4 Nos #12 at top

face eq spaced
600

EXTRA STEEL AROUND PIPE

300
1Nos #12 at
each side
OPENING. 175
4 Nos #12 at bottom
#10 rings @ 200 c/c
face eq spaced
c a
#8 @ 150 C/C
at EachFace(H)
d
Details of TB-1 ( 600X 300 )

shorter side wall


250 250 250 b
TB-1 ( 600X 300 )

1000
#8 @ 200 C/C #10 @ 200 C/C #10 @ 200 C/C #8 @ 200 C/C # 12@ 200 C/C #12 @ 200 C/C #10 @ 200 C/C #8 @ 200 C/C
Al through Al through Al through(v) Al through
#10 @ 150 C/C
# 8 @ 150 C/C # 8 @ 150 C/C # 8 @ 150 C/C(H) # 8 @ 150 C/C( H ) # 8 @ 150 C/C
3 Nos #10 ( Vertical) #8 @ 150 C/C
# 8 @ 150 C/C
# 8 @ 150 C/C # 8 @ 150 C/C at EachFace(H)
Hunch 300 X 300

300
#10 @ 200 C/C ( v) through out + #10 @ 200 C/C ( v) through out + #12 @ 200 C/C ( v) through - #12 @ 200 C/C ( v) through out + #10 @ 200 C/C ( v) through out +
#10 @ 200 C/C ( v) extra from #10 @ 200 C/C ( v) extra from out + #10 @ 200 C/C ( v) extra #10 @ 200 C/C ( v) extra from #10 @ 200 C/C ( v) extra from
base to 1000 ht base to 1000 ht from base to 1500 ht base to 1500 ht base to 1000 ht
1000

250

1500
b
#10 @ 175 C/C #10 @ 175 C/C d
450 450 450 450
both way mesh both way mesh c
a
Longer Side Wall
225

225
300 1500
200

200
#10 @ 175 C/C #10 @ 175 C/C
250 both way mesh 250 both way mesh WALL CORNERS DETAIL ( TYP)
# 10 @ 150 C/C
# 10 @ 150 C/C both ways WITH CORNER HAUNCH
both ways
vertical rods not mentioned here for
clarity. for that ref relevant section

REINF. DETAILS AT SECTION 1-1 REINF. DETAILS AT SECTION 2-2

BASE SLAB MESH STEEL

SLAB THK.
300
15240
2545 2540 2540 2540 2540 2540

200
100 thk P.C.C
CONTRACTOR
250 TANTIA - VOLTAS (J.V)
BASE SLAB MESH STEEL
DD - 30, SECTOR - 1, SALT LAKE CITY
KOLKATA - 700064, INDIA
2060

800 PROJECT
5 Nos- # 12 ( v ) JICA Assisted Odisha Integrated Sanitation Improvement Project
800
2060

# 8 @ 150 C/C
OWNER
AS PER SECTION

Q Q ODISHA WATER SUPPLY & SEWERAGE BOARD


8240
2060

CONSULTANT
300 DIA PILES
ENGINEERING & PROJECT MANAGEMENT CONSULTANT
(Consortium of Tokoy Engineering Consultants Co. Ltd. Tech. Inc
300 Ø
and Egls bceom International)
5 Nos- # 12 ( v )
TITLE:
2060

GA AND STRUCTURAL DETAILS OF STILLING BASIN


#8 @ 150 C/C NEAR KHANNAGAR PUMPING STATION CUTTACK.
100 COVER

SECTION - Q-Q DRG. NO. 2013 / PJ-633/ PS-2/ C-05 ( SHEET -2)

PILE FOUNDATION LAYOUT PLAN 300 Ø


SCALE DATE CHECKED APPVD. REV.NO SHEET NO
REINF. DETAIL PILE 20.03.2022 2/2
WITH BASE SLAB