Procedure - Testing of PRV R00
Procedure - Testing of PRV R00
DOCUMENT NO.:
WCP-TIS-PRV-PR-01-24
WO.No:- REV.
PT WIRA CIPTA
PERKASA PO.No : 2403-116 00
Revision : 00
ACEH
Date : 07-Mar-24
COMMENT SHEET
Incorporated
Rev Section Page Comment (Y/N) Description
Revision : 00
ACEH
Date : 07-Mar-24
TABLE OF CONTENTS
Revision : 00
ACEH
Date : 07-Mar-24
1. INTRODUCTION
This work is carried out to support the main work, namely Jasa Rental Gas Booster Compressor
Cluster IV PGE Aceh carried out by PT Wira Cipta Perkasa. Where the procurement of Pressure
Reducing Valve (PRV) requires unit testing before the goods are sent to the work site.
3. EQUIPMENT TESTED
The equipment/equipment tested as follow:
Pressure Reducing Valve (PRV)
Size: 4 Inch
Class: 300#
Brand: Argos
Quantity: 1 Unit
4. TESTING EQUIPMENT
The equipment used for testing shall conform to the manufacturer's recommendations. The Contractor
shall ensure all testing equipment is in good working order before any testing work is carried out.
5. TEST PROCEDURE
The PRV testing process is according to the following steps:
c. Verify if the restrictor installed in the pilot inlet, loading sensing line, is opened between 30%~70%.
d. Open SLOWLY AND GRADUALLY the inlet ball valve of skid, or when skid is adopted of by-pass
in the ball valve utilize it pressurize the stream.
e. As there is no pressure upstream the regulator the slam shut valve is blocked (fail close type).
Keep the by-pass or push button (located in the SSV body) to pressurize the line between the slam
shut valve and the pressure regulator.
f. Still pressing the by-pass or push button of slam shut valve; turn slowly the regulating screw of
pilot of regulator in order to allow a low pressure. Utilize the gauge to check the pressure increase
and adjust the regulator set point up to 20% of low set point of slam shut valve.
Revision : 00
ACEH
Date : 07-Mar-24
g. Since the actuator of slam shut valve is already pressurized release the by-pass or puss button to
reset the actuator.
h. Reset the obturator of slam shut valve using the respective lever.
i. Open the vent valve around 20% and check if set point keeps adjusted.
j. Turn the regulating screw clockwise to increase the outlet pressure to achieve desired set point.
k. If the pressure is oscillating use the restrictor.
l. Once the pressure is adjusted open the vent valve and check the set point.
m. After adjusted the set point close the vent valve and check lock up of regulator.
n. Verify the leak in connectors and other fittings.
o. Open SLOW AND GRADUALLY the outlet ball valve to start the stream operation.
p. If necessary, make thin adjustment using the regulating spring of pilot.
6. CHECK LIST
The check list for this activity can be seen in Appendix-1.
7. CLOSING
After the activity is well underway, the relevant parties can prepare a work completion report
signed by the relevant parties.