LEGENDS: NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS


SYMBOL DESCRIPTION QUA.
OTHERWISE SPECIFIED.
91 °
35.5 ADDRESSABLE STANDARD SMOKE DETECTOR
2. ALL EQUIPMENT UTILIZED MUST POSSESS UL LISTING
S
(UL/FM APPROVED) 04 AND/OR FM APPROVAL CERTIFICATIONS TO ENSURE
N
ITS SUITABILITY FOR THE INTENDED PURPOSE.
2C X 1.5 Sq.mm FIRE ARMORED CABLE -
DRAWING NOTE:
1. MANUAL CALL POINT TO BE MOUNTED AT 1100mm.
2. ALARM HORN STROBE TO BE MOUNTED AT 2200mm.
3. LINEAR HEAT DETECTION CABLE TO BE INSTALLED
WITHIN THE ELECTRICAL PIT.

REFERENCE STANDARDS:
1. SAUDI BUILDING CODE - 201.
2. SAUDI BUILDING CODE - 801.
3. NFPA - 72 .

01 02 03 04 05

17340

4335 4335 4335 4335

A
KEY PLAN

2360
LOOP CONTINUOUS
TO GROUND LEVEL

N
69°
35.9
4550 8530
BLOWER BUILDING

S S
7185

AMENDMENTS

4550
9385

00 S.A.P RAJ ISSUED FOR CONSTRUCTION 10/05/24


REV. BY CHK DESCRIPTION DATE

S S

B
COMPANY
LOOP RUNS FROM
GROUND LEVEL

MEZZANINE
2200

FIRE AND LIFE SAFETY CONSULTANT


C

JENSEN
HUGHES

PROJECT JOB NO. 6AAM00019


PROJECT DESCRIPTION

TABUK
INDEPENDENT SEWAGE TREATMENT
1 PLANTS PROJECT(S), SAUDI ARABIA
FIRE DETECTION & ALARM SYSTEM LAYOUT - MEZZANINE FLOOR - BLOWER BUILDING
SCALE 1:50 - DRAWING TITLE

FIRE DETECTION & ALARM SYSTEM


LAYOUT - MEZZANINE FLOOR -
BLOWER BUILDING
SCALE SHEET SIZE SHEET REV.

SCALE 1 : 50 1:50 A1 1-1

DRG.No. FD-BD-002
00
1m 0 1m 5m

You might also like