ANCHORING RODS TO ROOF BRICK WITH
STANDARD CHINESE EYE

1 .- PARTITION INSULATED TO THE STRUCTURE

The structure of a building can have one of two types of partitions: partitions attached
to the structure or partitions isolated from the structure. The type of partition walls of a
building is defined by the design engineer in the conceptual part of the building
structure.

In the partition walls isolated from the structure, all the lateral and upper edges of the
walls are separated from the structural elements through the use of technopore sheets
or elastomeric sealant. This type of partition allows the walls, in their plane, to have no
interaction with the frames that frame them during an earthquake and to behave
independently.

Figure Nº 1 INSULATED PARTITION FROM THE STRUCTURE AND REINFORCEMENT RODS

Page 1
LUREN LACASA MINING
COMPANY
In the partition wall isolated from the structure, the vertical reinforcement steel rods are
anchored at the base of the wall in the concrete slab and at the top of the partition wall
the support is articulated using the STANDARD CHINESE EYE. For placement, the
slab is drilled with a drill and the STANDARD CHINESE EYE is glued to the concrete
with epoxy adhesive.

Figure Nº 2 SUPERIOR ANCHORAGE OF VERTICAL REINFORCEMENT RODS IN INSULATED


PARTITION WALLS

In ceilings with lightened plastered slabs, the case occurs in which the vertical rod “falls”
under a roof brick, so here you can also use the STANDARD CHINESE EYE that is glued
to the “brick + plastering” compound with epoxy adhesive. Drilling is also done with a drill
and a rotary hammer should never be used.

Figure Nº4 UPPER ANCHORAGE OF RODS TO ROOF BRICK IN INSULATED PARTITIONING

Page 2
LUREN LACASA MINING
COMPANY
2 .- ANCHORING RODS TO THE CLAY ROOF BRICK PLATED WITH STANDARD
CHINESE EYE.

To determine the ultimate shear load of the anchor, tests were carried out in the Anti-
seismic Structures Laboratory of the Pontifical Catholic University of Peru. Anchors
were tested with 8mm, 3/8” and 1/2” corrugated rods to industrially manufactured 8-
hole clay roof bricks. The plastering of the roof brick was 1cm thick and was done with
bagged FINE MORTAR FOR WALL PLAYING.

Figure Nº5 CLAY ROOF BRICK PLATED WITH STANDARD CHINESE EYE

With the results of the tests at the PUCP, a table of allowable shear loads was
prepared for anchoring ø8mm, ø3/8” and ø1/2” corrugated rods in clay roof brick with
1cm plastering using STANDARD CHINESE EYE.

Figure Nº 6 SHEAR TEST SPECIMEN


3 .- PARTITION INSULATED TO THE STRUCTURE WITH ANCHORING OF
VERTICAL REINFORCEMENT RODS TO THE CLAY ROOF BRICK LADED USING

Page 3
LUREN LACASA MINING
COMPANY
STANDARD CHINESE EYE

The following tables have been prepared with the allowable load values, following the
provisions of Standards E.030 and E.070 for building partitions.
TABLE 1: ANCHOR OF VERTICAL RODS TO ROOF BRICK LADDER WITH STANDARD
CHINESE EYE

First, identify if the wall is plastered or plastered on both sides and enter TABLE 1A or
TABLE 1B as the case may be.

Second, determine the heights of the partitions shown in the architectural plans, for
each of them see in the corresponding table the type of silico-calcareous plates P-7, P-
10, P-12 or P-14 to be used.

Third, once the type of plate to be used has been established, see the diameter and
spacing of the vertical reinforcement rods required for that height and thickness of the
finished wall.

Page 4
TABLE 1
ANCHORING VERTICAL RODS TO LADRED ROOF BRICK WITH STANDARD CHINESE EYE
Aug-15

TABLE 1A: PARTITION WALLS WITH BOTH SIDES PLASTED

ISOLATED PARTITIONS IN APARTMENT, OFFICE AND HOTEL BUILDINGS


With P-7 plate With P-10 plate With P-12 plate With P-14 plate
WALL TYPE
Wall height "H" Vertical reinforcement spacing Wall height "H" Vertical reinforcement spacing Wall height "H" Vertical reinforcement spacing Wall height "H" Vertical reinforcement spacing
H max = 3.20m 1/2"@102cm or 3/8"@76.5cm

H max = 2.80m Ø3/8"@102cm H max = 3.20m Ø3/8"@76.5cm


Interior insulated H max = 3.40m 3/8"@76.5cm
walls H max = 2.45m Ø8mm@76.5cm

H max = 3.10m Ø3/8"@76.5cm H max = 3.50m Ø3/8"@51cm H max = 3.90m 1/2"@76.5cm or 3/8"@51cm

TABLE 1B: PARTITION WALLS PLATED ON BOTH SIDES

ISOLATED PARTITIONS IN APARTMENT, OFFICE AND HOTEL BUILDINGS


With P-10 plate With P-12 plate With P-14 plate
WALL TYPE
Wall height "H" Vertical reinforcement spacing Wall height "H" Vertical reinforcement spacing Wall height "H" Vertical reinforcement spacing
H max = 2.70m 1/2"@102cm or 3/8"@51cm

Interior insulated
walls H max = 2.70m Ø3/8"@76.5cm H max = 3.10m Ø3/8"@51cm
H max = 3.40m 1/2"@76.5cm or 3/8"@51cm

Important notes:
1 .- The thickness of the plastering of the lightened ceiling must be, at least, 1cm.
2 .- The clay roof brick must have a quality certificate issued by an accredited laboratory.
3 .- Valid only for LACASA STANDARD CHINESE EYE glued with epoxy adhesive .
4 .- See measurements and characteristics in the Technical Specification of LACASA STANDARD CHINESE EYE.
LUREN MINING COMPANY SA Véue (to exhéréeucéa
King Kong 11H bricks and line of silico-calcareous plates
Concrete-Stone pavers and slabs
Quick and hydrated lime, bagged or in bulk in containers Carbonate in bulk
and bagged

STANDARD CHINESE EYE FOR PARTITION WALLS

Technical specifications
1. USE:
Superior support of vertical reinforcement rods in partition walls isolated from the
structure.

MATERIAL:
2. •
Cold Rolled Steel JIS G-3141 and zinc plated interior and exterior

MEASURES:
3. Height: 50mm
Plate thickness: 1.5mm
4. RULES:

JIS G-3141 Technical Standard (Japanese Industrial Standards)


ASTM A-1008 Technical Standard (American Society for Testing and Materials)

5. OBSERVATIONS:
The Chinese Eye must be glued to the concrete of the ceiling slab or beam with
epoxy adhesive.
The Chinese Eye should be glued to the plastered clay roof brick with epoxy
adhesive.