Professional Documents
Culture Documents
Electrical Maintenance Manual Chapter 1
Electrical Maintenance Manual Chapter 1
Introduction
Lesson Page
1. Basic principles. 1-3
Content
2. Electrical tests. 1-6
3. Team testing. 1-8
Electrical maintenance
Definition
They are those preventive, corrective, predictive actions that are carried out to
improve the physical conditions of electrical equipment and thus extend its useful
life.
Advantages
It allows you to recognize the factors that cause the deterioration of electrical
equipment.
Repairs and minimizes failures and interruptions.
Consequences
Good electrical maintenance brings benefits, among them are:
Lower repair cost.
Reduction of unforeseen equipment stops.
Minimizes risks due to accidents to people and equipment.
Increased productivity.
Timely location of deficiency in the systems.
Technical Requests
Technical requirements are the technical specifications recommended by the
manufacturer and/or maintenance organization, and include the following
elements:
Equipment registration.
Preventive maintenance plan.
Instructions and procedures.
Repairs.
Failure analysis.
Component Description
It is necessary to have data on the electrical system
that can include unified diagrams, short-circuit
Equipment studies, coordination of protections, installation and
registration control diagrams, as well as other data that can be
used as a reference point for future maintenance.
Maintenance Tests
They are aimed at verifying, through tests, the correct operation and nominal
characteristics of electrical equipment and instruments.
The main condition for the application of electrical tests is the condition and
availability of the electrical equipment within the installation.
The following types are identified:
Acceptance.
Routine maintenance.
Special maintenance.
Acceptance Test
They are a series of tests recommended by the manufacturer, installers and
maintainers, on newly installed electrical equipment and instruments, before being
definitively delivered for normal operation. Take into account equipment
specifications and approved installation standards
out maintenance (beginning tests and ending tests). Its purpose is to evaluate the
possible deterioration of the equipment from the last maintenance intervention, to
the present, and the improvements obtained with the new action or intervention.
This makes it easier to reschedule maintenance.
The equipment on which this type of tests are carried out are those electrical
equipment that intervene in the generation, transmission and distribution of
electricity and process plants in general. These types of tests should be performed
at voltage levels equivalent to a maximum of 60% of factory tests or less
It applies to electrical power equipment or control systems and the test voltage
levels are those recommended by the department or evaluation committee.
This type of tests determine the physical integrity of the insulating materials and
the operating condition of the equipment involved. It is applied during maintenance
and evaluations due to failures or operational causes.
It consists of applying a voltage (DC) to the insulating medium and determining the
leakage current. Its purpose is to determine the physical integrity of the insulating
medium of the equipment.
The equipment and instruments involved are those of the electrical power system
(generators, transformers, motors, switches, insulators, cables, etc.).
Test voltage levels take into account the nominal operating voltage levels of the
equipment.
Note:
1. Tests with direct current are more recommended than those carried out with
alternating current, because they provide more information, which allows
comparisons to be made with previous tests.
2. Tests with alternating current are generally good or bad tests, without indicating
the safety margin with which the current passes.
3. Tests with direct current are preferable in equipment where the capacitive effect
is very high, such as cables. These are considered non-destructive .
where f = 0
Capacitive
Current where:
E = Nominal voltage of the equipment.
R = Ohmic resistance of the winding.
I = Capacitive charging current.
e = Base natural logarithms.
r = Insulator resistance in .
c = Capacitance in farads.
t = Time in seconds.
Dielectric At the beginning of the test this current is high, but it decreases
absorption
over time; Therefore the test reading should be taken and
current
recorded when the current stabilizes.
Volumetric It is the one that originates within the insulating material and the
charging
one that is interesting to evaluate, because it indicates its
current
physical condition.
The following graph shows the effects of the test application, caused by the use of
high DC voltage in an insulating system.
This test is carried out by applying voltages ranging from 100 volts to 10,000 volts,
using operating instruments: manual, motorized and/or electronic, which generate
the desired voltage and measure the electrical resistance of the material in mega-
ohms.
With the results obtained, the degree of deterioration of the insulating material of
the machine, device or equipment is evaluated, since these are indicative of the
existing contamination and how dangerous it can be to continue using the machine
without maintenance.
If the index obtained is below 1.25, it warrants investigation, that is, other tests and
evaluations are carried out.
If the polarization index is 1.5 or less than the equipment under test, it must be
investigated.
Spot Test
This test is very important and should be recorded each time it is performed, to
compare it with successive and previous tests.
Readings should be taken within one minute of starting the test or when the
instrument's indicator needle has stabilized. This test must always refer to 20º C for
transformers and 40º C for motors.
There are specific (international) tables and graphs of acceptance test values for
different equipment, although maintenance departments usually have their own
acceptance criteria.
For rotating machines, the minimum insulation resistance according to (IEEE) must
be 1000 for each volt (equipment operating voltage), plus 1 M .
Temperature Transformer
ºC In oil Dry
0 0.25 0.40
5 0.36 0.45
10 0.50 0.50
15 0.75 0.75
20 1.00 1.00
25 1.40 1.30
30 1.98 1.60
35 2.80 2.05
40 3.95 2.50
45 5.60 3.25
50 7.85 4.00
55 11.20 5.20
60 15.85 6.40
65 22.40 8.70
70 31.75 10.00
75 44.70 13.00
80 63.50 16.00
According to IEEE, in the case of electric motors it is important that the test be
corrected to 40º C. The correction is carried out according to the formula:
RC = Kt x Rt
where:
Rc = Corrected insulation resistance at 40º C (in M ).
Rt = Insulation resistance (M ) measured at temperature t.
Kt = Temperature coefficient for insulation resistance at temperature t.
The following graph gives the values of the insulation resistance coefficient Kt
according to the variation in temperature for rotating machines.
Approximate variation of insulation resistance with temperature for rotating machines (ANSI/IEEE
Std 43 – 1974)
Overvoltage Test
The overvoltage test is one that is carried out with direct current, equivalent to the
nominal voltage of the equipment involved multiplied by 1.41.
The test is carried out the same as the previous one, recording the leakage
currents or the insulation resistance, depending on the instrument.
The equipment and instruments to which this type of tests are applied are electrical
power systems (cables, generators, transformers, bushings, switches).
This test is of the destructive type. Its use is recommended in cases where the
equipment must be completely reliable, or where it is certain that the equipment or
sample cannot be saved through maintenance. In practice it is applied to define
failures of cables submerged in water.
The equipment and instruments to which this type of tests are applied are
transformers and switches immersed in oil. For power factor testing, voltage levels
range from 2500 volts to voltages that may be greater than 50 kilovolts.
The equipment and instruments to which these tests are applied are the protection
relays of electrical equipment (generators, motors, transformers, power lines,
cables); whose test voltage level and current are low; therefore they are generally
not considered.
The equipment under study are the grounding electrodes and the installation for
which the grounding was done (electrical substations, process plant equipment
such as: motors, transformations, instruments, among others). The volates applied
are low, coming from portable batteries installed in the measuring instruments.
The equipment to which the test is applied are the electrical generation,
transmission, electrical distribution and motor control center systems.
Incorporate closing and opening times into the coordination of electrical protections
and minimize damage to equipment caused by the electric arc.
The equipment to which this test is applied are power, medium and high voltage
switches; are not significant, very low voltage instruments are used.