SFFECO227

UL/
FMFi
reExt
ingui
shi
ngSyst
em
SFFECO-227
BASIC SYSTEM STRUCTURE
FLOW CALCULATION SOFTWARE &
ACTUATION PACKAGE
TECHNICAL SUPPORT MATERIAL
UNIT
SFFECO-227 Engineered System
Electrical, Manual and
comes with a UL/FM Software, which
Pneumatic Units Suitable
enables engineers to perform required
for Multiple System
flow, piping and nozzle details.
Cylinders Arrangements
SFFECO-227 Manuals are extensively
that give more flexibility
prepared to provide clear
features.
understanding of systems design,
installation and maintenance.

SYSTEM CONTAINER
ASSEMBLY
CONTROL & DETECTION
SFFECO-227 Engineered
HARDWARE COMPONENTS
System cylinders assembled
SFFECO-227 integrated clean
with Head Valves & Straps
agent system works hand
Starts from 35 lbs up to 1200
in-hand with state of the art
lbs equipped with head valve
UL/FM Approved Control
size of 1”, 1.5”, 2.5”, 3”, 4”
Detection, and Notification
Manufactures, Stamped, &
Components such as Potter
Tested in accordance to
Electric, Hochiki, Lifeco, etc.
UL/FM and DOT requirements.
WHY
SFFECO-227
Inert on people & safe on environment
?Superior to Water & Dry chemicals.

Lower design concentration, Safe, and Non-Toxic Suitable for Class A, B, C fires.

Active on Fire with complete extinguishment SFFECO-227 is an engineered and Pre-Engineered


capability designed to fully discharge within System designed to protect specific hazards.
seconds.
With SFFECO 227 clean agent system you assured
Three dimensional suppression, & with effective of fast, efficient, environmentally safe fire
penetration to knock down fires in hidden spaces. extinguishment.

Ability to recover quickly from business disruption. Recognized and certified by the top independent
listing and approval parties NFPA, UL, FM, U.S.
No cost of down time. EPA...
Zero Ozone depletion Potential.

HFC-227ea
CF3CHFCF3 - Hepta Fluoropropane is liquefied compressed
Colorless, Odorless, Electrically non-conductive gas, works to
quench fires in seconds & hold damage to a max.

HFC-227ea
Suppresses Fire Primarily by physically cooling flame through
removing heat energy, & interrupting the combustion reaction to an
extent that cannot sustain itself.

HFC-227ea
Waterless Fire Suppressant does not leave residues, Particulates,
Water or Corrosion.
‫ﺷﺮﻛﺔ اﻟﻤﺼﻨﻊ اﻟﺴﻌﻮدي ﺟﻬﺰة اﻃﻔﺎء‬
SAUDI FACTORY FOR FIRE EQUIPMENT Co.

SECTORS OF
APPLICATION

SF-KSA/227-CAT/06-21/REV00

In line with our policy of con�nuous product improvement,


SFFECO reserves the right to modify specifica�ons
without prior no�ce.

Jeddah Branch
Factory & Head Office - Riyadh
P.O. Box: 16769, Jeddah – 21474, KSA
2nd Industrial Area, Al-Kharj Road, Riyadh, KSA Tel : +966 12 670 6009, Fax: +966 12 676 0307
P.O. Box: 4441, Riyadh 14334 E-mail: jeddah@sffeco.com.sa
Tel : +966 11 2650070, Fax: +966 11 2652190 Dammam Branch
E-mail: riyadh@sffeco.com.sa P.O. Box: 7162, Dammam – 31462, KSA
Tel : +966 13 8351961, Fax: +966 13 8351968
SFFECO Global - Dubai
E-mail: dammam@sffeco.com.sa
P.O. Box: 261318, JAFZA South, Dubai U.A.E. Madinah Branch
Tel: +971 4 880 9890, Fax: +971 4 880 9822 Tel : 0148660959, 0148283256, Fax: 0148660969
www.
E-mail: sales@sffecoglobal.com E-mail: madinah@sffeco.com.sa SFFECO .com


&OHDQ([WLQJXLVKLQJ$JHQWV
7KHH[WLQJXLVKLQJDJHQWVOLVWHGLQWKLVVHFWLRQDUHHOHFWULFDOO\QRQFRQGXFWLYHDJHQWVWKDWH[WLQJXLVKILUHVDVQRWHGDQGOHDYHQR
UHVLGXHXSRQHYDSRUDWLRQ7KHVHDJHQWVDUHOLVWHGLQ1DWLRQDO)LUH3URWHFWLRQ$VVRFLDWLRQ1)3$6WDQGDUGRQ&OHDQ$JHQW)LUH
([WLQJXLVKLQJ6\VWHPVDQGDUHDFFHSWHGE\WKH8QLWHG6WDWHV(QYLURQPHQWDO3URWHFWLRQ$JHQF\ (3$ 6LJQLILFDQW1HZ$OWHUQDWLYHV
3ROLF\ 61$3 3URJUDPVXEMHFWWRDQ\61$31DUURZHG8VH/LPLWVDQGRWKHUUHVWULFWLRQV
-XULVGLFWLRQVRXWVLGHWKH8QLWHG6WDWHVPD\QRWUHFRJQL]H1)3$DQG(3$VDQFWLRQRIFHUWDLQFOHDQDJHQWV/RFDODQGQDWLRQDO
JRYHUQPHQWDOUHJXODWLRQVVKRXOGEHFRQVXOWHGSULRUWRDJHQWVHOHFWLRQ

&KHPRULŒ

7UDGH1DPH &KHPRULŒ

&KHPLFDO,GHQWLILFDWLRQ KHSWDIOXRURSURSDQH

'HVLJQDWLRQ +)&HD

0LQLPXP([WLQJXLVKLQJ&RQFHQWUDWLRQV &ODVV$±

&ODVV%±

$/& !

12$(/ 

/2$(/ 

8VHV )RUXVHLQ)0$SSURYHGILUHH[WLQJXLVKLQJV\VWHPVWKDWKDYH
EHHQWHVWHGH[SUHVVO\IRUXVHZLWK+)&HDDJHQW&ODVV$
VXUIDFHEXUQLQJRQO\ &ODVV%DQG&ODVV&H[WLQJXLVKLQJ
FDSDELOLWLHV

&RPSDQ\1DPH &KHPRUL//&
&RPSDQ\$GGUHVV :HVWWK6W:LOPLQJWRQ'HODZDUH86$
&RPSDQ\:HEVLWH 1RW$YDLODEOH
1HZ8SGDWHG3URGXFW/LVWLQJ 1R
/LVWLQJ&RXQWU\ 8QLWHG6WDWHVRI$PHULFD
$JHQW7\SH +)&
&HUWLILFDWLRQ7\SH )0$SSURYHG

‹)0$SSURYDOV$OOULJKWVUHVHUYHG RI
Clean Agent Fire Extinguishing Systems
These systems contain electrically nonconducting, volatile, or gaseous fire extinguishing agents that don't leave a residue upon
evaporation (per NFPA 2001 paragraph 1-3.1). They are effective for total flooding protection against hazards involving liquid
flammable materials, electrical equipment, and ordinary solid combustibles in occupancy arrangements which produce only surface
burning. In general, these agents are not effective or appropriate for hazards which produce deep-seated burning or for those which
involve chemicals containing their own oxygen (such as cellulose nitrate), metal hydrides, or reactive metals (such as sodium,
magnesium or uranium).
Clean Agent systems are similar in many respects to Halon 1301 and carbon dioxide systems. Discharge of the agent by total flooding
or local application may create atmospheric hazards to personnel. Toxic thermal decomposition products can be minimized by fast fire
detection coupled with rapid agent discharge. Personnel should not remain in the area following system discharge. Table A-1-5.1.1 of
NFPA 2001 provides information on toxicological and physiological effects covered in this equipment classification. The No Observed
Adverse Effect Level (NOAEL) is the highest concentration at which no adverse physiological or toxicological effect has been
observed. The Lowest Observed Adverse Effect Level (LOAEL) is the lowest concentration at which an adverse physiological or
toxicological effect has been observed.
Systems can only be FM Approved under this classification if they use agents having a component Approval. The system Approvals
specifically reference the relevant agent Approval. Individual agent listings appear under the category Clean Extinguishing Agents.
Compatible FM Approvals controls must be used. (See AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS AND OTHER
FIRE PROTECTION EQUIPMENT under ELECTRICAL SIGNALING.)
Application of this equipment should be subject to the limitations specified and subject to FM Global's acceptance of plans prior to
installation. Required design concentrations vary from agent to agent and depending upon maximum design parameters, the
concentration may vary among system manufacturers. The design concentrations listed by the system manufacturers are generally
accepted in electrical/electronic hazards, i.e. computer, telecommunication areas, provided that Class A ordinary combustibles are
kept to a minimum, thereby minimizing the potential for a deep seated Class A fire.
System charging and recharging shall be done only by the manufacturer or a FM Approved representative.
The Clean Agent systems FM Approved under this classification have been addressed by NFPA 2001, Standard on Clean Agent
Extinguishing Systems, 1994 Edition and must be listed in the United States Environmental Protection Agency (EPA) Significant New
Alternatives Policy (SNAP) as an acceptable substitute to Halon 1301.
Jurisdictions outside the United States may not recognize NFPA and EPA sanction of certain clean agents. Local and national
governmental regulations should be consulted prior to agent selection.
*Alternative to Halon 1211 and Halon 1301.

SFFECO 500 PSI Engineered HFC-227ea Fire Extinguishing System


System Designation: 500 PSI HFC-227ea
System Type: Engineered Clean Agent Fire Extinguishing System
Agent Identification: HFC-227ea
Minimum and Maximum Agent Storage Balanced Systems: 32 to 122ºF (0 to 50ºC)
Temperatures: Unbalanced Systems: 60 to 80ºF (16 to 27ºC)
Types of Nozzles Available: 180°, 360°
Minimum and Maximum Nozzle Heights: 1.0 to 16.0 ft (0.33 to 4.87 m)
360°: 1600 ft² (148.65 m²); Maximum Radial Coverage (Distance to Farthest
Maximum Area of Coverage for Nozzle Corner): 28.28 ft (8.62 m)
Type: 180°: 1600 ft² (148.65 m²); Maximum Radial Coverage (Distance to Farthest
Corner): 44.72 ft (13.63 m)
Minimum Design Concentrations for Hazard Class A: 6.96%
Class: Class B: 8.71% (for liquids other than heptane, see system manual)
Flow Calculation Software: Sffeco Flow Calculation Software SFF_v4.00.857.467
Sffeco Engineered HFC-227ea (500 PSI) Clean Agent Fire Suppression System
Design, Installation, Operation, and Maintenance Manual, SF-90225-E, Rev 0.0,
Design, Installation, Operation, and
April 1st, 2021
Maintenance Manual(s):
Sffeco Clean Agent HFC-227ea Fill Manual, SF-92221-FM Rev 0.0, April 1st 2021
Limitations or Exceptions to Approval: Limitations as defined in the software and manuals listed above

© 2007-2021 FM Approvals. All rights reserved. Page 1 of 2


Saudi Factory for Fire Equipment Co
2nd Industrial Area Al-Kharj Rd
Approved Filling Stations: Po Box 58469
Riyadh, 11515
Saudi Arabia

Company Name: Saudi Factory for Fire Equipment Co


Company Address: 2nd Industrial Area Al-Kharj Rd, PO Box 58469, Riyadh 11515, Saudi Arabia
Company Website: http://sffeco.com
New/Updated Product Listing: Yes
Listing Country: Saudi Arabia
Agent Type: HFC-227ea
Certification Type: FM Approved

© 2007-2021 FM Approvals. All rights reserved. Page 2 of 2


Clean Agent Fire Extinguishing Systems
These systems contain electrically nonconducting, volatile, or gaseous fire extinguishing agents that don't leave a residue upon
evaporation (per NFPA 2001 paragraph 1-3.1). They are effective for total flooding protection against hazards involving liquid
flammable materials, electrical equipment, and ordinary solid combustibles in occupancy arrangements which produce only surface
burning. In general, these agents are not effective or appropriate for hazards which produce deep-seated burning or for those which
involve chemicals containing their own oxygen (such as cellulose nitrate), metal hydrides, or reactive metals (such as sodium,
magnesium or uranium).
Clean Agent systems are similar in many respects to Halon 1301 and carbon dioxide systems. Discharge of the agent by total flooding
or local application may create atmospheric hazards to personnel. Toxic thermal decomposition products can be minimized by fast fire
detection coupled with rapid agent discharge. Personnel should not remain in the area following system discharge. Table A-1-5.1.1 of
NFPA 2001 provides information on toxicological and physiological effects covered in this equipment classification. The No Observed
Adverse Effect Level (NOAEL) is the highest concentration at which no adverse physiological or toxicological effect has been
observed. The Lowest Observed Adverse Effect Level (LOAEL) is the lowest concentration at which an adverse physiological or
toxicological effect has been observed.
Systems can only be FM Approved under this classification if they use agents having a component Approval. The system Approvals
specifically reference the relevant agent Approval. Individual agent listings appear under the category Clean Extinguishing Agents.
Compatible FM Approvals controls must be used. (See AUTOMATIC RELEASES FOR EXTINGUISHING SYSTEMS AND OTHER
FIRE PROTECTION EQUIPMENT under ELECTRICAL SIGNALING.)
Application of this equipment should be subject to the limitations specified and subject to FM Global's acceptance of plans prior to
installation. Required design concentrations vary from agent to agent and depending upon maximum design parameters, the
concentration may vary among system manufacturers. The design concentrations listed by the system manufacturers are generally
accepted in electrical/electronic hazards, i.e. computer, telecommunication areas, provided that Class A ordinary combustibles are
kept to a minimum, thereby minimizing the potential for a deep seated Class A fire.
System charging and recharging shall be done only by the manufacturer or a FM Approved representative.
The Clean Agent systems FM Approved under this classification have been addressed by NFPA 2001, Standard on Clean Agent
Extinguishing Systems, 1994 Edition and must be listed in the United States Environmental Protection Agency (EPA) Significant New
Alternatives Policy (SNAP) as an acceptable substitute to Halon 1301.
Jurisdictions outside the United States may not recognize NFPA and EPA sanction of certain clean agents. Local and national
governmental regulations should be consulted prior to agent selection.
*Alternative to Halon 1211 and Halon 1301.

SFFECO 360 PSI Engineered HFC-227ea Fire Extinguishing System


System Designation: 360 PSI HFC-227ea
System Type: Engineered Clean Agent Fire Extinguishing System
Agent Identification: HFC-227ea
Minimum and Maximum Agent Storage Balanced Systems: 32 to 122ºF (0 to 50ºC)
Temperatures: Unbalanced Systems: 60 to 80ºF (16 to 27ºC)
Types of Nozzles Available: 180°, 360°
Minimum and Maximum Nozzle Heights: 1.0 to 16.0 ft (0.33 to 4.87 m)
360°: 1600 ft² (148.65 m²); Maximum Radial Coverage (Distance to Farthest
Maximum Area of Coverage for Nozzle Corner): 28.28 ft (8.62 m)
Type: 180°: 1600 ft² (148.65 m²); Maximum Radial Coverage (Distance to Farthest
Corner): 44.72 ft (13.63 m)
Minimum Design Concentrations for Hazard Class A: 6.96%
Class: Class B: 8.71% (for liquids other than heptane, see system manual)
Flow Calculation Software: Sffeco Flow Calculation Software SFF_v4.00.857.467
Sffeco Engineered HFC-227ea (360 PSI) Clean Agent Fire Suppression System
Design, Installation, Operation, and Maintenance Manual, SF-90225-D, Rev 0.0,
Design, Installation, Operation, and
April 1st, 2021
Maintenance Manual(s):
Sffeco Clean Agent HFC-227ea Fill Manual, SF-92221-FM Rev 0.0, April 1st 2021
Limitations or Exceptions to Approval: Limitations as defined in the software and manuals listed above

© 2007-2021 FM Approvals. All rights reserved. Page 1 of 2


Saudi Factory for Fire Equipment Co
2nd Industrial Area Al-Kharj Rd
Approved Filling Stations: Po Box 58469
Riyadh, 11515
Saudi Arabia

Company Name: Saudi Factory for Fire Equipment Co


Company Address: 2nd Industrial Area Al-Kharj Rd, PO Box 58469, Riyadh 11515, Saudi Arabia
Company Website: http://sffeco.com
New/Updated Product Listing: Yes
Listing Country: Saudi Arabia
Agent Type: HFC-227ea
Certification Type: FM Approved

© 2007-2021 FM Approvals. All rights reserved. Page 2 of 2


CERTIFICATE OF COMPLIANCE
Certificate Number 20140505-EX15997
Report Reference EX15997-20140219
Issue Date 2014-MAY-05

Issued to: SAUDI FACTORY FOR FIRE EQUIPMENT CO


2ND INDUSTRIAL AREA, AL-KHARJ RD
PO BOX 58469, RIYADH, 11515, SA

This is to certify that Clean Agent Extinguishing System Units


representative samples of SF-90225-DS

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 2166 - Standard For Halocarbon Clean Agent


Extinguishing System Units
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Listing Mark should be considered as being covered by UL's
Listing and Follow-Up Service.
The UL Listing Mark generally includes the following elements: the symbol UL in a circle: with the
word “LISTED”; a control number (may be alphanumeric) assigned by UL; and the product category
name (product identifier) as indicated in the appropriate UL Directory.

Look for the UL Listing Mark on the product.

William R. Carney, Director, North American Certification Programs

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at www.ul.com/contactus

Page 1 of 1
CERTIFICATE OF COMPLIANCE
Certificate Number 20140505-EX15997
Report Reference EX15997-20140218
Issue Date 2014-MAY-05

Issued to: SAUDI FACTORY FOR FIRE EQUIPMENT CO


2ND INDUSTRIAL AREA, AL-KHARJ RD
PO BOX 58469, RIYADH, 11515, SA

This is to certify that Clean Agent Extinguishing System Units


representative samples of SF-92221-FM

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 2166, Halocarbon Clean Agent Extinguishing System


Units
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Listing Mark should be considered as being covered by UL's
Listing and Follow-Up Service.
The UL Listing Mark generally includes the following elements: the symbol UL in a circle: with the
word “LISTED”; a control number (may be alphanumeric) assigned by UL; and the product category
name (product identifier) as indicated in the appropriate UL Directory.

Look for the UL Listing Mark on the product.

William R. Carney, Director, North American Certification Programs

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at www.ul.com/contactus

Page 1 of 1
12/5/23, 2:24 PM GAQF.EX15997 - Clean-agent Extinguishing System Units | UL Product iQ

Clean-agent Extinguishing System Units

COMPANY

SAUDI FACTORY FOR FIRE EQUIPMENT CO


2ND INDUSTRIAL AREA
AL-KHARJ RD
PO BOX 58469
RIYADH, 11515 Saudi Arabia

EX15997

View model for additional information

Engineered, Halocarbon, System Units(s): FK-5-1-12 engineered extinguishing system units, 500 psig

Engineered, Halocarbon, System Units(s): HFC-227ea engineered extinguishing system units, 25 bar

Engineered, Halocarbon, System Units(s): HFC-227ea engineered extinguishing system units, 360 psig

Engineered, Halocarbon, System Units(s): HFC-227ea engineered extinguishing system units, 360 psig

Engineered, Halocarbon, System Units(s): HFC-227ea engineered extinguishing system units, 42 bar

Engineered, Halocarbon, System Units(s): SFFECO Prime 227, HFC-227ea engineered extinguishing system
units incorporating Chinese GB5100/2011 CCCF storage containers, 610 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime 227, HFC-227ea engineered extinguishing system
units incorporating DOT/TC storage containers, 360 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime 227, HFC-227ea engineered extinguishing system
units incorporating DOT/TC/TPED/TR CU/ISO storage containers, 360, 610, or 725 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime 227, HFC-227ea engineered extinguishing system
units incorporating INDIA PESO/IS storage containers, 360, 610, or 725 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime 227, HFC-227ea engineered extinguishing system
units incorporating UN/TC/TPED/TR CU/ISO storage containers, 360, 610, or 725 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime 227, HFC-227ea engineered extinguishing system
units incorporating UN/TPED/ISO storage containers, 360, 610, or 725 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime 227, HFC-227ea engineered extinguishing system
units incorporating UN/TPED/TR CU/ISO storage containers, 360, 610, or 725 psig

https://iq.ulprospector.com/en/profile?e=6071534 1/2
12/5/23, 2:24 PM GAQF.EX15997 - Clean-agent Extinguishing System Units | UL Product iQ

Engineered, Halocarbon, System Units(s): SFFECO Prime 227, HFC-227ea engineered extinguishing system
units incorporating UN/TPED/TR CU/ISO/DOT/TC storage containers, 360, 610, or 725 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime FK, FK-5-1-12 engineered extinguishing system
units incorporating DOT/TC storage containers, 360 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime FK, FK-5-1-12 engineered extinguishing system
units incorporating DOT/TC/TPED/TR CU/ISO storage containers, 360, 610, or 725 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime FK, FK-5-1-12 engineered extinguishing system
units incorporating INDIA PESO/IS storage containers, 360, 610, or 725 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime FK, FK-5-1-12 engineered extinguishing system
units incorporating UN/TC/TPED/TR CU/ISO storage containers, 360, 610, or 725 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime FK, FK-5-1-12 engineered extinguishing system
units incorporating UN/TPED/ISO storage containers, 360, 610, or 725 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime FK, FK-5-1-12 engineered extinguishing system
units incorporating UN/TPED/TR CU/ISO storage containers, 360, 610, or 725 psig

Engineered, Halocarbon, System Units(s): SFFECO Prime FK, FK-5-1-12 engineered extinguishing system
units incorporating UN/TPED/TR CU/ISO/DOT/TC storage containers, 360, 610, or 725 psig

Pre-Engineered, Halocarbon, System Units(s): HFC-227ea pre-engineered extinguishing system units,


240/360 psig

Pre-Engineered, Halocarbon, System Units(s): HFC-227ea pre-engineered extinguishing system units,


240/360 psig
Last Updated on 2023-10-27

The appearance of a company's name or product in this database does not in itself assure that products so identified
have been manufactured under UL Solutions' Follow - Up Service. Only those products bearing the UL Mark should
be considered to be Certified and covered under UL Solutions' Follow - Up Service. Always look for the Mark on the
product.

UL Solutions permits the reproduction of the material contained in Product iQ subject to the following conditions: 1.
The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in
their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement
"Reprinted from Product iQ with permission from UL Solutions" must appear adjacent to the extracted material. In
addition, the reprinted material must include a copyright notice in the following format: "©2023 UL LLC."

https://iq.ulprospector.com/en/profile?e=6071534 2/2

You might also like