a) Clamp connector to accommodate a minimum range of conductor sizes from Number 8 solid
through Number 2 stranded, AWG; or
b) Threaded stud with 3/8 in x 16 or 1/2 in x 13 threads suitable for bolting directly to bus bars; or
c) Threaded stud with M12 or M16 (metric) threads suitable for bolting directly to bus bars.
Minimum insulation
BIL (kV) creepage distance Withstand test voltage a
50 Hz or 60 Hzb 50 Hz or 60 Hzb
dry wet Impulse
1 min, 10 s, 1.2/50 µs
mm inches
kV, rms kV, rms full wave kV crest
30 51 2 10 6 30
75 140 5.5 27 24 75
95 250 10 35 30 95
Single-bushing outdoor capacitors shall have the bushing terminal as specified under 6.6.1 and the case shall
have a suitable connection point as the other terminal.
Indoor capacitors shall be provided with terminals consistent with current-carrying requirements in NFPA
70.
A bushing, cable, or conduit entrance shall be provided for outdoor metal-enclosed capacitor equipment
rated above 600 V.