Professional Documents
Culture Documents
U6 Systems
U6 Systems
U6 Systems
Unit objectives
Unit topics
• Unitary systems
• All-air systems
• Air-water systems
Suggested reading
6.1 Introduction
In this unit, commonly encountered air conditioning systems are
described and their psychrometric processes associated with heating,
cooling, humidification and dehumidification are presented.
Unitary systems
Air-water systems
Split systems
Fig 6.1
The smaller individual room units have been used extensively all
around the world mainly in residential and hotel applications although,
their use in the UK is limited probably because of their inherent noise
problems.
With this type of system, the condensing unit together with the
compressor is located remotely from the conditioned space. The room
unit contains the evaporator coil and the re-circulation fan. Some units
are configured with the compressor also in the room but with both
arrangements the major advantage over room conditioners is that the
noisy air-cooled condenser fan is located outside of the occupied
space.
Fig 6.2
The major disadvantage associated with this system is that the room
unit and the condensing unit need to be inter-connected by a
refrigerant circuit, which effectively limits the distance that the external
unit can be sited away from the room unit. This normally is 16 - 17m
horizontally and 10m vertically.
With both self-contained and split systems the unit only conditions air
which is drawn from the space being treated. There is, therefore, a
need for mechanical ventilation supply and extract in order to provide
fresh air to the occupied zone rather than having to rely on natural
ventilation or even infiltration.
This specialist type of air conditioning system makes use of units that
are reversible heat pumps that can provide both heating and cooling to
individual rooms simultaneously, and are mainly applied to buildings
having a large number of relatively small cellular spaces such as
hotels and small office buildings.
A reversing valve in each unit alters the direction of the refrigerant flow
effectively tuning the air conditioning unit into a heat pump. Heat is
supplied by the 27oC flow circuit to the coil across which room re-
circulating air is blown, thereby reducing the water temperature to 19
oC before being given up to the return water circuit.
If the water circuit contains excess heat, the surplus is rejected at the
cooling tower. Conversely, the boiler can make up any deficit in heat.
Plate heat exchangers are incorporated into the circuit to ensure that
the water circuit feeding the units remains “clean”, free from any dirt or
scaling associated with the cooling tower or boiler circuits.
Constant air volume (CAV) systems supply a fixed air flow rate to
conditioned spaces and as the loads within the occupied zones vary
the condition of the supply air state is altered to offset them.
Multi-zone systems;
Fig 6.3
A constant volume flow rate is supplied and changing loads are dealt
with by varying the state of the supply air. Close control over room
temperature can be maintained by re-heat but this is wasteful since full
cooling is being undertaken at the central plant, so chillers and boilers
are operating simultaneously.
This system does offer the advantage of being able to also maintain a
number of spaces, each with varying loads, at their required room
state by the use of one air handling plant. This is made possible by
providing local re-heater batteries close to the conditioned rooms.
Fig 6.4
At the central plant, mixed fresh and re-circulated air is split and flows
at high velocity across a heater battery down a “hot” duct or across a
cooler coil down the “cold” duct.
Another function of the mixing box is to reduce the static pressure from
the high velocity supply duct so that the mixed air can be delivered to
Fig 6.5
Air flowing across the cooling coil in the “cold” duct is cooled and
dehumidified to state C. Gains occurring in the cold duct raises the
temperature to C’.
At each mixing box, air from the “hot” duct at M’ is mixed proportionally
with air from the “cold” duct at C’ to offset the gains and the supply air
state can be obtained by using the room ratio line associated with
each zone.
Fig 6.6
Air passing down the “hot” duct and over the heater battery is supplied
at state Hw. Mixing then takes place locally and the Supply State
determined once again by the use of the room ratio lines associated
with the loads occurring within each zone.
Fig 6.7
Fig 6.8
The principle of supplying air to the occupied zone at constant
It is at the air terminals that control over the supply air quantity takes
place. Turndown is achieved by the use of either fixed geometry or
variable geometry terminals. The basic VAV system requires only a
cooling coil, fan and mixing dampers in order to provide cooling to
internal zones within a building, which may be suffering sensible heat
gains continually throughout the year.
All the occupied zones must be provided with the minimum amount of
fresh air even when the VAV terminal units are operating at maximum
turn down which, can be as low as 30%.
Fig 6.9
The summer and winter cycles associated with a VAV system serving
a number of zones that are provided with re-heaters at the terminal
units. In summer the heater battery at the central plant is switched off,
and in winter the cooler coil is also switched off.
Fig 6.10
large air supply quantities are not required, air-water systems may
effectively be used. The following systems will be dealt with here:
Chilled beam
Both fan coil unit systems and induction unit systems were developed
for use mainly as perimeter systems in office buildings. Fan coil unit
systems are becoming increasingly popular for a number of building
applications. Perimeter induction unit systems on the other hand are
no longer favoured having been replaced in the UK by other systems
such as VAV systems.
With air-water systems heating and cooling, water flow and return
circuits are piped around the building from a central boiler and water
chilling plant. Each individual terminal unit being connected to the
water circuits.
These are effectively small individual air handling units, which are
located in the conditioned room. They are normally positioned at the
perimeter wall below windows although, they can also be positioned in
the suspended ceiling void.
The simplest form of fan coil unit takes in room air and cools it by
passing it over a chilled water cooler coil before supplying it back into
the occupied space. There is no provision for treated fresh air and in
this regard, reliance is placed upon natural ventilation or even
infiltration. This is generally considered to be unacceptable in the UK.
Alternatively, fresh air can be introduced into the back of the unit
through the outside wall. There are problems with this method. They
are associated with noise and the ingress of dirt.
not need to handle the total air volume as in the case of all-air systems
since, re-circulation effectively takes place within the room. These
systems also offer the capability of ensuring that variable room
conditions can be maintained simultaneously in each zone.
The performance of the unit depends upon airflow rate through the
unit, the entering air temperature, coil capacity and chilled water
temperature and flow rate. Capacities between 0.5 and 5kW are
normally available.
Fig 6.11
Fan coil units have a sheet metal casing that house one or two coils
and fans, inlet and supply grilles and, in some units filters are
provided.
and then to a heating circuit using the same pipework. This is known
as a changeover system.
A better solution and, one that is adopted in the UK, is to provide both
a cooling and heating coil in each fan coil unit together with two flow
sets of flow and return pipes. One a chilled water circuit and the other
a heating system - this is known as a 4-pipe system.
Fig 6.12
With these systems, primary air that has been centrally conditioned is
ducted to each unit by a high velocity system and discharges through
a set of nozzles in the unit. This induces secondary room air to enter
the unit and after flowing over the secondary coil in the unit mixes with
the primary air prior to being supplied into the room. Thus re-
circulation takes place in the unit and not at the central plant as in the
case of fan coil unit systems. An extract system also needs to be
provided.
Fig 6.13
Fig 6.14
A ducted air supply may also be incorporated into the beams but there
are a number of examples in the UK where chilled beam systems
have been combined with displacement ventilation systems. These
supply air at around 19oC at low velocity through low level terminals or
floor swirl diffusers. Some systems make use of a floor void to
circulate air to the occupied space thus reducing the amount of
ductwork required.
Tutorial questions
The two zones are held at 21oCdb 50% saturation when the
outdoor air state is 28oCdb, 19.5oCwb in summer and -2oC
saturated in winter. fresh air, 30% by mass, is continuously
provided to each zone.
If the contact factor of the cooler coil is 0.85 and the off-coil
state is 10oCdb, determine
Zone 1 Zone 2
Summer:
Sensible heat gain 25kW 20kW
latent heat gain 10kW 5kW
Winter:
Sensible heat loss 15kW 10kW
latent heat gain 5kW 5kW
The “cold” deck contact factor is 0.83 and the leaving air
temperature is 10ocdb in summer and in winter the maximum
leaving air temperature at the “hot” deck is 30oCdb.
Space1 Space2
Summer: SHG = 40kW SHG = 30kW
SHG = 5kW LHG = 7.5kW
Winter: SHL=7.5kW SHG = 7.5kW
LLHG = 5kW LHG = 7.5kW
Design data
Outdoor Indoor Room
Summer: 30°Cdb; 24°Cdb; SHG = 80kW
22°Cwb 50% saturation SHG = 20kW
Winter: 1°Cdb; 20°Cdb; SHL=32kW
saturated 50% saturation LLHG = 18kW
Outline solutions
Q6.1
+ - +
Summer operation
1 Plot the states for outdoor and room air (Os, R) and ADP on
the psychrometric chart
2 Draw a line ADP-Os
3 As the supply temperature is 8C lowere, hence t ss = 13Cdb
4 Calculate RRL and draw it from R to meet t ss = 13Cdb . Obtain
the state of supply air: g ss = 5.7 gss=5.7g/kgair
5 Draw a horizontal line representing sensible reheat from
t ss = 13Cdb to meet ADP-Os line at WS, which is after coil
state, t ws = 9 Cdb
tos − t ws 28 − 9
CF = = = 0.91
tos − t ADP 28 − 7
SHG 18.7
m= = = 2.29kg / s
c(t r − t s ) 1.02 × 8
Winter operation
Vow = 0.86m 3 / kg
Comment 1:
There are some discrepancies between the results here and those at
Comment 2:
The cure is that in Summer the room temperature does not need to
be 21, but 24Cdb. A fan slower is in place. Hence in winter mode, the
supply will be just right.
Q6.3
SUMMER CYCLE
tm − tw
CF = = 0.83 ; ADP = 7.3°Cdb &
tm − t A
40 30
RRLR1 = = 0.89 ; RRLR 2 = = 0 .8
40 + 5 30 + 7.5
SHG 40
m= ; for room1 m1 = = 4.9 kg/s
c(t r + t s ) 1.02 × (21 − 13)
30
for room2 m2 = = 2.67 kg/s
1.02 × (21 − 10)
But for zone 1, there is a mixing by both cold and hot ducts
Since: ms t s = mht h + mc t c ; ms = mh + mc
WINTER CYCLE
Plot state point 'O' on the chart, draw line 'OR' from
m R t R + mo t o = mm t m tm =0.7x21 + 0.3x(-3)=13.5C
plot 'M' on line OR
From chart
tSMR1 = 27°Cdb, 0.0062kg/kg d.a.
tSMR2 = 24.5°Cdb, 0.0062kg/kg d.a.
for zone 1:
7 .5
ms1 = = 1.25 kg/s & tc=tm=13.5C
1.02 × (27 − 21)
for zone 2:
7 .5
ms 2 = = 2.1 kg/s & tc=tm=13.5C
1.02 × (24.5 − 21)
6.5
Outline solution
Summer:
m R t R + mo t o = mm t m tm =(0.7X24)+(0.3x30)=25.8°C
ADP = 11.0°C
Contact factor = 0.8.
Calculate off coil temperature: tw =14.0°C
SHG 80
m= = = 10.46kg / s
c(t r + t s ) 1.02 × (24 − 16.5)
Winter:
SHL = mc(t s − t r ) = 10.46 × 1.02 × (t s − 20); t s = 22.9 °C
There is a need for adding moist.
∆g = g r − g g = 0.0068 − 0.006 = 0.0008 kg/kg.d.a.
Total moist=0.0008*10.46=8.4g/s water vapour is to spray into
the air.