2014;29:5010–20.
primary frequency control. IEEE Trans Power Syst 2007;22(3):1259–66. [21] Delille G, Francois B, Malarange G. Dynamic frequency control support by energy
[10] He L, Li Y, Guerrero JM, Cao Y. A comprehensive inertial control strategy for hybrid storage to reduce the impact of wind and solar generation on isolated power sys-
AC/DC microgrid with distributed generations. IEEE Trans Smart Grid 2019. tem's inertia. IEEE Trans Sustainable Energy 2012;3:931–9.
https://doi.org/10.1109/TSG.2019.2942736. [22] Knap V, Sinha R, Swierczynski M, Stroe DI, Chaudhary S. Grid inertial response
[11] Feng L, Zhang J, Li G, Zhang BL. Cost reduction of a hybrid energy storage system with Lithium-ion battery energy storage systems. In: 2014 IEEE 23rd international
considering correlation between wind and PV power. Prot Control Modern Power symposium on industrial electronics (ISIE), Istanbul; 2014. p. 1817–22.
Syst 2016;1:1–11. [23] Zhang YJ, Zhao C, Tang W, Tang W, Low S. Profit-maximizing planning and control
[12] Sebastián R, Alzola RP. Effective active power control of a high penetration wind of battery energy storage systems for primary frequency control. IEEE Trans Smart
11
Z. Tan, et al. Electrical Power and Energy Systems 117 (2020) 105588
Grid 2018;9:712–23. [28] Stroe D, Knap V, Swierczynski M, Stroe A, Teodorescu R. Operation of a grid-con-
[24] Vargas LS, Bustosturu G, Larrain F. Wind power curtailment and energy storage in nected Lithium-Ion battery energy storage System for primary frequency regulation:
transmission congestion management considering power plants ramp rates. IEEE A battery lifetime perspective. IEEE Trans Ind Appl 2017;53:430–8.
Trans Power Syst 2015;30:2498–506. [29] Ota Y, Taniguchi H, Nakajima T, Liyanage KM, Baba J, Yokoyama A. Autonomous
[25] Mercier P, Cherkaoui R, Oudalov A. Optimizing a battery energy storage system for distributed V2G (Vehicle-to-Grid) satisfying scheduled charging. IEEE Trans Smart
frequency control application in an isolated power system. IEEE Trans Power Syst Grid 2012;3:559–64.
2009;24:1469–77. [30] Li P, Tan Z, Zhou Y, Li C, Li R, Qi XZ. Secondary frequency regulation strategy with
[26] Thorbergsson E, Knap V. Primary frequency regulation with li-ion battery based fuzzy logic method and self-adaptive modification of state of charge. IEEE Access
energy storage system - evaluation and comparison of different control strategies. 2018;6:43575–85.
In: 2013 10th international telecommunications energy conference, smart power [31] Liu H, Hu Z, Song Y, Lin J. Decentralized vehicle-to-grid control for primary fre-
and efficiency, Hamburg, Germany; 2013. p. 1–6. quency regulation considering charging demands. IEEE Trans Power Syst
[27] Jha IS, Sen S, Tiwari M, Singh MK. Control strategy for Frequency Regulation using 2013;28:3480–9.
Battery Energy Storage with optimal utilization. In: 2014 12th IEEE India inter- [32] Bevrani H. Robust power system frequency control. Springer; 2009. p. 19–21.
national conference on power electronics. Kurukshetra, India; 2014. p. 1–4.
12