Professional Documents
Culture Documents
Esercizi Svolti in Classe
Esercizi Svolti in Classe
Esercizi Svolti in Classe
d y (t )
5 + 4 y (t ) = 2
dt .
y (0) = 1
______________________________
d 2 y (t ) d y (t )
2
+5 + 6 y (t ) = 1
dt dt
y (0) = 1 .
y (0) = 0
______________________________
The process of drug ingestion, distribution and subsequent metabolism in an individual may be
represented by the simplified block diagram shown in the figure.
A simplified mathematical model for the process is made of the following differential equations:
d x1
= u − k1 x1
dt
d x2
= k1 x1 − k 2 x2
dt
where all variables are in deviation form and:
• x1 = drug mass in the gastrointestinal tract (GIT);
• x2 = drug mass in the bloodstream (BS);
• u = drug ingestion rate.
k1 and k2 are positive constants representing physiological properties of the individual in question,
and in general will neither be equal in a single subject, nor across subjects.
Obtain the expression of the transfer function relating the drug mass in the bloodstream to the drug
ingestion rate.
dT
Mc P = wc P (Ti − T ) + he S e (Te − T )
dt
,
d Te
M e c P ,e = Q − he S e (Te − T )
dt
1
𝑤𝑤𝑐𝑐𝑃𝑃 1
𝑇𝑇 ′ (𝑠𝑠) = 𝑄𝑄 ′ (𝑠𝑠) + 𝑇𝑇𝑖𝑖 ′(𝑠𝑠)
𝜌𝜌𝜌𝜌 𝜌𝜌𝜌𝜌
𝑤𝑤 𝑠𝑠 + 1 𝑠𝑠 + 1
𝑤𝑤
The measurement sensors (e.g., thermocouples and resistance temperature detectors) used industrially
to measure process temperatures are usually inserted in a thermowell (or thermal well) to protect them
from the process fluid and to be able to remove them for maintenance also when the process is in
operation. The process fluid transfers heat to the thermowell wall, which in turn transfers heat to the
sensor. A schematic of the installation of a measurement sensor is shown in the figure along with the
picture of some thermowells.
Thermal wells are typically made of metal or ceramic. The system “measurement sensor +
thermowell” has its own dynamics.
Parameter values
V = 5 m3; α = 12; q = 0.05 m3/min; k = 0.04 min−1; θ1 = 0.9 min; θ2 = 1.1 min.
It is required to select from a catalogue the control valve to be installed in the circuit shown in the
figure.
FI
The pump furnishes a constant head of 2.7 bar over the entire range of flows of interest. The pressure
drop in the line (excluding that in the valve) can be assumed equal to the pressure drop across heat
exchanger only, and is proportional to the square of the volumetric flowrate.
Under nominal conditions, 45 m3/h of liquid water at room temperature must flow in the circuit. At
these conditions, the pressure drop across the heat exchanger is equal to 2 bar.
Determine an appropriate value for the valve Cv and plot the installed valve characteristic for the
following cases:
a. a linear valve that is half-open at the design condition;
b. an equal percentage valve (R = 50) that is sized to be completely open at 110% of the nominal
flowrate;
c. same as in (b), except with a Cv that is 20% greater than calculated;
d. same as in (b), except with a Cv that is 20% smaller than calculated.
____________________________________________________
(Solution)
2.0
50
volumetric flowrate (m3/h)
linear
valve gain [(m3/h) / %]
40 Kv = 105 1.5
linear
Kv = 105
30 equal %
1.0
equal %
20
0.5
10 Kv = 75
95 Kv = 75
115 95 115
0 0.0
0.0 0.2 0.4 0.6 0.8 1.0 0 20 40 60 80 100
lift lift (%)
Adapted from SEMD4 – Example 11.2 p.183 and Example 11.3 p.184
Determine the closed-loop response to a unit step change in the set-point for three values of the
controller gain: Kc = 1, 2 e 5.
For the same controller gain values, find the closed-loop response and the offset resulting from a
disturbance step increase of 0.05 m3/min.
Consider the feedback control system shown in the figure, where Gv = K v , Gm = 1 , and
G p = K p /(τ p s + 1) , with τp > 0.
___________________________________________________
The system shown in the previous example is characterized by the following transfer functions:
1 1
Gp = , Gv = , G m = 1 , Gc = K c .
5s + 1 2s + 1
___________________________________________________
10 s 3 + 17 s 2 + 8s + 1 + K c = 0 .