Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/3838009

The design of a compact pulse transformer

Conference Paper · February 1999


DOI: 10.1109/PPC.1999.823610 · Source: IEEE Xplore

CITATIONS READS

12 1,639

8 authors, including:

James C Dickens John Mankowski


Texas Tech University Texas Tech University
461 PUBLICATIONS 3,204 CITATIONS 176 PUBLICATIONS 996 CITATIONS

SEE PROFILE SEE PROFILE

David Garcia-Sanoguera
Universitat Politècnica de València
129 PUBLICATIONS 3,203 CITATIONS

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Investigation of Plasma in Pulsed High-Current Electron Sources and High Power Microwave Devices View project

Multichannel Signal Synthesis View project

All content following this page was uploaded by James C Dickens on 29 May 2014.

The user has requested enhancement of the downloaded file.


THE DESIGN OF A COMPACT PULSE TRANSFORMER
J. ZHANG+, J. DICKENS, M. GIESSELMANN, J. KIM, E. KRISTIANSEN
J. MANKOWSKI, D. GARCIA, M. KRISTIANSEN
Pulsed Power Laboratory, Departments of Electrical Engineering and Physics
Texas Tech University, Lubbock, Texas, TX 79401-3 102, USA
’ Permanent address: Applied Physics Department, National University of Defense Technology, Changsha, 4 10073,
Hunan, China

Abstract

To improve the pulse shape and to obtain I.LSorder pulse basically uses a chamber with a diameter of 20 cm, our
duration on a diode load in an inductive energy storage transformer diameter is chosen not to exceed 20 cm.
system, an oil-submerged compact pulse transformer with Under such limitations of the transformer, we need a high
diameter of 20 cm and length of 70 cm has been designed coupling coefficient, the capability of withstanding 500
and tested. From theoretical calculations, the parameters kV voltage for more than 100 ns in the secondary, and the
with primary inductance b=3.4 pH, secondary mechanical force produced by the 130 kA primary current
inductance L,=90 pH, and coupling coefficient K=0.772 for more than 10 ks.
are obtained. To prevent breakdown, a conic secondary Based on the above considerations, a transformer with the
design is adopted. Under the condition of 500 kV structure shown in Figure 1 has been designed.
operation voltage, the maximum electric field in the
transformer is 205 kV/cm (in oil). The axial voltage B. Calculation of the Inductance and Coupling
distribution on the secondary is linear. Experiments have Coeflicient
been done to test the insulation, the mechanical force and
the coupling coefficient. The test results are consistent
By use of the inductance calculation formulas from Ref.
with the design parameters.
[l] and Ref. [2], the results obtained on the basis of the
given geometrical parameters of the transformer are
I. THE DESIGN OF THE TRANSFORMER shown in Table I.

A. Design Consideration C. Calculation Of Mechanical


On account of our energy source with a capacitor of 17 Strength
pF and a maximum voltage of 45 kV, and of our load
with more than ten R impedance requiring more than ten To estimate the possible damage due to the mechanical
kA current, 200 kV or so voltage, and -pS pulse duration, force resulting from the intense pulse current, we
we choose the primary inductance as 2-4 lH, the calculated the strain produced by the forces between the
secondary inductance as 70-90 PH. and the turn ratio turns of the primary, between the turns of the secondary,
around 5. Here is presented the calculation of the strain resulting
Since our exoerimental device for oulse conditioning from the repulsive force between the primary and the
L 1 v
secondary, which is the most severe one.
I

Helical Windina Transformer


mm I

Figure I. Transformer Structure.

~780?&490-2fS%l$10.~1999 IEEE. 704


Table I. Transformer Geometric Parameters, Inductance and Coupling Coefficient and between the primary and the
secondary.
Primary Parameters 1 Secondary Parameters ) Mutual Parameters 1
R,--Radius of ( 9cm RsL-Large Radius of ( 8cm ) M---Mutual
Primary Coil Secondary Coil Inductance
Rss-Small Radius of 6cm
Secondary Coil
Len,---Length of 50 cm Lens,---the Cylindrical 11.16cm M
Primary Coil Section Length of K=
Secondary Coil (L&p )o.5
Lensz---the Conic Section 40.64 cm ---Coupling
Length of Secondary Coil Coefficient
N,---the Turn 8 Ns---the Turn Number of 50
Number of Primary Secondary Coil N= (+)” ___
Coil
L,---the Inductance 3.4 pH Ls---the Inductance of 90.52 j.tH Turn Ritio
of Primary Secondary

According to Ref.[3], for two parallel coils, the force per F=5.279.16Newton. (5)
unit length on coil 1 from coil 2 is
Two polyethylene tubes with a thickness 0.9 cm and 1.5
dF - (PO)412
--
cm are put outside the primary coil to provide the
(1) mechanical support, and the axial cross section of the two
dP 21t 1 tubes withstands most of the mechanical force.
Taking the force with 10 ps duration and the material
where, I,, 12 are the currents in coil 1 and coil 2, Young’s modulus of polyethylene tubes into account, we
respectively; I is the distance between coil 1 and coil 2; get the strain, 0.01245%. According to Ref. [4], the yield
and dp is the line element on the coil I. In our case, all the point of steel is approximately a strain, 0.1%. Usually,
turns on primary and secondary are approximately polyethylene is more flexible than metal. Therefore,
parallel. Then, the repulsive force on the primary is such a design is safe for mechanical force.

D. Calculation of Breakdown Electrical


Strength and Voltage Distribution on the
(2) Secondary.

Since the secondary and primary of the transformer are


where, dl,, dlz are the integrating element along the axes coaxial and since the voltage on the primary is much
of the primary and the secondary, and d@ is the lower than that on the secondary, we can take the coaxial
integrating element along the angular direction of the transmission line approximation and assume the primary
primary, and RP is the radius of the primary coil, as ground. When we put the voltage U on the secondary,
respectively. the maximum electrical field appearing at the high voltage
By designating the average radial distance between end is
primary and secondary as

R,,,= $- RsL+ RssI


&lx= u ,
r,
(3)
2 (6)
where RsL, and Rss are the large radius and small radius
of the secondary coil shown in Table I, the interaction Rss
lnt;
Rp
3s
>
distance is
Setting U=500 kV, Rss=6 cm, and R,=9 cm. we get the
practical maximum electrical field in the transformer:
(4) E,,,=205 kV/cm
where I,, Ez are the integrating element axial position of According to the Martin Formula Is’ of transformer oil
breakdown, we have
the primary and the secondary, respectively.
Taking a sinusoidal current waveform into account, when
the primary current I ,=I35 kA, the secondary current Eb=0.48(MV/cm) ii~3Ao~07s (7)
Is=20 kA, we get the mechanical repulsive force on the where, t (j.ts) is the time that the pulse is above 63% of
primary peak voltage and A (cm’) is stressed area. In our case,

705
t=O. Ius and A=185.354cm2. then we get Et,=699 With an HP 4263B LCR meter at 100 kHz frequency,
kV/cm. From this point of view, the breakdown we measured the primary inductance, the secondary
electrical field is much bigger than the practical inductance and the coupling coefficient. The results are
electrical field in the transformer. Lp=3.46pH, Ls=86 pH, and K=0.755.

In many cases, the voltage distribution on the B. Measurement of the Voltage Distribution
transformer secondary is exponential. The equivalent on the Secondary
circuit for the secondary voltage distribution is shown
in Figure 2. In the figure, Lsi and C,i represent the With a Tektronix FG504 40 MHz Function Generator,
inductance and capacitance between two turns, and C,i we put a 100 kI-Iz sinusoidal signal on the secondary
is the capacitance between one turn of the secondary assembled together with the primary. Then, we used a
and the primary or ground; in our case, C,i-1.5 pF, Tektronix TD360 two-channel, digital, real-time
Csi-6.2 pF, L,i-1.8 pH. When the upper frequency oscilloscope to monitor the voltage difference from
from the fuse interruption is ~6.28.10~ radian/s, the each turn to one end, one by one. Since we cannot put
impedance from stray capacitance are much larger than the probe too far inside, we measured 10 turns on the
that from the inductance between turns. Consequently, high voltage end. In Figure 3, Series 2 reflects the
the voltage distribution on the secondary is only measurement; Series 1 results from the calculation
dependent on inductance between turns instead of stay based on a linear voltage distribution assumption. From
capacitance. In other words, the distribution is linear. this figure, we can see that the difference is so little that
we can take the practical voltage distribution on the
II. MEASUREMENT AND TEST secondary as being linear.

A. Measurement of Inductance and Coupling


Coeficien t

cg50 A cg49 A Cg48I Cgi+l I I Cgi I Cgiil AI cg3 AI cg2 I I Cgl I I


-I- T T T T T T T T
csx! cs49 Cs48
It :: tt !I It !! Cs,’ :: Ly :! LsTyii;y-~

Ls50 Ls49 Ls48 Lsi+l

Figure 2. the Equivalent Circuit for Secondary Voltage Distribution

30

25

20

15

10

0
14 7 10 13 16 19 22 25 26 31 34 37 40 43 46 49

Figure 3. The Secondary Voltage Distribution, the Series 2 is from measurement, the Series 1, from the calculation
based on a linear voltage distribution assumption.

706
c. Test of the Transformer 100 ns and a mechanical force resulting from 110 kA
primary current and 20 kA secondarycurrent within lops.
After submerging the transformer in transformer oil, we
used a 17 pF capacitor with a charging voltage 20 kV to
test it. The oscilloscope trace of the transformer test is REFERENCE
shown in Fig.4, which is from the measurementusing the
Pearsoncurrent monitors (models 1423 and 4418). From [I] F.W., Grover, Inductance Calculation, Dover
this figure, we find that the primary current is 57.6 kA, Publications, Inc., N.Y., 1973,p. 105.
the secondary current is 8.2 kA. On the basis of the 121 F.W., Grover, Inductance Calculation, Dover
measurement, we get the coupling coefficient 0.722. Publications, Inc., N.Y., 1973, p.122.
Compared with that measured with HP 4263B LCR [3] R.M.,Whitmer, Electromagnetics, 2”d ed., N. J.:
meter, the coupling coefficient is a little bit small. The Prentice-hall, Inc., Englewood Cliffs, 1962, p. 144.
difference possibly results from the loop discharge [4]John Wiley, Applied Mechanics, Vol.2, p.15.
resistance relative to intense discharge current. Such a [5] R.J., Adler, Pulse Power Formulary, North Star
test shows that the transformer has as good a performance ResearchCorporation, 1991, p.2 1.
as expected.

III. SUMMARY ACKNOWLEDGMENT


On the basis of design considerations, we built a compact This work was solely funded by the Explosive-Driven
pulse transformer. Calculations, measurementsand tests Power Generation MURI program funded by the Director
show that, hopefully, such a transformer with the primary of Defense Research & Engineering (DDR&E) and
managed by the Air Force Office of Scientific Research
inductance of 3.4 pH, the secondaryinductance of 86 pH,
(AFOSR)
and the coupling coefficient of 0.75 has the capability to
withstand 500 kV high voltage on the secondary within

Saved: 03 JUN 1999 15:41:55

+-Primary Current, 12.8 kA/div 1

bacitorVoltage, 4 kV/div+ 1 I *Secondary Current,


12.8 Wdiv

. Figure 4. The Oscilloscope Trace of the Transformer Test

707

View publication stats

You might also like