LC 231
Dual pump unit
Table of contents
English (GB)
Installation and operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Български (BG)
Упътване за монтаж и експлоатация. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Čeština (CZ)
Montážní a provozní návod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Deutsch (DE)
Montage- und Betriebsanleitung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Dansk (DK)
Monterings- og driftsinstruktion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Eesti (EE)
Paigaldus- ja kasutusjuhend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Español (ES)
Instrucciones de instalación y funcionamiento . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Suomi (FI)
Asennus- ja käyttöohjeet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Français (FR)
Notice d'installation et de fonctionnement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Ελληνικά (GR)
Οδηγίες εγκατάστασης και λειτουργίας . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Hrvatski (HR)
Montažne i pogonske upute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Magyar (HU)
Telepítési és üzemeltetési utasítás. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Italiano (IT)
Istruzioni di installazione e funzionamento . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Lietuviškai (LT)
Įrengimo ir naudojimo instrukcija . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
Latviešu (LV)
Uzstādīšanas un ekspluatācijas instrukcija . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
Nederlands (NL)
Installatie- en bedieningsinstructies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Polski (PL)
Instrukcja montażu i eksploatacji . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Português (PT)
Instruções de instalação e funcionamento . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
Română (RO)
Instrucţiuni de instalare şi utilizare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 384
Srpski (RS)
Uputstvo za instalaciju i rad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 405
Svenska (SE)
Monterings- och driftsinstruktion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
Slovensko (SI)
Navodila za montažo in obratovanje . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 445
Türkçe (TR)
Montaj ve kullanım kılavuzu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 466
3
Українська (UA)
Table of contents
4 LC 231
English (GB) Installation and operating instructions
English (GB)
Original installation and operating instructions 8.4 Code 9 (Power phase sequence wrong). . . . . . . . . . . . 20
Table of contents 8.5 Code 12 (Service needed) . . . . . . . . . . . . . . . . . . . . 20
8.6 Code 22 (Moisture in motor of pump) . . . . . . . . . . . . . 20
1. General information . . . . . . . . . . . . . . . . . . . . . . . . 5 8.7 Code 25 (Wrong configuration) . . . . . . . . . . . . . . . . . 20
1.1 Hazard statements . . . . . . . . . . . . . . . . . . . . . . . . . . 5 8.8 Code 26 (Contactor shorted). . . . . . . . . . . . . . . . . . . 20
1.2 Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 8.9 Code 48 (Motor is overloaded) . . . . . . . . . . . . . . . . . 20
2. Installing the product . . . . . . . . . . . . . . . . . . . . . . .6 8.10 Code 51 (Blocked) . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.1 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 8.11 Code 56 (Underload, current sensor measures a value
2.2 Mechanical installation . . . . . . . . . . . . . . . . . . . . . . .6 too low). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.3 Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . .8 8.12 Code 57 (Missing water in the application) . . . . . . . . . . 21
8.13 Code 69 (Winding temperature too high) . . . . . . . . . . . 21
3. Starting up the product . . . . . . . . . . . . . . . . . . . . . 11 8.14 Code 72 (Internal fault) . . . . . . . . . . . . . . . . . . . . . . 21
3.1 Connecting to Grundfos GO Remote . . . . . . . . . . . . . . 11 8.15 Code 76 (Internal fault) . . . . . . . . . . . . . . . . . . . . . . 21
3.2 Startup wizard on Grundfos GO Remote . . . . . . . . . . . 11 8.16 Code 84 (Memory storage media faulty) . . . . . . . . . . . . 21
3.3 Startup wizard on the operating panel . . . . . . . . . . . . . 11 8.17 Code 85 (Internal fault) . . . . . . . . . . . . . . . . . . . . . . 22
3.4 How to enable Bluetooth on the operating panel . . . . . . . 11 8.18 Code 117 (Door opened) . . . . . . . . . . . . . . . . . . . . . 22
3.5 How to disable Bluetooth on the operating panel . . . . . . 12 8.19 Code 157 (Real-time clock monitoring) . . . . . . . . . . . . 22
3.6 Configuring the IO terminals using Grundfos GO 8.20 Code 159 (Communication error CIMxxx) . . . . . . . . . . . 22
Remote. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8.21 Code 163 (Motor-drive protection function
3.7 Testing the product. . . . . . . . . . . . . . . . . . . . . . . . . 12 measurement fault) . . . . . . . . . . . . . . . . . . . . . . . . 22
4. Product introduction. . . . . . . . . . . . . . . . . . . . . . . 12 8.22 Code 165 (Signal fault) . . . . . . . . . . . . . . . . . . . . . . 22
4.1 Product description . . . . . . . . . . . . . . . . . . . . . . . . 12 8.23 Code 181 (Signal fault, PTC input) . . . . . . . . . . . . . . . 22
4.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 8.24 Code 191 (High water level) . . . . . . . . . . . . . . . . . . . 23
4.3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 8.25 Code 205 (Level switch inconsistency) . . . . . . . . . . . . 23
4.4 Application types . . . . . . . . . . . . . . . . . . . . . . . . . . 12 8.26 Code 220 (Contactor wear out) . . . . . . . . . . . . . . . . . 23
4.5 Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8.27 Code 229 (Water on floor) . . . . . . . . . . . . . . . . . . . . 23
4.6 Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 9. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.7 Supported communication interface modules and 9.1 Electrical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
9.2 Mechanical data . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5. Control functions . . . . . . . . . . . . . . . . . . . . . . . . . 14 9.3 Environmental data . . . . . . . . . . . . . . . . . . . . . . . . 24
5.1 Operating panel . . . . . . . . . . . . . . . . . . . . . . . . . . 14 9.4 Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6. Setting the product. . . . . . . . . . . . . . . . . . . . . . . . 15 10. Disposing of the product . . . . . . . . . . . . . . . . . . . . 24
6.1 Setting the application type with Grundfos GO Remote. . . 15
11. Document quality feedback . . . . . . . . . . . . . . . . . . 24
6.2 Setting the sensor type . . . . . . . . . . . . . . . . . . . . . . 15
6.3 Setting the start level . . . . . . . . . . . . . . . . . . . . . . . 15
6.4 Setting the stop level . . . . . . . . . . . . . . . . . . . . . . . 15 1. General information
6.5 Setting the high level . . . . . . . . . . . . . . . . . . . . . . . 16 Read this document before you install the product.
6.6 After-run delay, high level. . . . . . . . . . . . . . . . . . . . . 16 Installation and operation must comply with local
6.7 Stop delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 regulations and accepted codes of good practice.
6.8 Power-on delay . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.9 Dry-running protection. . . . . . . . . . . . . . . . . . . . . . . 16 1.1 Hazard statements
6.10 Using the same level switch for the start and stop level . . 16
The symbols and hazard statements below may appear in Grundfos
6.11 Multipump settings . . . . . . . . . . . . . . . . . . . . . . . . . 16 installation and operating instructions, safety instructions and
6.12 Antiseizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 service instructions.
6.13 Signal-detection time . . . . . . . . . . . . . . . . . . . . . . . 16
DANGER
6.14 Setting the maximum number of restarts with Grundfos
GO Remote . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Indicates a hazardous situation which, if not avoided, will
result in death or serious personal injury.
6.15 Setting the service interval with Grundfos GO Remote . . . 17
6.16 Operating the product . . . . . . . . . . . . . . . . . . . . . . . 17 WARNING
6.17 Motor protection . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Indicates a hazardous situation which, if not avoided,
6.18 Alarm reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 could result in death or serious personal injury.
6.19 Setting the buzzer with Grundfos GO Remote . . . . . . . . 18
6.20 Setting units for Grundfos GO Remote. . . . . . . . . . . . . 18 CAUTION
6.21 Setting units for the operating panel with Grundfos GO Indicates a hazardous situation which, if not avoided,
Remote. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 could result in minor or moderate personal injury.
6.22 GENIbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
The hazard statements are structured in the following way:
6.23 Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.24 Starting the startup wizard with the operating panel . . . . . 19 SIGNAL WORD
Description of the hazard
7. Servicing the product . . . . . . . . . . . . . . . . . . . . . . 19
Consequence of ignoring the warning
7.1 Updating the product software . . . . . . . . . . . . . . . . . . 19
7.2 Replacing the battery . . . . . . . . . . . . . . . . . . . . . . . 19 • Action to avoid the hazard.
7.3 Replacing the CIM module . . . . . . . . . . . . . . . . . . . . 19
1.2 Notes
8. Fault finding the product . . . . . . . . . . . . . . . . . . . . 19
The symbols and notes below may appear in Grundfos installation
8.1 Overview of alarm and warning codes . . . . . . . . . . . . . 19
and operating instructions, safety instructions and service
8.2 Code 2 (Power phase missing) . . . . . . . . . . . . . . . . . 20 instructions.
8.3 Code 4 (Too many motor restarts) . . . . . . . . . . . . . . . 20
5
English (GB)
Place the front cover above the control unit, if possible. This
A blue or grey circle with a white graphical symbol way, you do not need to remove the flat cable between the front
indicates that an action must be taken. cover and the control unit.
1. Loosen the screws.
A red or grey circle with a diagonal bar, possibly with a 2. Carefully separate the front cover from the back cover.
black graphical symbol, indicates that an action must not
Be careful not to damage the cable connecting the front cover
be taken or must be stopped.
and the back cover.
3. Place the front cover above the back cover on the support
If these instructions are not observed, it may result in
brackets.
malfunction or damage to the equipment.
4. To ensure that the front cover does not tilt, insert the two bottom
screws into the open holes at the top of the back cover.
Tips and advice that make the work easier.
2.1 Location
Install the product in a location that meets the following
requirements:
• Place the product in a flood-safe place.
• Make sure that the ambient temperature is within the limits.
• Install the product as close as possible to the connected pumps,
sensors, and accessories.
• The product must be protected from direct sunlight.
• The product must be easily accessible.
• We recommend that you install the product in a protective shed
or enclosure to avoid direct sunlight and rain.
• Indoor installation: The product must be installed in a well-
TM071322
ventilated room to ensure cooling of its components.
Related information
TM074473
If you need to remove the front cover completely, you must remove
the flat cable between the front cover and the back cover.
Related information
2.3.3 Connecting the pump supply and power supply
2.2.2 Removing the front cover
The front cover must be removed to make any connections or to
install the Communication Interface Module (CIM).
6
3. Pull out the flat cable that is connected to the circuit board. Do
English (GB)
not remove the flat cable from the front cover.
TM071323
165 (6.5")
TM070121
Related information
2.2.2 Removing the front cover
7
2.2.5 Installing a communication interface module 2.3 Electrical connection
English (GB)
You can fit a communication interface module (CIM) in the control 2.3.1 Cable requirements
unit to enable communication with external systems. The module is
optional and is not delivered with the product. See the installation WARNING
and operating instruction for the module regarding electrical Electric shock
connections. Death or serious personal injury
‐ The wires from the pump phases must be rated at 90
Use an antistatic service kit when handling electronic
°C (194 °F).
components. This prevents static electricity from
damaging the components. ‐ The wires from the temperature sensor, if any, must be
rated at 480 V and 70 °C (158 °F).
1. Loosen the screws and remove the front cover.
Be careful not to damage the cable between the front cover and
For the US market only, use flexible metal conduits
the back cover.
(FMC).
2. Push the module onto the three guide pins and into the socket.
Press the module home, using your fingers.
Changes or modifications not expressly approved by
Grundfos may void the user's authority to operate the
equipment.
Cable cross-sections
Type of cable Stranded with ferrule Solid
Cross-section [mm2] [AWG] [mm2] [AWG]
Contactor for the pump 1.5 - 2.5 16-14 1.5 - 4 16-12
Terminal block for the
2.5 - 10 14-8 2.5 - 16 14-6
power supply
8
7. In cases where PTC and moisture sensors are present, you end
English (GB)
All cable glands and plugs must be mounted after the
installation is completed. up with three wires: a PTC wire, a moisture sensor wire and a
common wire. Connect only the PTC wire and the moisture
If the gaskets are not pre-mounted on the cable glands,
sensor wire. The common wire must be isolated.In Grundfos GO
mount them on the cable glands before the control unit is
Remote, you must select that both the PTC wire and
mounted on the wall.
the moisture sensor wire are connected, and select a cool-down
time for the thermal protection.
For the PTC connection, do not connect the third wire
(common wire) in the control unit. It must be isolated with
a cable-end cap. 1
Take into account the total leakage current of all the electrical
PTC1/PTC2
equipment in the installation.
2
1. Check that the supply voltage and frequency correspond to the
values stated on the nameplate. PTC1/PTC2
TM076634
3. Before switching the power on, check all voltages with a
multimeter and make sure that the voltage between neutral and
each phase does not exceed 250 VAC.
PTC connection
4. Connect the power cables and pump cables according to the
relevant electrical diagram, including the cables from the motor
temperature and moisture sensor, if any. Tighten the terminal Pos. Description
screws to the correct torque. See the table below. 1 PTC/Klixon sensors
• All wires must be secured inside the cabinet using 2 Moisture sensors
cable ties.
• The wires must not cross the safety barriers
between the connectors. The control unit only supports standard pumps and not
sensor-variant pumps.
• All cable glands must be mounted and
plugged, even if they are not in use, to ensure the
correct IP protection level.
Remember to remove the jumper from the PTC terminal if you
are connecting cables from the temperature sensor to the PTC
terminals.
PTC1 PTC2
TM076640
Recommended PTC wiring
TM070570
Example:
M1
TM070125
M2
9
English (GB)
T1 T2 T3 T1 T2 T3
L1 L2 L3 N N N PE PE PE A B A B
PTC1 PTC2
CIO1 24V
L1 L2 L3 N PE
TM070571
• For a not shielded wire, attach it to the protection cover with a
M1 cable tie.
TM070126
M2
L1 L2 L3 N N PE PE PE A B A B
PTC1 PTC2
TM070760
L1 L2 L3 PE
CIO1 GND CIO2 GND 24V GND 24V GND
M2
Sensor type Sensor function Terminals
Analog All levels CIO1 - 24 V
Dry-running level CIO2 - GND
Three-phase connections for two pumps without neutral, for Norway
only Stop level DIO1 - GND
10
2. Lead the wires through one of the cable glands. 3. Starting up the product
English (GB)
3. Depending on the type of the alarm device, connect the wires to
the relevant terminals. Note that all wires must be secured 3.1 Connecting to Grundfos GO Remote
inside the cabinet using cable ties. Before connecting the product to Grundfos GO Remote, the
• NO (Normally Open) and C (Common) Grundfos GO Remote app must be downloaded to your smartphone
or tablet. The app is free of charge and available for iOS and
• NC (Normally Closed) and C (Common). Android devices.
4. Tie the wires with cable ties. 1. Open Grundfos GO Remote on your device. Make sure that
Bluetooth is enabled.
Your device must be within reach of the product to establish
Bluetooth connection.
2. Press the Bluetooth CONNECT button on Grundfos GO
Remote.
3. Press the connect button on the operating panel. The blue LED
above the connect button is flashing until your device is
connected. Once the connection is established, the LED will be
permanently on.
NC NC C NO Grundfos GO Remote is now loading the data for the product.
Related information
3.4 How to enable Bluetooth on the operating panel
TM070569
3.5 How to disable Bluetooth on the operating panel
Designation Description
S-1 Analog sensor
S-2 Digital sensor
-- A Nominal current (see the nameplate of the pump)
1Ph Single-phase
3Ph Three-phase
Related information
6.1 Setting the application type with Grundfos GO Remote
6.24 Starting the startup wizard with the operating panel
11
3. Press the connect button on the operating panel. The blue LED 4. Product introduction
English (GB)
12
A second pump starts when the liquid level reaches Start level P2. 4.5 Terminals
English (GB)
The pump stops when the liquid level is lowered to Stop level.
If the inflow of liquid exceeds the capacity of the installed pump, the
level in the tank or well starts to rise. Eventually, the High level
sensor registers a high liquid level in the tank or well. If set, the
signal from the High level sensor can be used to activate an output
relay which can then be used to give a visual or acoustic alarm or
send a signal to a SCADA system.
If the pump is running and the liquid level in the tank or well falls
below the dry-running level, the dry-running protection stops the
pump to ensure that it is not damaged mechanically.
Fill
1
2
3
4
TM070123
TM0713351
5
1 2 3 4 5 6 7 8
Pos. Description
Pos. Description 1 Contactor for pump 1
1 High level 2 Contactor for pump 2
2 Stop level 3 Terminal block for the power supply
3 Start level P1: start level for pump 1 Terminal block for temperature and moisture-protection
4
4 Start level P2: start level for pump 2 sensor for pump 1
5 Dry-running level Terminal block for temperature and moisture-protection
5
sensor for pump 2
In the filling application, the pump is installed in a tank or well from 6 Alarm 1
where it pumps the liquid. The liquid is pumped into a second tank
where the level sensors are installed. 7 Alarm 2
The pump starts to fill the second tank when Start level P1 is 8 Analog and digital inputs and outputs.
reached.
A second pump starts when the liquid level reaches Start level P2. 1 2 3 4 5 6 7 8
The pump stops when the liquid level reaches Stop level.
If the pump for some reason does not stop at Stop level and the
liquid level keeps rising, the High level sensor eventually
registers this. If set, the signal from the High level sensor can be
used to activate a relay output which can then be used to give a
visual or acoustic alarm or send a signal to a SCADA system via a
communication interface.
If the pump is running and the liquid level in the tank falls below the
dry-running level, the dry-running protection stops the pump to DIO1 GND DIO2 GND DI1 GND DI2 GND
ensure that it is not damaged.
9 10 11 12 13 14 15 16
Related information
6.1 Setting the application type with Grundfos GO Remote
6.16.1 Automatic operation
TM070124
Pos. Description
1 Digital input/output 1, configurable
2 GND
3 Digital input/output 2, configurable
4 GND
5 Digital input 1
6 GND
7 Digital input 2
13
4.7 Supported communication interface modules and
English (GB)
Pos. Description
protocols
8 GND
The following Grundfos communication interface modules can be
9 Configurable input/output 1 added to the product.
10 GND
11 Configurable input/output 2 Communication interface module Protocol
12 GND CIM 050 GENIbus
13 Supply voltage, 24 V, max. 200 mA CIM 150 PROFIBUS DP
14 GND CIM 200 Modbus RTU
15 Supply voltage, 24 V, max. 200 mA CIM 260 3G/4G
16 GND CIM 270 1) GRM
CIM 280 1) Grundfos Utility Connect
Related information
CIM 300 BACnet
3.6 Configuring the IO terminals using Grundfos GO Remote
Modbus TCP
4.6 Identification CIM 500 PROFINET IO
4.6.1 Nameplate GRM IP
1 2 3 4 5 6 1) Not supported.
Related information
99350749
°C P1 5. Control functions
8
14
13 12 11 10 9 1 2 3 4 5 6 7
8
Pos. Description
9
1 Product name
2 Supply voltage 15
3 Maximum current 14 10
4 Maximum start current 13
5 Version number and material number 11
6 Production code (year and week) 8
TM070082
7 Serial number 12
8 IC, only for UL variants
9 FCC text, only for UL variants
Pos. Symbol Description
10 FCC ID, only for UL variants
11 Factory code 1 Display
12 IP class ft
2 m Units
13 Minimum to maximum ambient temperature
14 Production site 3 High level
15 Markings and approvals 4 Start level, pump 2
Up/Down buttons:
Pos. Description
8 • Press these buttons to navigate between
Type: submenus or change the value settings.
1
• LC 231: wall-mounted version OK button:
9
2 Number of pumps supported • Press this button to save changed values.
3 Current range of pump [A] Connect button:
Starting method: 10 • Press this button to connect the control unit
4 to Grundfos GO Remote via Bluetooth.
• DOL: direct-on-line
Panel type:
5
• PI: Plastic enclosure
14
6.3.2 Setting the start level with the operating panel
English (GB)
Pos. Symbol Description
The settings apply to analog sensors. For digital sensors, the
Reset button:
setting is automatically activated.
11 • Press this button during startup to reset
1. Press and hold OK until the display and dry running start
settings and start over or to reset an alarm
flashing.
or warning.
Operating mode for the pump: 2. Continuously press OK until the indicator light for the start level
for pump 1 starts flashing.
• On: The pump has been switched on
1 2 3
manually.
12 On Off Auto
• Off: The pump has been switched off
manually.
Status Settings Assist
• Auto: The pump is running automatically
based on settings.
Setpoint Control mode
13 Display The display shows the pump status.
5.00 bar Const. pressure
Lock symbol:
14 If the symbol is lit, the control unit is locked from
TM071336
making Operaring
changes.mode Actual controlled value
Normal
Alarm and warning symbol:
15 Red: Alarm
4.90 bar
Yellow: Warning 3. Set the start level for pump 1 by using the Up and Down
buttons.
The control unit enables manual setting and monitoring of the
system. 4. Press OK.
9 8 7 6 5 The indicator light for the start level for pump 2 starts flashing.
6. Setting the product
TM071337
2. Select the type.
• Empty
• Fill
5. Set the start level for pump 2 by using the Up and Down
Related information buttons.
3.3 Startup wizard on the operating panel 6. Continuously press OK until the display stops flashing.
4.4 Application types The settings have now been stored.
6.2 Setting the sensor type 6.4 Setting the stop level
6.2.1 Setting the sensor type with Grundfos GO Remote 6.4.1 Setting the stop level with Grundfos GO Remote
1. Go to Settings > Level control > Sensor type. The settings apply to analog sensors. For digital sensors, the
setting is automatically activated.
2. Select the type.
The stop level is the same for pump 1 and pump 2.
• Analog sensors
1. Go to Settings > Level control > Stop level
• Digital sensors
2. Set the stop level.
6.2.2 Setting the sensor type with the operating panel
1. Press and hold OK until S-1 or S-2 starts flashing. If you are using the same level for start and stop,
remember to set a stop delay. This will prevent the
2. Select the sensor type using the Up and Down buttons. pump from starting and stopping too frequently.
• S-1: Analog sensors
6.4.2 Setting the stop level with the operating panel
• S-2: Digital sensors.
The settings apply to analog sensors. For digital sensors, the
3. Press OK to confirm the setting. setting is automatically activated.
4. Continuously press OK to confirm all other settings and to exit The stop level is the same for pump 1 and pump 2.
the setup. 1. Press and hold OK until the display starts flashing.
2. Set the start level for pump 1. If you are using the same level for the start and stop
level, remember to set a stop delay. This will prevent
3. Go to Settings > Level control > Start level P2. the pump from starting and stopping too frequently.
4. Set the start level for pump 2.
15
6.5 Setting the high level 6.9.1 Setting the dry-running level with Grundfos GO Remote
English (GB)
6.6.1 Setting the after-run delay, high level 6.11.1 Setting the multipump settings with Grundfos GO
Remote
1. Go to Settings > Level control > After-run delay, high level.
1. Go to Settings > Multi pump settings.
2. Select Enable or Disable.
2. Set Inter pump delay.
3. Set a delay time. This is the starting delay between the pumps ensuring that they
do not start at the same time.
Related information
8.22 Code 165 (Signal fault) 3. Set Max number of running pumps.
8.25 Code 205 (Level switch inconsistency) This is the maximum number of pumps that are allowed to run at
the same time.
6.7 Stop delay a. When the number is set to 1, it is possible to set the nominal
The stop delay is the time from when the stop level is reached until pump current to 12 A (IEC) or 9.6 A (UL).
the pump stops. The stop delay prevents the pump from starting b. When the number is set to 2, it is possible to set the nominal
and stopping too frequently and reduces water hammer in long pump current to 9 A (IEC) or 7.6 A (UL).
pipes.
6.12 Antiseizing
6.7.1 Setting the stop delay with Grundfos GO Remote
The Anti-seizing function prevents a pump from choking or seizing
1. Select Settings > Level control > Stop delay > State
up as a result of deposits buildup. Anti-seizing is used in pits that
2. Select Stop delay time. have had no inlet flow for a long period. The Anti-seizing function
ensures that the pump starts as often as set in Anti-seizing > >
3. Set the Stop delay time. Interval. The pump will operate for the number of seconds
indicated by the user.
6.8 Power-on delay
6.12.1 Setting the "Anti-seizing" function with Grundfos GO
With this function it is possible to delay the startup of the pump after
Remote
the power supply has been switched on. The purpose is to avoid
disturbing the main power network which could happen if several 1. Go to Settings > Anti-seizing.
pumps start up immediately when the power supply is switched on.
2. Set the function to Enabled.
6.8.1 Setting the power-on delay with Grundfos GO Remote
3. Set the time interval.
1. Go to Settings > Power-on delay.
4. Set the operating time.
2. Set the function to Enabled.
6.13 Signal-detection time
3. Set the time delay.
The signal-detection time is the minimum time a level has to be
6.9 Dry-running protection active before the control unit initiates an action, such as starting or
stopping a pump.
If the pump is running and the liquid level in the tank or pit becomes
lower than the dry-running level, the dry-running protection will stop 6.13.1 Setting the signal-detection time with Grundfos GO
the pump to ensure that it is not damaged. Remote
Dry-running protection is dependent on a feedback signal from a 1. Go to Settings > Level control > Signal detection time.
level sensor installed in the tank or pit.
2. Set the signal-detection time.
16
6.14 Setting the maximum number of restarts with Here you select whether the pump must return to automatic
English (GB)
Grundfos GO Remote operating mode or stop when the manual start ends and
Automatic return has been enabled.
If the pump is seized up as a result of deposits buildup, it will be • Forced start time
stopped automatically due to overheating, provided that the motor
Here you set the time period in which the pump must run in
protection has been set. When the motor has cooled down, the
manual operating mode.
control unit will unsuccessfully try to restart the pump and this
scenario will be repeated. 1. Go to Settings > Manual start.
In order to prevent this, it is possible to set a maximum number of 2. Select Automatic return and choose one of the following
restart attempts within a set interval. options:
1. Go to Settings > Max number of restarts. • Disabled
2. Enable the function. • Enabled.
3. Set the interval within which the allowed number of restarts are 3. Go one step back in the menu and select Return to.
to be counted.
4. Choose one of the following options:
4. Set the maximum number of pump restarts which are allowed • Auto
during the set interval.
• Off.
Related information
5. Go one step back in the menu and select Forced start time.
6.17.4 Setting the motor protection with Grundfos GO Remote
6.17.1 Overheat protection 6. Set the time period in which the pump must run in manual
operating mode.
6.17.2 Overload protection
8.3 Code 4 (Too many motor restarts) Related information
6.16.2.2 Starting and stopping the pump manually with the
6.15 Setting the service interval with Grundfos GO operating panel
Remote 6.16.2.1 Starting and stopping the pump manually with Grundfos
GO Remote
You can set a time in Grundfos GO Remote in order to get a
reminder that the pump needs service when the time comes.
6.17 Motor protection
1. Go to Settings > Service > State
2. Select Enable and press OK. Make sure that all settings are entered according to the
pump and system requirements to avoid malfunction.
3. Select the pump.
4. Enter the number of hours until next service and press OK. 6.17.1 Overheat protection
The control unit offers thermal protection for the connected motors.
6.16 Operating the product
Two types of thermal-protection sensor can be connected to the
6.16.1 Automatic operation control unit: a PTC sensor (analog) and a thermal switch (digital).
In automatic operating mode, the control unit starts and stops the Under normal running conditions, the sensor will act as a short
pump based on the signals it receives from the connected level circuit, but when its temperature limit is reached, it will open and tell
sensors and the corresponding level settings within the control unit. the control unit that the temperature is too high, and the pump is
stopped. When the temperature has dropped to the sensor-trigger
Related information level, the pump will return to normal running conditions. It will not be
4.4 Application types possible to start the pump manually as long as the temperature is
too high.
6.16.2 Manual operation
Related information
6.16.2.1 Starting and stopping the pump manually with
Grundfos GO Remote 6.14 Setting the maximum number of restarts with Grundfos GO
Remote
1. Go to Settings > Control, pump 1 or Control, pump 2.
6.17.4 Setting the motor protection with Grundfos GO Remote
2. Start the pump by selecting On and pressing OK. 8.13 Code 69 (Winding temperature too high)
3. Stop the pump by selecting Off and pressing OK. 6.17.2 Overload protection
Related information The pump is protected by internal software-based motor protection.
6.16.2.3 Choosing what the pump must do after manual start Related information
6.16.2.2 Starting and stopping the pump manually with the 6.14 Setting the maximum number of restarts with Grundfos GO
operating panel Remote
1. To start a pump manually, press and hold the Pump button until 6.17.4 Setting the motor protection with Grundfos GO Remote
the pump starts. 8.9 Code 48 (Motor is overloaded)
The On indicator light is lit when the pump is operating in 6.17.3 Moisture protection
manual mode.
When a moisture sensor is installed in series with the temperature
2. Stop the pump by pressing the Pump button. sensor, the control unit needs to know how to determine whether
The Off indicator light is lit when the pump is stopped. there is a high temperature or moisture in the pump. If the
temperature is too high, normally the temperature sensor will go
Related information back to its normal stage when the temperature has dropped to its
6.16.2.3 Choosing what the pump must do after manual start trigger level. If there is moisture in the pump, then the moisture
sensor will keep the series connection open until the pump is
6.16.2.3 Choosing what the pump must do after manual start opened and serviced.
The following can be configured: To determine which sensor has been active, a cool down
• Automatic return time must be entered. This is the time that will normally pass until
Here you select if the pump must automatically return to a the temperature has dropped enough for the temperature sensor to
defined operating mode when the manual start ends. return to its normal stage. If the cool down time is exceeded, the
control unit will assume that there is moisture in the pump, and it
• Return to will send a moisture alarm.
17
Related information 6.19 Setting the buzzer with Grundfos GO Remote
English (GB)
6.17.4 Setting the motor protection with Grundfos GO Remote The internal buzzer is used to give an acoustic sound if there is a
warning or an alarm.
6.17.4 Setting the motor protection with Grundfos GO Remote
1. Go to Settings > Buzzer settings.
You can set the current, temperature and moisture protection via a
setup wizard. 2. Select when the buzzer is to be activated:
1. Go to Settings > Motor protection pump 1 or Motor • All alarms
protection pump 2. • All alarms and warnings.
2. Follow the on-screen wizard to set the following:
6.20 Setting units for Grundfos GO Remote
• Nominal pump current
Changing units as described here will only change the units shown
• Trip IEC class
in Grundfos GO Remote. It will not affect the units shown on the
• Trip class P delay operating panel of products connected to Grundfos GO Remote.
• Overheat protection. 1. Press the Menu button in the upper left corner of Grundfos GO
Remote.
Related information
2.3.3 Connecting the pump supply and power supply
6.14 Setting the maximum number of restarts with Grundfos GO
Remote
6.17.1 Overheat protection
6.17.2 Overload protection
6.17.3 Moisture protection
6.17.5 Trip classes
8.10 Code 51 (Blocked)
8.26 Code 220 (Contactor wear out)
6.17.5 Trip classes
LC 23X offers two ways of motor protection:
• an adjustable trip class (P)
• trip classes according to the IEC standard that defines trip
classes (5, 10, 20 and 30).
Related information
6.17.4 Setting the motor protection with Grundfos GO Remote
TM075196
3. If you want to delete all alarms and warnings from the history
log, press Show log > Reset alarm and warning logs.
6.18.2 Setting the automatic alarm reset with Grundfos GO
Remote 2. Go to General > Settings > Products > Units.
1. Go to Settings > Automatic alarm reset. 3. Select US or Grundfos default units.
2. Select one of the following: 6.21 Setting units for the operating panel with Grundfos
GO Remote
The control unit does not reset
Changing units as described below changes the units shown in the
No automatic reset any alarm or warning. You
operating panel of the product connected to Grundfos GO Remote.
must do it manually.
It does not affect the units shown in Grundfos GO Remote.
The control unit resets alarms 1. Go to Settings > Display units.
and warnings unless the
All except pump critical
related fault can damage the 2. Select the units to be used on the operating panel.
pump. • SI Units
The control unit resets alarms • US Units.
All alarms and warnings, regardless of
the fault. 6.22 GENIbus
6.18.3 Resetting alarms and warnings on the operating panel GENIbus, the Grundfos Electronics Network Intercommunications
bus, is a fieldbus developed by Grundfos to meet the need for data
You can manually reset alarms and warnings on the operating transfer in all typical Grundfos motor or pump applications.
panel. However, if the fault causing the alarm or warning has not Grundfos devices with GENIbus can be wired together in networks
been removed, the alarm or warning will appear again. and integrated in automation systems. Each device on the network
must have a unique GENIbus address. GENIbus is based on the
1. Press Reset on the operating panel to reset the alarm or
RS485 hardware standard and typically operates at a baud rate of
warning.
9600 bits/s.
18
6.22.1 Setting the GENIbus address with Grundfos GO Remote
English (GB)
DANGER
1. Go to Settings > GENI bus address. Intoxication or risk of chemical burn
Death or serious personal injury
2. Set the GENIbus address.
‐ The battery can cause severe or fatal injuries in 2
The GENIbus address is a unique identifier for the product on hours or less if it is swallowed or placed inside any
the network. part of the body. In such an event, seek medical
attention immediately.
6.23 Security
The replacement or servicing of batteries must be carried
6.23.1 Locking the operating panel
out by a qualified person.
The operating panel can only be locked with Grundfos GO Remote.
The battery contained within this product, whether new or
1. Go to Settings > Security > Lock Display. used, is hazardous and is to be kept away from children.
2. Enable the setting and press Done. To replace the battery, do the following:
3. Select if you want to restrict access to Settings only or 1. Remove the front cover.
Settings and operation.
2. Gently grab around the battery without touching it too much.
4. Press Done.
3. Push the battery to the side to release it.
The lock symbol on the operating panel is now lit. 4. Pull the battery up.
6.23.2 Unlocking the operating panel 5. Insert a new battery of the correct type.
The operating panel can only be unlocked with Grundfos GO
Remote. Related information
1. Go to Settings > Security > Lock Display. 9.3 Environmental data
2. Disable the setting and press Done. 7.3 Replacing the CIM module
The lock symbol on the operating panel is switched off.
WARNING
6.23.3 Locking Grundfos GO Remote Electric shock
Death or serious personal injury
1. Go to Settings > Security > Lock GO Remote.
‐ Switch off the power supply before making any
2. Enable the setting and press Done. electrical connections.
3. Enter a four digit PIN code and press CONFIRM. ‐ Make sure that the power supply cannot be switched
on accidentally.
A lock symbol indicates which menus are locked. To view or change
settings, you must enter the PIN code. 1. Switch off the power supply to the product and
other components with external supply.
6.23.4 Unlocking Grundfos GO Remote
2. Write down the terminal connection of each wire to ensure
1. Go to Settings > Security.
correct re-connection.
2. Enter the four digit PIN code.
3. Disconnect all wires connected to the CIM module.
3. Select Lock GO Remote.
4. Remove the screws that holds the module.
4. Disable the setting and press Done.
5. Remove the module from the control unit.
All menus in Grundfos GO Remote are unlocked. 6. Fit the new module.
6.24 Starting the startup wizard with the operating panel 7. Connect all wires.
• Press and hold the OK button for 5 seconds until S-1 or S-2
starts flashing. 8. Fault finding the product
Related information WARNING
3.3 Startup wizard on the operating panel Electric shock
Death or serious personal injury
7. Servicing the product ‐ Switch off the power supply before you start any work
on the product.
WARNING
Electric shock ‐ Make sure that the power supply cannot be switched
Death or serious personal injury on accidentally.
‐ Switch off the incoming power supply before you start Fault finding and fault correction must be carried out by qualified
any work on the product or connected pumps. persons.
‐ Make sure that the power supply cannot be switched
on accidentally. 8.1 Overview of alarm and warning codes
19
English (GB)
20
8.13 Code 69 (Winding temperature too high)
English (GB)
Cause Remedy
The pump is clogged. • Remove the blockage. • Alarm code 69 is shown on the display.
The blockage causes the motor • Check the pit conditions to • The alarm symbol on the display turns red and the pump stops.
current to rise, which could ensure blockage is not • Alarm code Winding temperature too high is displayed in
damage the pump. possible again. Grundfos GO Remote.
Cause Remedy PTC input wiring and/or • Make sure that the two PTC
sensors are incorrect. wires from the pump are
The pump is blocked. • Dismantle the pump by connected correctly to the
The pump cannot rotate due to removing the pump head, and terminals on the product.
a blockage. remove any blockage or
• Make sure that the third PTC
impurities preventing the
wire is left unconnected if
pump from rotating.
present.
• Check the water quality to
• Make sure that the PTC wires
eliminate the risk of lime
are undamaged.
precipitation.
• Make sure that the PTC
Before dismantling the pump,
sensors within the pumps are
drain the system or close the
undamaged.
isolating valves on either side
of the pump. The pumped • Perform a test by
liquid may be scalding hot and disconnecting the PTC wires
under high pressure. from the pump and shorting
PTC1 terminal A and B
Related information and also PTC2 terminal A and
6.17.4 Setting the motor protection with Grundfos GO Remote B, and verify that the error is
cleared.
8.11 Code 56 (Underload, current sensor measures a • Replace the product due to
value too low) the damaged PTC
circuit. Contact Grundfos.
• Alarm code 56 is shown on the display.
• The alarm symbol on the display turns red and the pump stops. Related information
• Alarm code Underload, current sensor measures a value too 6.17.1 Overheat protection
low is displayed in Grundfos GO Remote.
8.14 Code 72 (Internal fault)
Cause Remedy
• Alarm code 72 is shown on the display.
The measured current is too • Make sure that the nominal
• The alarm symbol on the display turns red and the pump stops.
low. pump current is configured
correctly in Grundfos GO • Alarm code Internal hardware fault is displayed in Grundfos
Remote. GO Remote.
• Make sure that the pump is Cause Remedy
connected to the pump
terminals on the product. Fault in internal hardware. • Contact Grundfos or an
authorised service workshop.
• Make sure that the pump
cable is not damaged.
8.15 Code 76 (Internal fault)
• Make sure that the pump
rating is within the specified • Alarm code 76 is shown on the display.
current or power rating of the • The alarm symbol on the display turns red and the pump stops.
product. • Alarm code Drive unit communication fault is displayed in
Some smaller pumps have • Make sure that the pumps get Grundfos GO Remote.
PTC/Klixon sensors integrated sufficient cooling and are not
into the motor windings, but the blocked. Cause Remedy
sensors have no connection out Internal communication fault. • Contact Grundfos or an
of the pump. In case of authorised service workshop.
overheating, the sensors stop
the pump, and no current is
8.16 Code 84 (Memory storage media faulty)
drawn.
• Warning code 84 is shown on the display if you press
the Up or Down button.
8.12 Code 57 (Missing water in the application)
• The warning symbol on the display turns yellow and the pump's
• Alarm code 57 is shown on the display.
operating mode is unchanged.
• The alarm symbol on the display turns red and the pump stops.
• Warning code Memory storage media faulty is displayed in
• Alarm code Dry run is displayed in Grundfos GO Remote. Grundfos GO Remote.
Cause Remedy Cause Remedy
Low water level in the pit and • Check and configure the An error in the internal memory • Replace the control unit.
the pump stops due to the dry- sensor stop level. has been detected.
running function.
21
English (GB)
The CIM module is defective. • Contact Grundfos. 8.23 Code 181 (Signal fault, PTC input)
Related information • Alarm code 181 is shown on the display.
2.2.5 Installing a communication interface module • The alarm symbol on the display turns red and the pump stops.
• Alarm code Signal fault, PTC input is displayed in Grundfos
8.21 Code 163 (Motor-drive protection function GO Remote.
measurement fault)
Cause Remedy
• Alarm code 163 is shown on the display.
There is a signal fault in the • Make sure that the two PTC
• The alarm symbol on the display turns red, but the pump's
PTC input. wires from the pump are
operating mode is unchanged.
connected correctly to the
• Alarm code Drive unit configuration fault is displayed in terminals on the product.
Grundfos GO Remote.
• Make sure that the third PTC
wire is left unconnected, if
present.
• Make sure that the PTC wires
are undamaged.
22
English (GB)
Cause Remedy Cause Remedy
• Make sure that the PTC The contactor has reached its
sensors within the pumps are maximum number of operating
undamaged. cycles and is worn out.
• Perform a test by
disconnecting the PTC wires Related information
from the pump and shorting 6.17.4 Setting the motor protection with Grundfos GO Remote
PTC1 terminal A and B
and also PTC2 terminal A and 8.27 Code 229 (Water on floor)
B, and verify that the error is • Warning code 229 is shown on the display if you press
cleared. the Up or Down button.
• Replace the product due to • The warning symbol on the display turns yellow and the pump's
damaged PTC circuit. Contact operating mode is unchanged.
Grundfos.
• Warning code Water on floor is displayed in Grundfos GO
Related information Remote.
2.3.3 Connecting the pump supply and power supply Cause Remedy
8.24 Code 191 (High water level) The sensor detects water on • Check for water leakage.
the floor.
• Alarm code 191 is shown on the display.
• The alarm symbol on the display turns red, but the pump's
operating mode is unchanged.
9. Technical data
• Alarm code High water level is displayed in Grundfos GO 9.1 Electrical data
Remote.
Voltage
Cause Remedy
• 1 x 110-240 V - 10 %/+ 10 %, PE
The defined start level did not • Check and configure the
• 3 x 200-460 V - 10 %/+ 10 %, PE.
start the pump. sensor start level.
The pump is not big enough to • Contact Grundfos or an Frequency
remove the water. authorised service workshop. 50/60 Hz.
The level sensor is defective • Check the functionality of the Maximum starting current
and not reacting on level level sensor.
IEC: 78 A.
changes.
UL: 68 A.
Related information
Minimum power factor
3.6 Configuring the IO terminals using Grundfos GO Remote
0.86.
8.25 Code 205 (Level switch inconsistency) Digital input
• Alarm code 205 is shown on the display. IEC: solid or stranded 0.5 - 2.5 mm2, flexible 0.25 - 1.5 mm2.
• The alarm symbol on the display turns red and the pump stops. UL: solid or stranded AWG 28-12.
• Alarm code Level switch inconsistency is displayed in Stripping length: 5-6 mm (0.19"-0.24").
Grundfos GO Remote.
23
Cable diameters 9.4 Temperature
English (GB)
IEC stranded 0.75 to 2.5 mm2. Min. storage temperature -30 °C (-22 °F)
IEC solid 1.5 to 4.0 mm2. Max. storage temperature 60 °C (140 °F)
UL stranded or solid AWG 18 to 12.
Screw torque: 1.2 Nm. Ambient temperature
Related information
2.3.2 Protection of controller and supply cables
Pollution degree
Category 3.
Motor protection
Software class B.
Action type 2.B.
Battery
Size BR2032.
Related information
7.2 Replacing the battery
24
Argentina Estonia Lithuania South Africa
Grundfos companies
Bombas GRUNDFOS de Argentina S.A. GRUNDFOS Pumps Eesti OÜ GRUNDFOS Pumps UAB GRUNDFOS (PTY) LTD
Ruta Panamericana km. 37.500industin Peterburi tee 92G Smolensko g. 6 16 Lascelles Drive, Meadowbrook Estate
1619 - Garín Pcia. de B.A. 11415 Tallinn LT-03201 Vilnius 1609 Germiston, Johannesburg
Tel.: +54-3327 414 444 Tel.: + 372 606 1690 Tel.: + 370 52 395 430 Tel.: (+27) 10 248 6000
Fax: +54-3327 45 3190 Fax: + 372 606 1691 Fax: + 370 52 395 431 Fax: (+27) 10 248 6002
E-mail: lgradidge@grundfos.com
Australia Finland Malaysia
GRUNDFOS Pumps Pty. Ltd. OY GRUNDFOS Pumput AB GRUNDFOS Pumps Sdn. Bhd. Spain
P.O. Box 2040 Trukkikuja 1 7 Jalan Peguam U1/25 Bombas GRUNDFOS España S.A.
Regency Park FI-01360 Vantaa Glenmarie industrial Park Camino de la Fuentecilla, s/n
South Australia 5942 Tel.: +358-(0) 207 889 500 40150 Shah Alam, Selangor E-28110 Algete (Madrid)
Tel.: +61-8-8461-4611 Tel.: +60-3-5569 2922 Tel.: +34-91-848 8800
Fax: +61-8-8340-0155 France Fax: +60-3-5569 2866 Fax: +34-91-628 0465
Pompes GRUNDFOS Distribution S.A.
Austria Parc d’Activités de Chesnes Mexico Sweden
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. 57, rue de Malacombe Bombas GRUNDFOS de México GRUNDFOS AB
Grundfosstraße 2 F-38290 St. Quentin Fallavier (Lyon) S.A. de C.V. Box 333 (Lunnagårdsgatan 6)
A-5082 Grödig/Salzburg Tel.: +33-4 74 82 15 15 Boulevard TLC No. 15 431 24 Mölndal
Tel.: +43-6246-883-0 Fax: +33-4 74 94 10 51 Parque industrial Stiva Aeropuerto Tel.: +46 31 332 23 000
Fax: +43-6246-883-30 Apodaca, N.L. 66600 Fax: +46 31 331 94 60
Germany Tel.: +52-81-8144 4000
Belgium GRUNDFOS GMBH Fax: +52-81-8144 4010 Switzerland
N.V. GRUNDFOS Bellux S.A. Schlüterstr. 33 GRUNDFOS Pumpen AG
Boomsesteenweg 81-83 40699 Erkrath Netherlands Bruggacherstrasse 10
B-2630 Aartselaar Tel.: +49-(0) 211 929 69-0 GRUNDFOS Netherlands CH-8117 Fällanden/ZH
Tel.: +32-3-870 7300 Fax: +49-(0) 211 929 69-3799 Veluwezoom 35 Tel.: +41-44-806 8111
Fax: +32-3-870 7301 E-mail: infoservice@grundfos.de 1326 AE Almere Fax: +41-44-806 8115
Service in Deutschland: Postbus 22015
Belarus kundendienst@grundfos.de 1302 CA ALMERE Taiwan
Представительство ГРУНДФОС в Минске Tel.: +31-88-478 6336 GRUNDFOS Pumps (Taiwan) Ltd.
220125, Минск Greece Fax: +31-88-478 6332 7 Floor, 219 Min-Chuan Road
ул. Шафарнянская, 11, оф. 56, БЦ «Порт» GRUNDFOS Hellas A.E.B.E. E-mail: info_gnl@grundfos.com Taichung, Taiwan, R.O.C.
Тел.: +375 17 397 397 3 20th km. Athinon-Markopoulou Av. Tel.: +886-4-2305 0868
+375 17 397 397 4 P.O. Box 71 New Zealand Fax: +886-4-2305 0878
Факс: +375 17 397 397 1 GR-19002 Peania GRUNDFOS Pumps NZ Ltd.
E-mail: minsk@grundfos.com Tel.: +0030-210-66 83 400 17 Beatrice Tinsley Crescent Thailand
Fax: +0030-210-66 46 273 North Harbour Industrial Estate GRUNDFOS (Thailand) Ltd.
Bosnia and Herzegovina Albany, Auckland 92 Chaloem Phrakiat Rama 9 Road
GRUNDFOS Sarajevo Hong Kong Tel.: +64-9-415 3240 Dokmai, Pravej, Bangkok 10250
Zmaja od Bosne 7-7A GRUNDFOS Pumps (Hong Kong) Ltd. Fax: +64-9-415 3250 Tel.: +66-2-725 8999
BiH-71000 Sarajevo Unit 1, Ground floor, Siu Wai industrial Fax: +66-2-725 8998
Tel.: +387 33 592 480 Centre Norway
Fax: +387 33 590 465 29-33 Wing Hong Street & 68 King Lam GRUNDFOS Pumper A/S Turkey
www.ba.grundfos.com Street, Cheung Sha Wan Strømsveien 344 GRUNDFOS POMPA San. ve Tic. Ltd. Sti.
E-mail: grundfos@bih.net.ba Kowloon Postboks 235, Leirdal Gebze Organize Sanayi Bölgesi
Tel.: +852-27861706 / 27861741 N-1011 Oslo Ihsan dede Caddesi
Brazil Fax: +852-27858664 Tel.: +47-22 90 47 00 2. yol 200. Sokak No. 204
BOMBAS GRUNDFOS DO BRASIL Fax: +47-22 32 21 50 41490 Gebze/ Kocaeli
Av. Humberto de Alencar Castelo Branco, Hungary Tel.: +90 - 262-679 7979
630 GRUNDFOS Hungária Kft. Poland Fax: +90 - 262-679 7905
CEP 09850 - 300 Tópark u. 8 GRUNDFOS Pompy Sp. z o.o. E-mail: satis@grundfos.com
São Bernardo do Campo - SP H-2045 Törökbálint ul. Klonowa 23
Tel.: +55-11 4393 5533 Tel.: +36-23 511 110 Baranowo k. Poznania Ukraine
Fax: +55-11 4343 5015 Fax: +36-23 511 111 PL-62-081 Przeźmierowo ТОВ "ГРУНДФОС УКРАЇНА"
Tel.: (+48-61) 650 13 00 Бізнес Центр Європа
Bulgaria India Fax: (+48-61) 650 13 50 Столичне шосе, 103
Grundfos Bulgaria EOOD GRUNDFOS Pumps india Private Limited м. Київ, 03131, Україна
Slatina District 118 Old Mahabalipuram Road Portugal Tel.: (+38 044) 237 04 00
Iztochna Tangenta street no. 100 Thoraipakkam Bombas GRUNDFOS Portugal, S.A. Fax: (+38 044) 237 04 01
BG - 1592 Sofia Chennai 600 097 Rua Calvet de Magalhães, 241 E-mail: ukraine@grundfos.com
Tel.: +359 2 49 22 200 Tel.: +91-44 2496 6800 Apartado 1079
Fax: +359 2 49 22 201 P-2770-153 Paço de Arcos United Arab Emirates
E-mail: bulgaria@grundfos.bg Indonesia Tel.: +351-21-440 76 00 GRUNDFOS Gulf Distribution
PT GRUNDFOS Pompa Fax: +351-21-440 76 90 P.O. Box 16768
Canada Graha intirub Lt. 2 & 3 Jebel Ali Free Zone, Dubai
GRUNDFOS Canada inc. Jln. Cililitan Besar No.454. Makasar, Romania Tel.: +971 4 8815 166
2941 Brighton Road Jakarta Timur GRUNDFOS Pompe România SRL Fax: +971 4 8815 136
Oakville, Ontario ID-Jakarta 13650 S-PARK BUSINESS CENTER, Clădirea
L6H 6C9 Tel.: +62 21-469-51900 A2, etaj 2 United Kingdom
Tel.: +1-905 829 9533 Fax: +62 21-460 6910 / 460 6901 Str. Tipografilor, Nr. 11-15, Sector 1, Cod GRUNDFOS Pumps Ltd.
Fax: +1-905 829 9512 013714 Grovebury Road
Ireland Bucuresti, Romania Leighton Buzzard/Beds. LU7 4TL
China GRUNDFOS (Ireland) Ltd. Tel.: 004 021 2004 100 Tel.: +44-1525-850000
GRUNDFOS Pumps (Shanghai) Co. Ltd. Unit A, Merrywell Business Park E-mail: romania@grundfos.ro Fax: +44-1525-850011
10F The Hub, No. 33 Suhong Road Ballymount Road Lower
Minhang District Dublin 12 Russia U.S.A.
Shanghai 201106 PRC Tel.: +353-1-4089 800 ООО Грундфос Россия Global Headquarters for WU
Tel.: +86 21 612 252 22 Fax: +353-1-4089 830 ул. Школьная, 39-41 856 Koomey Road
Fax: +86 21 612 253 33 Москва, RU-109544, Russia Brookshire, Texas 77423 USA
Italy Тел. (+7) 495 564-88-00 (495) 737-30-00 Phone: +1-630-236-5500
Columbia GRUNDFOS Pompe Italia S.r.l. Факс (+7) 495 564 8811
GRUNDFOS Colombia S.A.S. Via Gran Sasso 4 Uzbekistan
E-mail grundfos.moscow@grundfos.com
Km 1.5 vía Siberia-Cota Conj. Potrero I-20060 Truccazzano (Milano) Grundfos Tashkent, Uzbekistan
Chico, Tel.: +39-02-95838112 Serbia The Representative Office of Grundfos
Parque Empresarial Arcos de Cota Bod. 1A. Fax: +39-02-95309290 / 95838461 Grundfos Srbija d.o.o. Kazakhstan in Uzbekistan
Cota, Cundinamarca Omladinskih brigada 90b 38a, Oybek street, Tashkent
Tel.: +57(1)-2913444 Japan 11070 Novi Beograd Tel.: (+998) 71 150 3290 / 71 150 3291
Fax: +57(1)-8764586 GRUNDFOS Pumps K.K. Tel.: +381 11 2258 740 Fax: (+998) 71 150 3292
1-2-3, Shin-Miyakoda, Kita-ku Fax: +381 11 2281 769
Croatia Hamamatsu www.rs.grundfos.com
GRUNDFOS CROATIA d.o.o. 431-2103 Japan
Buzinski prilaz 38, Buzin Tel.: +81 53 428 4760 Singapore
HR-10010 Zagreb Fax: +81 53 428 5005 GRUNDFOS (Singapore) Pte. Ltd.
Tel.: +385 1 6595 400 25 Jalan Tukang
Fax: +385 1 6595 499 Korea Singapore 619264
www.hr.grundfos.com GRUNDFOS Pumps Korea Ltd. Tel.: +65-6681 9688
6th Floor, Aju Building 679-5 Faxax: +65-6681 9689
Czech Republic Yeoksam-dong, Kangnam-ku, 135-916
GRUNDFOS Sales Czechia and Slovakia Seoul, Korea Slovakia
s.r.o. Tel.: +82-2-5317 600 GRUNDFOS s.r.o.
Čajkovského 21 Fax: +82-2-5633 725 Prievozská 4D 821 09 BRATISLAVA
779 00 Olomouc Tel.: +421 2 5020 1426
Tel.: +420-585-716 111 Latvia sk.grundfos.com
SIA GRUNDFOS Pumps Latvia
Denmark Deglava biznesa centrs Slovenia
GRUNDFOS DK A/S Augusta Deglava ielā 60 GRUNDFOS LJUBLJANA, d.o.o.
Martin Bachs Vej 3 LV-1035, Rīga, Leskoškova 9e, 1122 Ljubljana
DK-8850 Bjerringbro Tel.: + 371 714 9640, 7 149 641 Tel.: +386 (0) 1 568 06 10
Tel.: +45-87 50 50 50 Fax: + 371 914 9646 Fax: +386 (0)1 568 06 19
Fax: +45-87 50 51 51 E-mail: tehnika-si@grundfos.com
E-mail: info_GDK@grundfos.com
www.grundfos.com/DK