NEAR MISS INCIDENT/ DANGEROUS OCCURRENCE SUGGESTED PROFORMA

 Near Miss : Human injury escaped & no damage to property, equipment or interruption to work
 Dangerous Occurrence: Damage to property, equipment or interruption of work, but not resulting in
personal injury/illness. E.g. fire incident, collapse of structure, crane failure etc.

Report No: 03

Name of site: Revival of Ramagundam, Telengana Date: 13/06/2020

Name of work: Electrical works Contractor:

Incident reported by : EIL

Date and time of Incident : 13/06/2020, 07.15PM

Location : Near Switch Yard

Brief Description of Incident: A flash over incident happened on 13/06/2020 at 07.15 PM near switch
Yard. The 3Phase 440 Volts, temporary power cable to storm water reservoir pumps from SS#1
(PCC 1301) might have damaged and got minor punctures at the half way due to the nearby site
grading/paving works and resulted in a flash over, when the rain water ingressed in to the already
damaged cable.

Probable cause of Incident: Electrical protection devices are not functioning/tripped in the source
location.
The cable laid above the ground and further damages during the grading and pavement works

Suggested corrective action: Cable shall be routed properly as per the Standards/Specification.
Inspection shall be done on regular basis and ensure that the cables as well as the protection devices
are defect free.
Electrical permit system shall be followed religiously.

Steps taken to avoid recurrence: Yes x No

To : Owner

: RCM/Site-in-charge EIL (3 copies)

Divisional Head (Constn) through RCM

Project Manager, EIL, through RCM