* AUTO pwb (AUTO2 pwb/AUTO1 pwb) has several types of hardwares and softwares.
In some case, it requires to change the setting of Jumper(JP), Dip Switch(SW) and
Internal Data. Therefore please refer to this document when you replace AUTO PWB.
1) AUTO PWB has 3 types of LED driver hardware's pwb, and they need to use ther appropriate software.
It the 3 different pwbs can be identified by revision number as below table.
2) Also, the software has 2 types that Ver. 4.XX series and Ver. 5.XX series.
And these 2 types of software are incompatible.
a) Ver. 5.XX series is for type which Auto pilot connects with EC-8x00(NCT TCS) or FURUNO's ECDIS.
b) Ver. 4.XX series is for except above a).
!!! The Auto unit display becomes faulty indication when wrong software(ROM)
is installed to AUTO pwb. In most cases, it does not require to replace the
ROM which is installed on new AUTO pwb with other version.
If Ver.5.XX ROM was installed on original AUTO pwb, please install latest
Ver.5.XX ROM to new AUTO pwb. (Refer to below tables.)
* AUTO PWB [Type 2] release from 2005 ,AUTO PWB [Type 3] release from 2011
MMA Ver. 3.10(S) or before Ver. 3.10(T) or later Ver. 4.11 or later
PID Ver. 3.10(S) or before Ver. 3.10(T) or later Ver. 4.10 or later
Page 1
1) Setting of Internal data Confirm Internal data (at service mode) for new Auto PWB.
DATA 3
to AUTO PWB[Type 1] and AUTO PWB[Type 2,3] are same setting.
DATA 11
DATA 14
to AUTO PWB[Type 1] and AUTO PWB[Type 2,3] are same setting.
DATA 21
DATA 29
to Default setting is OK
DATA 40
(*): Please refer to the attached "PR-6000 Non-Volatile Memory Setting Table"
for new pwb and software.
Page 2
2) Auto2 PWB's Jumper setting Confirm Jumper setting for new Auto PWB.
Type [2]
Jumper Details Type [1]
Type [3]
Pilot type other than
1-2 SHORT
JP 1 Select of ADPT 12V PR-64xx/67xx
2-3("C") SHORT Pilot type is PR-64xx/67xx
Pilot type other than
1-2 SHORT
JP 2 Select of ADPT 0V PR-64xx/67xx
2-3("C") SHORT Pilot type is PR-64xx/67xx
OPEN Normal operation
JP 3 Reset of No.1 PID's CPU
SHORT CPU RESET
OPEN Normal operation
JP 5 Reset of No.2 PID's CPU
SHORT CPU RESET
OPEN Normal operation
JP 8 Reset of MMA's CPU
SHORT CPU RESET
1-2 OPEN NAV1: 1,200 to 19,200bps
Set of NAV port 1-2 SHORT NAV1: 1,200 to 38,400bps
JP 9 Baud
rate(*1) 3-4 OPEN NAV2: 1,200 to 19,200bps
3-4 SHORT NAV2: 1,200 to 38,400bps
OPEN TG-6000(9,600bps)
JP 10 Set of No.1 GYRO port
SHORT TG-8000(38,400bps)
OPEN TG-6000(9,600bps)
JP 12 Set of No.2 GYRO port
SHORT TG-8000(38,400bps)
OPEN ------
JP 15 Not in use at the moment
SHORT ------
OPEN Steering unhold
JP 16 set of steering hold
SHORT Steering hold ( *2 )
OPEN Buzzer volume low
JP 17 set of buzzer volume
SHORT Buzzer volume loud ( *3 )
(*1): If NAV1 and NAV2 options are not installed, please set JP9 same as above table.
Old autopilot, which was installed with AUTO pwb [Type 1], doesn't have steering hold
(*2):
function, however please short JP16.
(*3): If external buzzer was not installed on AUTO pwb, please open JP17.
The above mentioned "○" is default JP setting. Please set JP according to ship's specification.
Page 3
3) Auto PWB's Dip SW setting Confirm Dip SW swtting for new Auto PWB.
SW No. No. Function AUTO PWB [Type 1] Function AUTO PWB [Type 2,3]
Select of RC ON RCP PWB is installed
1 mode OFF RCP PWB is not installed
Select of ON RC-NAV (serial tyoe) mode is installed
2 RC-NAV mode OFF RC-NAV (serial tyoe) mode is not installed
Select of ON RC-RC (analog tyoe) mode is installed
3 RC-RC mode OFF RC-RC (analog tyoe) mode is not installed
SW 1
ON Error log display Select of ON for New PR-6000
4 Output Error log
serial I/O OFF
OFF Normal operation for Old PR-6000
Non-Volatile ON At factory use
5 memory coercion
insertion OFF Normal condition
Select self- ON Use self-diagnosis
6 diagnosis mode
OFF Normal condition
At factory use ON Factory use ON TG-8000(38,400bps)
1 this function OFF Normal operation
Gyro baud rate
OFF TG-6000(9,600bps)
SW 2
(PID/No.1) 2 Maximum rudder
(*1)
3 angle
SW 4
(PID/No.2) 4
Narrow rudder
5 angle
(*2)
6
1
SW 3
(PID/No.1)
2 Internal RATE (*3)
3
SW 5 ON ADPT function is installed
(PID/No.2) Select of
4 ADPT mode OFF ADPT function is not installed
(*3) 0 1 2 3 4 5 6 7
1 OFF ON OFF ON OFF ON OFF ON
2 OFF OFF ON ON OFF OFF ON ON
3 OFF OFF OFF OFF ON ON ON ON
Page 4
4) Table for serving of PR-6000 RATE, Automatic weather adjustment
SHIP TYPE
D.W.T
0 1 2 3 4 5 6 7 8
5,000 - 1 1 1 or 2 1 0 or 1
10,000 1 1 2 1 1
10,000 - 2 2 2 2 1 or 2
50,000 2 2 2 2 2
50,000 - 2 or 3 3 3 2 2 3 2
100,000 2 2 or 3 2 or 3 2 2 2 2
100,000 - 3 3 2 2 or 3
200,000 3 3 2 or 3 2 or 3
200,000 - 3 2 or 3 3
300,000 3 2 or 3 3
300,000 - 4
500,000 3
500,000 - 4
or more 3
Upper stage: Setting value for AUTO PWB SW3 and SW5 of RATE.
Lower stage: Setting value for non volatile RAM(DATA 5)of automatic weather adjustment step width.
[0] Container
[0]: [0] 0.2 deg/step
[0]: [0]:
[0] 1 - 15 sec
[1] Any
[1]: Lpp < 100m [1] 0.3 deg/step
[1]: [1] 10 - 30 sec
[1]:
[2] Tanker
[2]: Lpp > 250m [2] 0.4 deg/step
[2]: [2] 20 - 50 sec
[2]:
[3] Tanker
[3]: Lpp < 250m [3] 0.5 deg/step
[3]: [3] 40 - 80 sec
[3]:
Page 5
5) Auto PWB's connection Replace Auto pwb. The position of some parts have changed.
AUTO PUB
[Type 1]
No.1
No.1
No.2 No.2
Common
OPEN
AUTO PWB
[Type 2,3]
Page 6
6) OPERATION TEST Please confirm the operation in all modes (NFU, HAND, AUTO, RC)
NO.1 SYSTEM
PUMP MODE OPERATION REMARKS
NFU
HAND
NO.1
AUTO
RC
NFU
HAND
NO.2
AUTO
RC
NO.2 SYSTEM
PUMP MODE OPERATION REMARKS
NFU
HAND
NO.1
AUTO
RC
NFU
HAND
NO.2
AUTO
RC