Professional Documents
Culture Documents
2017-Generalized Delta Circuit For Short Circuit Calculation
2017-Generalized Delta Circuit For Short Circuit Calculation
Abstract—In this paper, a novel concept of Generalized can cope with large-scale distribution systems of any com-
Δ-circuit is proposed, that enables integration of distributed plexity, including modern distributed generators (DGs) with an
generators (DGs) based on contemporary technologies into the arbitrary selected fault current control strategies.
short-circuit calculations of large-scale distribution systems. Mod-
ern DG models, such as doubly fed induction generators (DFIGs) SCC is one of the basic Distribution Management System
and three-phase inverter based DGs (IBDGs) differ from the clas- (DMS) power calculations. Its results are necessary for the
sical synchronous and induction generator models. It is shown that development and execution of numerous other applications,
their models cannot be integrated in traditional short-circuit calcu- including: Relay Setting and Coordination, Fault Location,
lation procedures because they include a large number of possible Isolation and Supply Restoration, and Protection Equipment
fault current control strategies. Therefore, the concept of Gener-
alized Δ-circuit is proposed and allows for any control strategy
Selection. The entire range of fault current results obtained
implemented in modern DGs to be integrated in the short-circuit by online SCC is used to provide reliability and selectivity of
calculation procedure. An improved backward/forward sweep the protection system. Hence, an online SCC procedure must
procedure is developed for calculation of the Generalized Δ-circuit satisfy two basic features when large-scale distribution systems
state. The faulted system state is calculated by the superposition are considered: 1) high speed and 2) high accuracy.
of the known prefault state and calculated Generalized Δ-circuit
A SCC method for traditional distribution systems, Equiva-
state. Results show that unlike previously developed online
short-circuit calculations, the proposed method can handle DFIGs lent Voltage Source Method (EVS), is provided in the Interna-
and IBDGs with arbitrary selected fault current control strategies. tional IEC 60909 Standard [1]. However, as shown in [2], doubly
Index Terms—Distributed generation, distribution manage- fed induction generators (DFIGs) as well as three-phase inverter
ment system, distribution system, relay protection, short-circuit based DGs (IBDGs) present particular issues as their models
calculation. cannot be integrated in EVS. In [2], an attempt to extend EVS
LIST OF ACRONYMS AND ABBREVIATIONS to cope with modern DGs is proposed. However, the proposed
Short-Circuit Calculation SCC solution is not general because the control strategies assumed
Distributed Generator DG for DFIGs and IBDGs were oversimplified and only balanced
Distribution Management System DMS three-phase short-circuits were considered. In [3], [4] a Hybrid
Equivalent Voltage Source EVS Compensation Method (HCM) is used for SCC. This method is
Doubly Fed Induction Generator DFIG based on the compensation technique for solving the loop cur-
Three Phase Inverter Based DG IBDG rents, fault currents and currents injected by synchronous ma-
Hybrid Compensation Method HCM chines. Afterwards, backward/forward sweep (BFS) in the phase
Backward/Forward Sweep BFS domain is used for calculating voltages and currents of every
Improved Backward/Forward Sweep IBFS bus/branch in the system. BFS does not require building and fac-
Single Line to Ground SLG torization of the system’s nodal admittance matrix, which makes
Double Line to Ground 2LG HCM fast and highly effective for large-scale distribution sys-
Double Line 2L tems. However, HCM is not suitable for fault analysis of distribu-
Three Line to Ground 3LG tion systems with modern DGs because it is based on a premise
Threshold TH that synchronous generators are the only active elements. In [5],
[6] SCCs for systems containing IBDGs are proposed and it is
I. INTRODUCTION shown that these methods give good results compared to dynam-
HE objective of this paper is to develop an effective and ical simulations on a small system. However, DFIGs were not
T robust online Short-circuit calculation (SCC) method that discussed in these studies. Moreover, the calculation procedures
in both papers are bus oriented and use the system’s nodal admit-
tance matrix. While this approach is highly effective for trans-
Manuscript received May 24, 2016; revised August 19, 2016; accepted Octo-
ber 7, 2016. Date of publication October 12, 2016; date of current version June mission systems, as shown in [7], it is at least three times more
16, 2017. Paper no. TPWRS-00786-2016. time-consuming than BFS when used for large-scale distribution
The authors are with the Department of Electrical Engineering and Com- systems. More recent publications [8]–[10] perform SCCs using
puter Sciences, Case Western Reserve University, Cleveland, OH 44106-7078
USA (e-mail: lxs533@case.edu; mxp438@case.edu; kal4@case.edu). the superposition theorem. The traditional way of using the
Digital Object Identifier 10.1109/TPWRS.2016.2617158 superposition theorem for SCC is based on decomposing the
0885-8950 © 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on June 18,2024 at 13:57:00 UTC from IEEE Xplore. Restrictions apply.
3238 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 32, NO. 4, JULY 2017
faulted system into two separate systems. The first is the known key parameters for computing the Generalized Δ-circuit are pro-
pre-fault system, while the second is called the Δ-circuit. Thus, vided. In Section V the calculation of the Generalized Δ-circuit
the calculation of the faulted system comes down to the Δ- is presented. Results are presented and discussed in Section VI.
circuit calculation. The main characteristic of the Δ-circuit is The paper is concluded in Section VII.
that it is passive everywhere except at the fault location, which
makes it easy to calculate. This approach is highly effective and II. DISTRIBUTION SYSTEM MODEL
has been used for years for systems containing only synchronous
and induction machines. In [8], [9] DGs were not discussed at A. Transformers, Line Sections, and Load Modeling
all. The approach in [10] copes well with synchronous and in- In this paper, the equivalent circuit of the distribution system
duction machine DGs and with DFIGs and IBDGs that have is considered in per unit domain. Thus, the transformers are rep-
very simplified control strategies. Therefore, it is of limited use resented with their short-circuit impedances and magnetizing
in those applications where DFIGs and IBDGs can implement a admittances and line sections are modeled with their Π circuits
wide range of fault current control strategies [11]. This research [12]. A common practice in SCCs for distribution systems is to
addresses the lack of online SCC methods for active distribution neglect the influence of loads [1], [2]. However, it is shown in
systems that include DFIGs and IBDGs that implement a wide [19] that neglecting loads could lead to unacceptable inaccuracy
range of fault current control strategies. when performing SCC for relay protection purposes. The error
The SCC proposed in this paper is based on the superposi- regarding currents at the beginning of a feeder, as a result
tion theorem. However, it is shown that the traditional Δ-circuit of neglecting loads can be as high as 20%. Thus, loads are
concept [8]–[10], [12] is of limited use for distribution systems modeled as constant currents in this paper the currents obtained
containing modern DGs. DFIG models for SCC differ with re- from the pre-fault state.
spect to the fault severity and protection scheme used for the
DFIG power converter. They can be modeled either as induction
B. DG Modeling
machines or as ideal current sources [13]–[18]. Thus, an algo-
rithm for deciding which DFIG models should be used, based on An extensive lists of different DG technologies and ways by
the severity of the fault and the converter’s protection scheme, which they are connected to the distribution system are presented
is developed in this paper and integrated into the proposed SCC in [2], [10], and [20]. DGs are sorted into four types, considering
procedure. IBDGs are modeled as ideal current sources exclu- their SCC models [2], [10]:
sively. There is a wide range of control strategies used in today’s 1) Type I – Synchronous DG directly connected to the sys-
IBDGs for their injected fault currents. In the general case, tem;
when their fault currents exceed their pre-fault currents, these 2) Type II – Induction DG directly connected to the system;
models cannot be integrated in the existing SCC procedures. 3) Type III – DFIG;
Therefore, the Generalized Δ-circuit concept is developed in 4) Type IV – IBDG.
this paper. Contrary to the traditional Δ-circuit, besides for the Type I DGs are modeled as ideal voltage source behind
fault location, the Generalized Δ-circuit is active at every bus impedance in sub-transient, transient and steady-state time pe-
where these DGs are connected to the system. Thus, with the riods for the purpose of SCC [12]. Type II DGs are modeled in
use of the Generalized Δ-circuit, models for modern DGs can the same manner, but only in transient and steady state periods
be integrated in the SCC. For the calculation of the traditional [12]. Models for both Type I and Type II DGs are integrated in
Δ-circuit, an improved BFS (IBFS) procedure is proposed in the SCC using the traditional Δ-circuit [10], and they will be
[10] and modified in this paper for the calculation of the Gen- treated exactly the same in the Generalized Δ-circuit. As for
eralized Δ-circuit. The IBFS does not require building and fac- Types III and IV DGs, their models cannot be integrated in the
torization of the system’s nodal admittance matrix and it is traditional Δ-circuit. Therefore their operation and models are
performed in the sequence domain. This makes the proposed explained in detail, as follows.
procedure fast and easy for programming. Type III DG (DFIG) is in most cases used in wind generation.
To verify the accuracy and applicability of the proposed SCC DFIG’s stator is directly connected to the distribution system,
method, it is first compared with HCM in [3] using a distribution while its rotor is connected to the system by power converter.
system without modern DGs. Then the IBFS is compared with DFIG is the most complex to model. Its short-circuit model
the extended EVS method [2] on the distribution system with depends on the severity of the fault and on the method used for
modern DGs. Results show that unlike previously developed the protection of the converter [13]–[18]. The power electronic
SCC procedures, the proposed procedure, which is based on devices of the converter are sensitive to the above rated currents,
the Generalized Δ-circuit model, can handle DFIGs and IBDGs thus the converter needs to be protected [13]–[18]. There are two
with a wide range of fault current control strategies. In addition, main protection methods: crowbar and chopper [15]–[17].
contrary to existing SCC procedures, the algorithm developed in When the crowbar is used for the converter’s protection,
this paper allows IBFS to use the appropriate models for DFIGs it short-circuits the rotor’s terminals when the fault is severe
for short-circuits anywhere in the system. These facts make the [15]–[17]. If this happens, the DFIG model becomes similar
proposed procedure effective and significantly more robust than to the induction machine (Type II DG) [2], [13]–[15]. A sin-
previously developed online SCC procedures. gle difference between these two models is that the crowbar’s
The remainder of the paper is organized as follows. In resistance is added in series to the rotor’s resistance. The crow-
Section II, distribution system modeling is presented. Section III bar’s resistance should not be neglected for SCC purposes as
presents the Generalized Δ-circuit for SCC. In Section IV, the it can be as much as 20 times larger than the rotor’s resistance
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on June 18,2024 at 13:57:00 UTC from IEEE Xplore. Restrictions apply.
STREZOSKI et al.: GENERALIZED Δ -CIRCUIT CONCEPT FOR INTEGRATION OF DISTRIBUTED GENERATORS IN ONLINE SHORT-CIRCUIT 3239
[13] and [15]. If the fault is not as severe (e.g. if it happens far
from the DFIG), the crowbar will not react and the converter
will continue to control the injected current [15]. In this case,
the DFIG model is the same as the model of the Type IV DG, ex-
plained below. In this paper the severity of the fault is estimated
using the voltage at the DFIG terminals. It is assumed that the
Fig. 1. Type IV DG’s short-circuit model.
crowbar will be activated if the voltage at the DFIG terminals
falls below the threshold value. If the voltage at the DFIG ter-
minals remains above the threshold, the DFIG will control its
f pf
fault current. where IˆDG4 and IˆDG4 are the IBDG fault current and its pre-
When chopper protection is used, better grid support, such fault current, respectively.
as Low Voltage Ride Through, is achieved during a fault by Control Strategy II covers a wide range of control strategies
keeping the rotor’s converter active, but still limiting the currents where IBDGs and DFIGs supply any fault currents, higher than
to protect the power converter [15]. In this case, the converter their pre-fault currents. In most cases the fault current limit is
will continue to control the DFIG’s fault current even in the case 1-1.5 of their rated currents [15]–[17]. There are many control
of a severe fault, and it should be modeled in the same way as strategies that can be applied for the proportion of the real and
the Type IV DG [15]–[17]. imaginary components of the injected fault current [15]–[17].
DFIGs from different manufacturers could use different con- The control strategy applied in IBDG is either defined by the
trol strategies and different threshold values [16], [17]. However, Grid Code for the specific country [5], or by manufacturers
with the manufacturer’s information about the control strategy [15]–[17]. In this paper, the control strategy is assumed in ac-
and protection method used in the DFIG’s power converter, it cordance with [15], and it is briefly explained as follows. As
can be easily incorporated in the procedure proposed in this it is usually required from IBDG to produce reactive power
paper. during the fault, it is assumed that the real component of the
Type IV DG (IBDG) is used in wind and solar generation, as IBDG’s current does not change from its pre-fault value, while
well as in micro turbines. It is modeled in the same way, regard- its imaginary component changes immediately after a drop in
less of the primary energy source [2], [13]–[17]. The IBDG’s the terminal voltage. Therefore, the positive sequence current
generator is fully decoupled from the distribution system by supplied by the IBDG throughout the duration of the fault is
power converter. Therefore, the electrical model of the IBDG calculated as [15]:
is completely dependent on the control strategy implemented f f
f
in the converter. During fault conditions, in order to protect the IˆDG4 = Real IˆDG4 + j Imag IˆDG4
power electronic devices, IBDG switches to a current-limiting
mode, with the predefined current limit [15], [16]. Controllers pf 2
= Real Iˆ DG4 − j (IDG4m ax )2 − Real Iˆpf DG4
are set to inject only positive sequence currents, even during un-
balanced faults [15]–[17]. Thus, the short-circuit model of this (2)
type is represented by an ideal current source in the positive se-
quence only [15], [16]. This is a particular issue for the existing In (2), IDG4m ax is a limit of the current supplied by the IBDG
SCC methods which are designed for conventional synchronous during a fault. Real corresponds to the real component, while
and induction generator models [1]–[4]. In this paper, the two Imag corresponds to the imaginary component of the current.
distinct IBDG control strategies, including DFIGs that maintain Different manufacturers could use different control strategies.
control of the injected fault current, are: For instance, in [5] it is suggested that IBDG should inject a
1) Control Strategy I: IBDGs and DFIGs maintain the same purely reactive current with the magnitude of its rated current
pre-fault currents throughout the duration of the fault; during the fault. It is obvious that this control strategy is covered
f
2) Control Strategy II: IBDGs and DFIGs supply fault cur- by the Control Strategy II and that IˆDG 4 can be calculated similar
rents which have higher magnitudes and different phase to (2). In summary, as long as the manufacturer provides the
angles than the pre-fault currents. information about the control strategy for the current injected
Control Strategy I is applied when the fault is not severe f
by its DG, current IˆDG4 can always be calculated in a manner
regarding DFIGs and IBDGs and they manage to maintain similar to (2). Moreover, if the information about the control
their pre-fault controls. In some modern IBDGs [15]–[17] strategy from the manufacturer is not available, this information
and some DFIGs with chopper protection [15], controllers should be obtained from the Fault Ride Through requirements
can be set in accordance with this strategy independently on of the Distribution Code of specific country [21]. In that way,
the fault severity. If the fault is severe and the controllers are f
current IˆDG4 can be calculated even without manufacturer’s
set to supply the fault current different than the pre-fault one information. In Fig. 1 the short-circuit model of the Type IV
[13]–[18], Control Strategy II is applied for IBDGs and DFIGs. DG is shown.
For the Control Strategy I, the positive sequence current sup- In the following text, DFIGs which maintain their control of
plied by the IBDG during the fault is: the fault current will be treated same as IBDGs. Both of these DG
types will be termed Type III-IV DGs. In addition, their pre-fault
pf f
and fault currents will be marked with IˆDG3−4 and IˆDG3−4 ,
f pf
IˆDG4 = IˆDG4 (1) respectively.
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on June 18,2024 at 13:57:00 UTC from IEEE Xplore. Restrictions apply.
3240 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 32, NO. 4, JULY 2017
TABLE I
EQUATIONS FOR CALCULATING SHORT-CIRCUIT
CURRENTS AT FAULT LOCATION
Û k a ( Ẑ k− + Ẑ k0 ) Û k a Û k a Û k a
Jˆk+
Ẑ k+ + Ẑ k− + Ẑ k0 Ẑ k+ Ẑ k− + Ẑ k+ Ẑ k0 + Ẑ k− Ẑ k0 Ẑ k+ + Ẑ k− Ẑ k+
Fig. 2. Γ Segment.
Û k a −Ẑ k0 Û k a Û k a
Jˆk− − 0
Ẑ k+ + Ẑ k− + Ẑ k0 Ẑ k+ Ẑ k− + Ẑ k+ Ẑ k0 + Ẑ k− Ẑ k0 Ẑ k+ + Ẑ k−
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on June 18,2024 at 13:57:00 UTC from IEEE Xplore. Restrictions apply.
STREZOSKI et al.: GENERALIZED Δ -CIRCUIT CONCEPT FOR INTEGRATION OF DISTRIBUTED GENERATORS IN ONLINE SHORT-CIRCUIT 3241
the simplicity of the well-established equations from this table, In (7) L and l represent sending and receiving nodes of all
these will still be used for calculation of the short-circuit currents Γ segments (Fig. 2), excluding breakpoint nodes. From (6) and
at the fault location in the Generalized Δ-circuit. (7) it is evident that the traditional Δ-circuit state could be
However, the influence of the excess currents on the fault calculated directly by the proposed approach. As a result, there
current flow in the whole system is significant. Neglecting this is no need for the traditional iterative procedure [3], [4], [10].
influence could seriously affect protection equipment settings Control Strategy II: Some or all Type III-IV DGs supply fault
and coordination as well as protection of power converters of currents which are different from their pre-fault currents.
Type III-IV DGs. Therefore, their influence must be considered As established in Section III, the Generalized Δ-circuit is ac-
in the calculation of the Generalized Δ-circuit state – Section V. tive not only at the fault location but also at every location where
Thévenin impedances seen from bus k (Ẑk+ , Ẑk− , Ẑok ) are the Type III-IV DGs with Control Strategy II are connected to
calculated in the following way: annul the voltage source at the positive sequence circuit. Thus, (6a) cannot be used for
the faulted node and annul Type III-IV DG excess currents in calculating the positive sequence of the Generalized Δ-circuit.
the Generalized Δ circuit. Inject a unity current at the faulted It must be calculated by injecting short-circuit currents at the
node, in positive, negative and zero sequence circuits. In each fault location plus injecting the excess currents at every location
of the three sequences, calculate voltages of every node of the of positive sequence circuit where Type III-IV DGs with Con-
sequence circuits obtained in this way and memorize it in the trol Strategy II are connected. In this paper, the original IBFS
following vectors (T indicates the matrix/vector transposition): procedure [10] is modified by injecting the excess currents at
+ T every location where Type III-IV DGs with Control Strategy II
Ẑ k = Û2+ Û3+ . . . Ûk+ . . . Ûn+ , (4a) are connected. The modified IBFS procedure is presented as
− − − T follows:
Ẑ k = Û2 Û3 . . . Ûk− . . . Ûn− , (4b) Backward sweep:
0 T Δ + h + 1 Δ + h
Ẑ k = Û20 Û30 . . . Ûk0 . . . Ûn0 . (4c) Iˆl = JˆlΔ + + (JˆclΔ + )h + ŷlo
+
Ûl
The computation of these vectors requires performing three Δ + h + 1
+ Iˆj + JˆDG3
Δ+
− 4l ,
IBFS procedures [10], for positive, negative and zero sequences.
j ∈a l
These vectors are termed Thévenin vectors since their k-th ele-
ments are numerically equal to Thévenin impedances seen from l = n + p , . . . , 3, 2; (8)
the bus k: Forward sweep:
Ẑk+ (=) Ûk+ ; Ẑk− (=) Ûk− ; Ẑk0 (=) Ûk0 (5) Δ + h + 1 h + 1 h + 1
Ûl = ÛLΔ + − ẑl+ IˆlΔ + ,
+ − 0
Vectors Ẑ k , Ẑ k
and Ẑ k
will be used for direct calculation l = 2, 3, . . . , n + p; (9)
of the traditional Δ-circuit states for positive, negative and zero
Breakpoint currents correction:
sequence, respectively. The improved calculation of the tradi-
tional Δ-circuit state as well as the calculation of the General- + h Δ+ h + 1 + h+1
c ) = ŶN (Û1 )
(ΔĴΔ +
− (ÛΔ
2 ) ,
ized Δ-circuit state are the subject of Section V.
−1
ŶN+
= Ẑ+T , (10)
V. CALCULATION OF THE GENERALIZED Δ-CIRCUIT
+ h+1 + h Δ+ h
STATE IN SEQUENCE DOMAIN (ĴΔ
c ) = (ĴΔ
c ) + (ΔĴc ) (11)
The calculation of the Generalized Δ-circuit state in sequence The injected fault currents are known from Table I:
domain is proposed for two different cases, in accordance with
Section II B, as follows. 0, l = k
JˆlΔ + = (12)
Control Strategy I: All Type III-IV DGs supply fault currents JˆkΔ + = 0, l=k
which are the same as their pre-fault currents.
In this case the Generalized Δ-circuit reduces to the tradi- The Type III-IV DGs’ excess currents are known from (3):
⎧
tional Δ-circuit. Using (4) and equations from Table I, its three ⎨0, l ∈
/ αDG3 − 4
sequence domain states are calculated in the following way: ˆ
JDG3 − 4 l =
Δ+ 0, l ∈ αDG3 − 4 , Control Strategy I (13)
+ + T ⎩ ˆΔ +
+ −IDG3−4 l , l ∈ αDG3 − 4 , Control Strategy II
Û2 Û3 . . . Ûk+ . . . Ûn+ = Ẑk Jˆk+ , (6a)
− − T − The iterative procedure is stopped when the convergence cri-
Û2 Û3 . . . Ûk− . . . Ûn− = Ẑ k Jˆk− , (6b) terion is achieved:
0 0 T 0 Δ + h + 1 Δ + h
Û2 Û3 . . . Ûk0 . . . Ûn0 = Ẑ k Jˆk0 . (6c) Ûl − Ûl ≤ εU , l = 2, 3, . . . , n + p (14)
Û + − Û + Û − − Û − All parameters and state variables which are defined in the
Iˆl+ = L + l ; Iˆl− = L − l ;
Ẑl Ẑl sequel refer to positive sequence (+in the superscript). h is
the iteration number; n is the number of three-phase buses in
Û 0 − Û 0 the system; p is the number of loops. ẑl+ and ŷlo
+
are the se-
Iˆl0 = L 0 l (7)
Ẑl ries and shunt parameters of the l-th Γ segment – Fig. 2 (the
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on June 18,2024 at 13:57:00 UTC from IEEE Xplore. Restrictions apply.
3242 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 32, NO. 4, JULY 2017
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on June 18,2024 at 13:57:00 UTC from IEEE Xplore. Restrictions apply.
STREZOSKI et al.: GENERALIZED Δ -CIRCUIT CONCEPT FOR INTEGRATION OF DISTRIBUTED GENERATORS IN ONLINE SHORT-CIRCUIT 3243
IBFS [kA] HCM [kA] Difference in magnitude[%] IBFS [kA] EVS [kA] Difference in magnitude[%]
normal operating conditions, each one providing 12% of the terminals. The threshold refers to the phase with the minimal
system’s total load. This means that the power supplied by DGs voltage. The Control Strategy I was assumed – if the crowbar
was almost 50% of the total load. This made the test system an does not react, DFIG would continue to supply the pre-fault
adequate testbed of future active distribution systems. current throughout the duration of the fault. For the IBDG, the
In order to validate the proposed method, IBFS was first Control Strategy II was assumed (Eq. 2). It was assumed that the
compared with the HCM in [3]. As the HCM is not designed for current limit is 1.5 of the rated current. Additionally, since [2]
IBDGs and DFIGs, these DGs were disconnected from the test neglects the influence of loads, they were neglected in the IBFS
feeder for this comparison. Therefore, only Type I and Type II for this comparison. Thus, the IBFS was simplified to match [2]
DGs were connected. Results are shown in the Table II for all as much as possible. Short-circuits were simulated at buses 671
four solid short-circuits (3LG, 2LG, 2L and SLG) at bus 680. and 680. Results are presented for 3LG, as [2] is not designed
The current of the substation branch (IˆSB ), the current at the for unbalanced faults. Tables III and IV show the results of this
fault location (Iˆfault ) and currents injected by Types I and II comparison. The current of the substation branch, the current
DGs (IˆDG1 and IˆDG2 , respectively) are shown in the table. Due at the fault location and currents injected by DGs are shown
to the space constraints in this paper, in case of unbalanced in tables. Currents injected by Type III and Type IV DGs are
faults only the maximal current of all three phases is presented marked by IˆDG3 and IˆDG4 , respectively.
in all tables that follow. For example, if an SLG fault occurs in For the short-circuit at bus 671 (Table III) the voltage at the
phase a, then only the phase a current is presented in tables that DFIG’s terminals dropped below the threshold value. Thus the
follow. crowbar should react. However, for the short-circuit at bus 680
Slight differences in results from Table II (less than 6%) (Table IV) the voltage at the DFIG’s terminals remained above
appear since loads were modeled as constant currents in the the threshold value. Thus, in this case crowbar should not react.
IBFS and as constant impedances in the HCM. These differences The IBFS was further tested on the same feeder from Fig. 4
are same in absolute values (kA) for all currents from Table II, for three unbalanced short-circuits (2LG, 2L, and SLG), but
but as currents IˆSB and Iˆfault have significantly higher values with all four DGs connected to the feeder. Short-circuits were
than currents IˆDG1 and IˆDG2 , the percentage differences appear simulated at bus 671, one at a time. Loads were taken into
much higher for currents IˆDG1 and IˆDG2 . account for this example. The threshold for crowbar’s reac-
The IBFS was further compared with the extended EVS tion and control strategies for DFIG and IBDG were assumed
method [2]. For this comparison, all four DGs were connected same as for the previous example. Test results are shown in
to the feeder. The control strategies implemented in IBDG and Table V.
DFIG were assumed as explained in Section II. For DFIG it was In this example (short-circuits at bus 671), voltages at DFIG’s
assumed that the crowbar is installed, as [2] cannot implement terminals dropped below the crowbar’s threshold value for all
the chopper protection. The threshold value for the crowbar to three short-circuits. Therefore, DFIG model is switched from
react was assumed to be 70% of the rated voltage at the DFIG’s Type III-IV DG model to Type II DG model after the second
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on June 18,2024 at 13:57:00 UTC from IEEE Xplore. Restrictions apply.
3244 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 32, NO. 4, JULY 2017
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on June 18,2024 at 13:57:00 UTC from IEEE Xplore. Restrictions apply.
STREZOSKI et al.: GENERALIZED Δ -CIRCUIT CONCEPT FOR INTEGRATION OF DISTRIBUTED GENERATORS IN ONLINE SHORT-CIRCUIT 3245
VII. CONCLUSION [11] F. Gao and M. Iravani, “A control strategy for a distributed generation
unit in grid-connected and autonomous modes of operation,” IEEE Trans.
Modern DG models, such as DFIGs and IBDGs, cannot be Power Del., vol. 23, no. 2, pp. 850–859, Apr. 2008.
integrated in traditional SCC procedures due to the wide range [12] R. Bergen and V. Vittal, Power System Analysis, 2nd ed. Englewood Cliffs,
NJ, USA: Prentice-Hall, 2000.
of their fault current control strategies. Thus, a novel online SCC [13] E. Muljadi and V. Gevorgian, “Short-circuit modeling of a wind power
procedure (IBFS), based on the proposed Generalized Δ-circuit plant,” in Proc. 2011 IEEE Power Energy Soc. General Meeting, Detroit,
is presented in this paper. Besides for coping with traditional MI, USA, 2011, pp. 1–9.
DGs, the Generalized Δ-circuit concept allows integration of [14] R. A. Walling and M. L. Reichard, “Short circuit behavior of wind tur-
bine generators,” in Proc. 2009 IEEE Annu. Conf. Protective Relay Eng.,
any control strategy implemented in modern DGs into the pro- College Station, TX, USA, 2009, pp. 492–502.
posed SCC procedure. Additionally, the algorithm for deciding [15] D. F. Howard, “Short-Circuit currents in wind-turbine generator net-
which DFIG model should be used, based on the severity of works,” Ph.D. dissertation, Dept. Elect. Eng., Georgia Inst. of Technol.,
Atlanta, GA, USA, 2013.
the fault and DFIG’s protection scheme, was developed in this [16] J. R. Williams and B. Karlson, “Wind power plant Short-Circuit modeling
paper and integrated into the proposed procedure. guide,” Sandia Nat. Lab., Albuquerque, NM, USA, 2012.
The robustness of the IBFS is established by the simplicity [17] Joint Working Group, “Fault current contribution from wind plants,” report
to the T&D Committee of the IEEE Power and Energy Society, Pro Relay,
of how a large range of distribution system models – from over- 2015.
simplified to rigidly modeled distribution systems, including [18] F. Sulla, J. Svensson, and O. Samuelsson, “Symmetrical and unsymmet-
modern DGs with an arbitrary selected control strategies, are rical short-circuit current of squirrel-cage and doubly-fed induction gen-
handed in the method. Also, using Thévenin vectors for calcu- erators,” Elect. Power Syst. Res., vol. 81, no. 7, pp. 1610–1618, 2011.
[19] L. Strezoski and M. Prica, “Calculation of relay currents in active weakly-
lating the negative and zero sequence circuits of the Generalized meshed distribution systems,” in Proc. IEEE Clemson Univ. Power Syst.
Δ-circuit, makes this procedure extremely fast. The accuracy, Conf., Clemson, SC, USA, 2016, pp. 1–6.
robustness and extremely low computation time of the IBFS [20] A. Rankovic, B. Maksimovic, and A. Saric, “A three-phase state estima-
tion in active distribution networks,” Elect. Power Energy Syst., vol. 54,
makes procedure developed in this paper particularly suitable pp. 154–162, 2014.
and efficient for a large number of DMS power applications in [21] L. Strezoski, V. A. Katic, B. Dumnic, and M. Prica, “Short-Circuit model-
future distribution systems. ing of inverter based distributed generators considering the FRT require-
ments,” in Proc. IEEE North Amer. Power Symp., Denver, CO, USA, 2016,
In addition, the fact that the SCC solvers in current Interna- pp. 1–6.
tional Standards are limited to traditional systems without mod- [22] D. Shirmohammadi, H. W. Hong, A. Semlyen, and G. X. Luo,
ern DGs, while the IBFS has great performances when modern “A compensation-based power flow method for weakly meshed distri-
large-scale distribution systems are considered, the proposed bution and transmission networks,” IEEE Trans. Power Syst., vol. 3, no. 2,
pp. 753–762, May 1988.
procedure could be implemented in solvers for some future and
updated International Standards for SCCs of active distribution
systems. Luka Strezoski (S’13) received the B.S. and M.Sc. degrees in power en-
gineering from the University of Novi Sad, Novi Sad, Serbia, in 2013 and
2014, respectively. He is working toward the Ph.D. degree. He is currently
with the Electrical Engineering and Computer Science Department, Case West-
REFERENCES ern Reserve University, Cleveland, OH, USA, as a Research Scholar. His re-
search interests include distribution system modeling; power flow and short-
[1] Short-Circuit Currents in Three-Phase A.C. Systems—Part 0: Calculation circuit calculations; and integration of distributed generators to the DMS power
of Short-Circuit Currents, IEC 60909-0, 2001. applications.
[2] T. N. Boutsika and S. A. Papathanassiou, “Short circuit calculations in
network with distributed generation,” Elect. Power Syst. Res., vol. 78,
pp. 1181–1191, 2008.
[3] Z. Xiaofeng, F. Soudi, D. Shirmohammadi, and C. S. Cheng, “A distribu-
tion short circuit analysis approach using hybrid compensation method,”
IEEE Trans. Power Syst., vol. 10, no. 4, pp. 2053–2059, Nov. 1995.
[4] W. M. Lin and T. C. Ou, “Unbalanced distribution network fault analysis Marija Prica (M’10) received the B.S. and M.S. degrees in power engineering
with hybrid compensation,” IET Gener., Transm., Distrib., vol. 5, no. 1, from the University of Novi Sad, Novi Sad, Serbia, in 2000 and 2006, respec-
pp. 92–100, 2011. tively, and the Ph.D. degree from Carnegie Mellon University, Pittsburgh, PA,
[5] D. Van Tu, S. Chaitusaney, and A. Yokoyama, “Maximum-allowable USA, in 2010. She is an Assistant Professor at Case Western Reserve Univer-
distributed generation considering fault ride-through requirement and sity, Cleveland, OH, USA. Her interest include distribution system planning and
reach reduction of utility relay,” IEEE Trans. Power Del., vol. 29, no. 2, protection; integration of advanced technologies and control; decision-making
pp. 534–541, Apr. 2014. for future electricity systems; and optimization of energy storage operation.
[6] M. E. Baran and I. M. El-Markaby, “Fault analysis on distribution feeders
with distributed generators,” IEEE Trans. Power Syst., vol. 20, no. 4,
pp. 1757–1764, Nov. 2005.
[7] V. Strezoski and P. Vidović, “Power flow for general mixed distribution
networks,” Int. Trans. Elect. Energy Syst., vol. 25, no. 10, pp. 2455–2471,
2015.
[8] R. A. Jabr and I. Dzafic, “A fortescue approach for real-time short circuit Kenneth A. Loparo (F’99–LF’16) is the Nord Professor of Engineering and
computation in multiphase distribution networks,” IEEE Trans. Power Chair of the EECS Department, Case Western Reserve University, Cleveland,
Syst., vol. 30, no. 6, pp. 3276–3285, Nov. 2015. OH, USA. His research interests include stability and control of nonlinear sys-
[9] M. Abdel-Akher and K. M. Nor, “Fault analysis of multiphase distribution tems with applications to large-scale electric power systems, nonlinear filtering
systems using symmetrical components,” IEEE Trans. Power Del., vol. 25, with applications to monitoring, fault detection, diagnosis, and reconfigurable
no. 4, pp. 2931–2939, Oct. 2010. control, etc.
[10] L. Strezoski and M. Prica, “Real-time short-circuit analysis of active distri- Dr. Loparo is an Editor of the IEEE TRANSACTION ON POWER SYSTEMS and
bution systems,” in Proc. IEEE Power Energy Conf. Illinois, Champaign, has held numerous positions in the IEEE Control Systems Society.
IL, USA, 2016, pp. 1–8.
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY DURGAPUR. Downloaded on June 18,2024 at 13:57:00 UTC from IEEE Xplore. Restrictions apply.