05 4000-2.0 Cold Formed Metal Framing - Delegated Design and Design Calculations
05 4000-2.0 Cold Formed Metal Framing - Delegated Design and Design Calculations
05 4000-2.0 Cold Formed Metal Framing - Delegated Design and Design Calculations
Re:
Submittal
Progressive Architecture Engineering I, Inc. | 1811 4 Mile Road NE | Grand Rapids, MI 49525 | 616.361.2664 | progressiveae.com
Turner Construction Company
13430 NW Frwy., Suite 500
Houston, TX 77040
(713) 840-8441
SUBMITTAL FOR:
SUBMITTAL #: 05 4000-002-0
ARCHITECT: Progressive AE
COMMENTS:
PROJECT INFORMATION
BELLAIRE, TX 77401-3005
WALTECH CO.INC.
1. EXCEL ENGINEERING IS ACTING AS A SPECIALTY STRUCTURAL COMPONENT ENGINEER, DESIGNING THE COLD-FORMED STEEL FRAMING OF THE GOVERNING CODES
CONSTRUCTION
PROJECT ONLY. EXCEL ENGINEERING TAKES FULL RESPONSIBILITY FOR THE DESIGN OF THE STRUCTURAL COLD-FORMED STEEL FRAMING AND
THEIR ATTACHMENT TO THE SUPPORTING STRUCTURAL ELEMENTS OF THE BUILDING. EXCEL ENGINEERING TAKES NO RESPONSIBILITY FOR THE 2012 "INTERNATIONAL BUILDING CODE" IBC 2012 SHEET SHEET TITLE
DESIGN OF ANY SUPPORTING STRUCTURAL ELEMENTS. IT IS ASSUMED THAT ALL SUPPORTING STRUCTURAL ELEMENTS HAVE BEEN DESIGNED
2010 "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES" ASCE 7-10
BY THE PROJECT ENGINEER OF RECORD (EOR) AND/OR ARCHITECT OF RECORD (AOR) TO WITHSTAND THE FORCES IMPOSED BY THE
SET
STRUCTURAL COLD-FORMED STEEL FRAMING. EXCEL ENGINEERING EXPECTS THAT THIS COMPONENT SUBMITTAL WILL BE REVIEWED BY THE 2010 "NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS" AISI S100-10
EOR AND/OR AOR FOR CONFORMANCE WITH THE OVERALL PROJECT REQUIREMENTS. 2011 "CODE OF STANDARD PRACTICE FOR COLD-FORMED STEEL STRUCTURAL FRAMING" AISI S202-11 CFS FRAMING DRAWING SUBMITTAL DATE: OCT. 25, 2023
1998 "STRUCTURAL WELDING CODE - SHEET STEEL" AWS D1.3-98 ARCHITECTURAL CONTRACT DOCUMENTS DATED: FEB. 22, 2023
2. SECTION PROPERTIES ARE ASSUMED TO BE IN ACCORDANCE WITH THE AMERICAN IRON AND STEEL INSTITUTE "NORTH AMERICAN 2011 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" ACI 318-11 STRUCTURAL CONTRACT DOCUMENTS DATED: FEB. 22, 2023
SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS" 2012 EDITION WITH SUPPLEMENTS. THE CONTRACTOR IS
TO VERIFY THAT THE MATERIALS INSTALLED MEET OR EXCEED THESE DESIGN VALUES. DESIGN STRESSES C1 COVER SHEET
3. ALL COLD-FORMED STEEL FRAMING HAS BEEN DESIGNED FOR UNIFORM LATERAL LOADS AND WALL CONSTRUCTION DEAD LOADS ONLY. C2 GENERAL INFORMATION
F-10167
SUBMITTAL DATES
PROJECT NUMBER
230381700
SHEET INFORMATION
SHEET NUMBER
C1
2023 © EXCEL ENGINEERING, INC.
APPROVED FASTENERS MEMBER DESIGNATION
POWER DRIVEN FASTENERS CONCRETE SCREW ANCHORS
ARCHITECTS ● ENGINEERS ● SURVEYORS
Always a Better Plan
100 CAMELOT DRIVE
FOND DU LAC, WI 54935
PHONE: (920) 926-9800
WWW.EXCELENGINEER.COM
P.D.F. TO STEEL CONCRETE SCREW ANCHORS
ABBREVIATIONS
BELLAIRE, TX 77401-3005
WALTECH CO.INC.
MASONRY SCREW ANCHORS
P.D.F. TO CONCRETE
TO CONCRETE TO CMU
SCREWS
HOLE REINFORCING
WELD
METAL TO WOOD SCREWS
PROJECT ENGINEER
F-10167
SUBMITTAL DATES
DRAWING INFORMATION ISSUE DATE OCT. 25, 2023
REVISIONS
PROJECT NUMBER
1 230381700
1
S1 SHEET INFORMATION
SHEET NUMBER
C2
2023 © EXCEL ENGINEERING, INC.
T.O.PARAPET
202'-0"
FIFTH FLOOR
151'-9"
BELLAIRE, TX 77401-3005
140'-3"
WALTECH CO.INC.
THIRD FLOOR
129'-0"
SECOND FLOOR
114'-6"
FIRST FLOOR
100'-0"
7 9 11
S2 S3 S3
T.O. PARAPET
176'-6"
SIXTH FLOOR
172'-6"
PARTS MEZZANINE
162'-0"
FIFTH FLOOR
151'-9"
FOURTH FLOOR
140'-3"
THIRD FLOOR
129'-0"
SECOND FLOOR
114'-6"
PROJECT ENGINEER
FIRST FLOOR
101A 100'-0" JEFF HENRIKSEN
jeff.henriksen@excelengineer.com
(920) 322-1689
1 5 8 7 DRAWN BY: SBB
S1 S2 S2 S2
PROFESSIONAL SEAL
2
E1 ELEVATOR ROOF
201'-0"
PARTS MEZZANINE
ISSUE DATE OCT. 25, 2023
162'-0" REVISIONS
FIFTH FLOOR
151'-9"
FOURTH FLOOR
140'-3"
THIRD FLOOR
129'-0"
SECOND FLOOR
4 114'-6"
OPEN
PROJECT NUMBER
3
E1
E1
2023 © EXCEL ENGINEERING, INC.
ARCHITECTS ● ENGINEERS ● SURVEYORS
Always a Better Plan
100 CAMELOT DRIVE
FOND DU LAC, WI 54935
PHONE: (920) 926-9800
WWW.EXCELENGINEER.COM
PROJECT INFORMATION
BELLAIRE, TX 77401-3005
WALTECH CO.INC.
8
D2
13 13
D2 D2
PROJECT ENGINEER
8 JEFF HENRIKSEN
D2 jeff.henriksen@excelengineer.com
8 8 (920) 322-1689
15 DRAWN BY: SBB
D2 D2
D2 PROFESSIONAL SEAL
11
D2
11
D2
7
3 D1
D1
F-10167
SUBMITTAL DATES
4 10 10
D1 D2 D2
PROJECT NUMBER
230381700
1 2 3 4
SHEET INFORMATION
S1 S1 S1 S1
SHEET NUMBER
S1
2023 © EXCEL ENGINEERING, INC.
ARCHITECTS ● ENGINEERS ● SURVEYORS
Always a Better Plan
100 CAMELOT DRIVE
FOND DU LAC, WI 54935
PHONE: (920) 926-9800
WWW.EXCELENGINEER.COM
PROJECT INFORMATION
BELLAIRE, TX 77401-3005
17 17
WALTECH CO.INC.
D2 D2
8 8
D2 D2
4 4
11
12
D2
4 4
D1 D1
8 8
D2 D2
14
D2
PROJECT ENGINEER
JEFF HENRIKSEN
jeff.henriksen@excelengineer.com
(920) 322-1689
DRAWN BY: SBB
PROFESSIONAL SEAL
11
D2
3 3
D1 D1
F-10167
SUBMITTAL DATES
12
ISSUE DATE OCT. 25, 2023
D2 REVISIONS
4 4 4
D1 D1 D1
PROJECT NUMBER
230381700
5 6 7 8
SHEET INFORMATION
S2 S2 S2 S2
SHEET NUMBER
S2
2023 © EXCEL ENGINEERING, INC.
ARCHITECTS ● ENGINEERS ● SURVEYORS
Always a Better Plan
100 CAMELOT DRIVE
FOND DU LAC, WI 54935
PHONE: (920) 926-9800
WWW.EXCELENGINEER.COM
PROJECT INFORMATION
BELLAIRE, TX 77401-3005
WALTECH CO.INC.
8 8
D2 D2
4
D1
8 16
D2 D2
PROJECT ENGINEER
JEFF HENRIKSEN
jeff.henriksen@excelengineer.com
(920) 322-1689
DRAWN BY: SBB
PROFESSIONAL SEAL
3
D1
3
D1
F-10167
SUBMITTAL DATES
4
D1 ISSUE DATE OCT. 25, 2023
REVISIONS
4
D1
PROJECT NUMBER
230381700
9 10 11 SHEET INFORMATION
S3 S3 S3
SHEET NUMBER
S3
2023 © EXCEL ENGINEERING, INC.
ARCHITECTS ● ENGINEERS ● SURVEYORS
Always a Better Plan
100 CAMELOT DRIVE
FOND DU LAC, WI 54935
PHONE: (920) 926-9800
WWW.EXCELENGINEER.COM
PROJECT INFORMATION
BELLAIRE, TX 77401-3005
WALTECH CO.INC.
1 2
D1 D1
1
D1 PROJECT ENGINEER
1
D1
JEFF HENRIKSEN
3 jeff.henriksen@excelengineer.com
(920) 322-1689
D1 DRAWN BY: SBB
PROFESSIONAL SEAL
4
F-10167
D1
SUBMITTAL DATES
PROJECT NUMBER
230381700
SHEET INFORMATION
SHEET NUMBER
5
D1
6
D1
7
D1 D1
2023 © EXCEL ENGINEERING, INC.
5
D1
PROJECT INFORMATION
9
D2 1 5
D1 D1
PROJECT CONTRACTOR
D1
BELLAIRE, TX 77401-3005
WALTECH CO.INC.
8 9 10 11 12
D2 D2 D2 D2 D2
13 14 15 16 17
D2 D2 D2 D2 D2
PROJECT ENGINEER
JEFF HENRIKSEN
jeff.henriksen@excelengineer.com
(920) 322-1689
DRAWN BY: SBB
PROFESSIONAL SEAL
F-10167
SUBMITTAL DATES
PROJECT NUMBER
230381700
SHEET INFORMATION
SHEET NUMBER
D2
2023 © EXCEL ENGINEERING, INC.
Design Calculations
STRUCTURAL CALCULATIONS
COLD-FORMED STEEL FRAMING
PROJECT 230381700
TABLE OF CONTENTS
1 COVER
2 GENERAL NOTES
3 DESIGN CRITERIA
4 - 21 STRUCTURAL CALCULATIONS
22 - 31 CONNECTION DESIGN
GENERAL NOTES
1. EXCEL ENGINEERING IS ACTING AS A SPECIALTY STRUCTURAL COMPONENT ENGINEER, DESIGNING THE COLD-FORMED STEEL FRAMING OF THE
PROJECT ONLY. EXCEL ENGINEERING TAKES FULL RESPONSIBILITY FOR THE DESIGN OF THE STRUCTURAL COLD-FORMED STEEL FRAMING AND
THEIR ATTACHMENT TO THE SUPPORTING STRUCTURAL ELEMENTS OF THE BUILDING. EXCEL ENGINEERING TAKES NO RESPONSIBILITY FOR THE
DESIGN OF ANY SUPPORTING STRUCTURAL ELEMENTS. IT IS ASSUMED THAT ALL SUPPORTING STRUCTURAL ELEMENTS HAVE BEEN DESIGNED
BY THE PROJECT ENGINEER OF RECORD (EOR) AND/OR ARCHITECT OF RECORD (AOR) TO WITHSTAND THE FORCES IMPOSED BY THE
STRUCTURAL COLD-FORMED STEEL FRAMING. EXCEL ENGINEERING EXPECTS THAT THIS COMPONENT SUBMITTAL WILL BE REVIEWED BY THE
EOR AND/OR AOR FOR CONFORMANCE WITH THE OVERALL PROJECT REQUIREMENTS.
2. SECTION PROPERTIES ARE ASSUMED TO BE IN ACCORDANCE WITH THE AMERICAN IRON AND STEEL INSTITUTE "NORTH AMERICAN
SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS" 2012 EDITION WITH SUPPLEMENTS. THE CONTRACTOR IS TO
VERIFY THAT THE MATERIALS INSTALLED MEET OR EXCEED THESE DESIGN VALUES.
3. ALL COLD-FORMED STEEL FRAMING HAS BEEN DESIGNED FOR UNIFORM LATERAL LOADS AND WALL CONSTRUCTION DEAD LOADS ONLY.
4. ALLOWABLE STRESS HAS NOT BEEN INCREASED DUE TO WIND. HOWEVER, THE STRENGTH LEVEL WIND LOAD HAS BEEN REDUCED TO 42% (70%
FOR SERVICE LEVEL) FOR THE PURPOSE OF DETERMINING DEFLECTION PER IBC 2012, TABLE 1604.3, NOTE F.
5. THE CONTENTS OF THIS SUBMITTAL SHOW THE APPLICATION OF COLD-FORMED STEEL FRAMING COMPONENTS. THE FRAMING CONTRACTOR IS
TO REFER TO THE PROJECT CONTRACT DOCUMENTS FOR ADDITIONAL REQUIREMENTS.
6. DIMENSIONS SHOWN HEREIN ARE FOR ENGINEERING PURPOSES ONLY AND MUST BE REVIEWED FOR THE PURPOSE OF APPROVAL. ALL
CONDITIONS ARE SUBJECT TO SUCH APPROVAL, AND TO FIELD VERIFICATION PRIOR TO FABRICATION OR ERECTION.
7. MECHANICAL BRIDGING SHALL BE USED IN ALL CASES WHERE INDICATED. INSTALLATION OF BRIDGING MUST BE COMPLETED BEFORE ANY
LOADS ARE APPLIED TO THE SYSTEM. ALL BRIDGING SHALL BE TERMINATED AT JAMBS, CORNER STUDS OR COLUMNS. BRIDGING ENDS SHALL
NOT HANG LOOSE. STUDS SHALL BE BRACED AGAINST ROTATION.
8. FOR SPECIFIC REQUIREMENTS AND WARRANTY INFORMATION ON SYSTEMS OR MATERIALS CONNECTED AND APPURTENANT TO THE COLD-
FORMED STEEL FRAMING INCLUDING CLADDING, SHEATHING, ROOFING, WINDOWS, DOORS, CAULKING AND FLASHING, REFER TO THE
MANUFACTURERS' DATA. THIS SUBMITTAL ASSUMES NO RESPONSIBILITY FOR THE PROPER CONSTRUCTION OR FUNCTION OF THE TOTAL
ARCHITECTURAL ASSEMBLY. THE COORDINATION OF ARCHITECTURAL AND/OR STRUCTURAL BUILDING COMPONENTS IS NOT UNDER THE
SCOPE OF THIS SUBMITTAL OR CONTRACT.
9. ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO PERPENDICULAR MEMBERS. STUD ENDS MUST SEAT TIGHTLY
INTO TRACKS IN ALL BEARING APPLICATIONS.
10. NO SPLICES IN STUDS, JOISTS, HEADERS, OR OTHER LOAD CARRYING MEMBERS MAY BE MADE WITHOUT PRIOR ENGINEERING REVIEW AND
SPECIFIC DETAILS FOR ANY SUCH REVISION TO THE ORIGINAL DESIGN.
11. THIS SUBMITTAL DOES NOT TAKE PRECEDENCE OVER THE CONTRACT DOCUMENTS WITH REGARD TO MINIMUM KSI, THICKNESS, DEPTH,
FLANGE WIDTH, OR SPACING, UNLESS APPROVED BY THE EOR AND/OR AOR.
12. THE CONNECTOR VALUES USED IN THIS SUBMITTAL ARE FROM PUBLISHED MANUFACTURER SPECIFICATIONS (VALUES ENCLOSED). ALL SCREW
AND WELD VALUES ARE BASED ON THE 2010 AISI NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL
MEMBERS WITH SUPPLEMENTS. WELDING PROCEDURE SHALL BE IN ACCORDANCE WITH AWS D1.3-98. THE CONTRACTOR SHALL CONFIRM
WITH THE MANUFACTURER THAT THE CONNECTORS THEY INTEND TO USE MEET OR EXCEED THE DESIGN VALUES REQUIRED.
13. THE CONTRACTOR IS RESPONSIBLE TO NOT OVERLOAD MEMBERS DURING CONSTRUCTION OR ERECTION AND TO SUPPLY ADEQUATE
TEMPORARY BRACING UNTIL PERMANENT BRIDGING PROVIDING STABILITY TO BOTH FLANGES IS IN PLACE.
14. TOUCH-UP ALL WELDS WITH ZINC-RICH PAINT (ASTM A-780). APPLY TO BOTH SIDES OF STUD.
15. FUTURE EXPANSION HAS NOT BEEN CONSIDERED AS PART OF THE DESIGN OF THIS PROJECT.
16. THE CONTRACTOR IS CAUTIONED AS TO NOT STORE ANY CONSTRUCTION MATERIALS OR UNDERTAKE ANY CONSTRUCTION OPERATION WHICH
WILL EXCEED THE DESIGN LIVE LOAD CAPACITIES NOTED.
100 CAMELOT DRIVE PROJECT: Audi Central Houston PAGE:
FOND DU LAC, WI 54935 LOCATION: Houston, TX
3
P: 920|926|9800 F: 920|926|9801 CLIENT: Waltech Co., Inc. DATE: 10/25/2023
www.excelengineer.com PROJECT #: 230381700 ENGR: JDH
DESIGN CRITERIA
GOVERNING CODES
2012 "INTERNATIONAL BUILDING CODE" IBC 2012
2010 "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES" ASCE 7-10
2010 "NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS" AISI S100-10
2011 "CODE OF STANDARD PRACTICE FOR COLD-FORMED STEEL STRUCTURAL FRAMING" AISI S202-11
1998 "STRUCTURAL WELDING CODE - SHEET STEEL" AWS D1.3-98
2011 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" ACI 318-11
DESIGN STRESSES
CONCRETE 4000 PSI = COMPRESSIVE STRENGTH (f'c)
STRUCTURAL STEEL 36 KSI (MIN) = YIELD STRESS (Fy) - ASTM A-36: ALL SHAPES U.N.O.
COLD-FORMED STEEL FRAMING 33 KSI (MIN) = YIELD STRESS (Fy) - A1003 U.N.O.
WELD ELECTRODES 60 KSI (MIN) = TENSILE STRENGTH (Fxx) @ THICKNESS < 1/8" (CFS FRAMING)
70 KSI (MIN) = TENSILE STRENGTH (Fxx) @ ALL OTHER THICKNESS
DESIGN LOADING
WIND: 139 MPH = STRENGTH LEVEL WIND SPEED
108 MPH = EQUIVALENT SERVICE LEVEL WIND SPEED
II = RISK CATEGORY
''C'' = EXPOSURE CATEGORY
0.18 = INTERNAL PRESSURE COEFFICIENT
139.00
BASIC WIND SPEED (3-SECOND GUST) = .........................................................................................................................................................................
MPH V FIGURE 26.5-1
C
EXPOSURE CATEGORY = ..........................................................................................................................................................................................
26.7.3
0.00 θ
ROOF PITCH = ...................................................................................................................................................................................................................
DEG
ON
ROOF PITCH REDUCTION = ..........................................................................................................................................................................................
85.50
MEAN ROOF HEIGHT = .....................................................................................................................................................................................................
FT h 26.2
0.00
PARAPET HEIGHT = ...........................................................................................................................................................................................................
FT hp
NO
PARAPET LIMITING HEIGHT & CONTINUITY = ..................................................................................................................................................................
51.48 qz
VELOCITY PRESSURE @ Z (C&C) = ....................................................................................................................................................................................
PSF EQ. 30.3-1
51.48 qh
VELOCITY PRESSURE @ h (C&C) = ....................................................................................................................................................................................
PSF EQ. 30.3-1
0.18 GCpi
INTERNAL PRESSURE COEFFICIENT = ................................................................................................................................................................................
TABLE 26.11-1
9.00
EDGE ZONE DIMENSION = ................................................................................................................................................................................................
FT a FIGURE 30.4-1
FOR BUILDINGS WITH A MEAN ROOF HEIGHT (h) GREATER THAN 60 FT AND LESS THAN 90 FT, VALUES FROM FIGURES
30.6.2
30.4-1 THROUGH 30.4-6 SHALL BE PERMITTED TO BE USED IF THE HEIGHT TO WIDTH RATIO IS ONE OR LESS.
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
Design Loads
Wall Lateral Pressure : 33.17 psf
Parapet Lateral Pressure :
RO Lateral Pressure : Jamb Only
Lateral element force multiplier
Strength : 1.0
Deflection : 0.7
Header: Box (lateral top, bottom)
Gravity Load at Header: 10 psf
Brace Settings
Flexural Distortional Distortional Interconnection
Component(s) Members(s) Bracing Axial KyLy Axial KtLt K-Phi(lb-in/in) Lm Spacing
Jamb Studs 600S162-43(33), (2) Non-Composite 72 in 72 in 72 in 0 None N/A
Vertical Header 600S162-43(33), Boxed Full N/A N/A 0 None N/A
Lat. Top Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Lat. Bottom Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Analysis Results
Axial Max Max. Moment Max. Bottom Top or End
Component(s) Members(s) Load (lb) KL/r (ft-lb) Shear (lb) Reaction (lb) Reaction (lb)
Jamb Studs 600S162-43(33), (2) Non-Composite 63.8 125 1169.8 425.4 425.4 319.6
Vertical Header 600S162-43(33), Boxed N/A N/A 53.1 63.8 N/A 63.8
Lat. Top Head 600T125-43(33), Single N/A N/A 88.0 105.8 N/A 105.8
Lat. Bottom Head 600T125-43(33), Single N/A N/A 0.0 0.0 N/A 0.0
Design Results
Deflection A+M V+M
Component(s) Members(s) Span Parapet Interaction Interaction Web Stiffners Design OK
Jamb Studs 600S162-43(33), (2) Non-Composite L/1029 L/0 0.599 0.42 R1, R2 Yes
Vertical Header 600S162-43(33), Boxed L/51525 NA 0.02 0.03 No Yes
Lat. Top Head 600T125-43(33), Single L/16942 NA 0.12 0.12 No Yes
Lat. Bottom Head 600T125-43(33), Single L/0 NA 0.00 0.00 No Yes
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
* Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Notes:
1) Values in parentheses are stress ratios.
2) Bridging connectors are not designed for back-back, box, or built-up sections.
3) Reference www.strongtie.com for latest load data, important information, and general notes.
4) CFS Designer will not select bridging connectors unless all flexural and axial bracing settings are the same.
5) If the bracing length is larger than the span length, bridging connectors are not designed.
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
Design Loads
Wall Lateral Pressure : 33.17 psf
Parapet Lateral Pressure :
RO Lateral Pressure : Jamb Only
Lateral element force multiplier
Strength : 1.0
Deflection : 0.7
Header: Box (lateral top, bottom)
Gravity Load at Header: 10 psf
Brace Settings
Flexural Distortional Distortional Interconnection
Component(s) Members(s) Bracing Axial KyLy Axial KtLt K-Phi(lb-in/in) Lm Spacing
Jamb Studs 600S250-54(50), Single 72 in 72 in 72 in 0 None N/A
Vertical Header 600S162-43(33), Boxed Full N/A N/A 0 None N/A
Lat. Top Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Lat. Bottom Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Analysis Results
Axial Max Max. Moment Max. Bottom Top or End
Component(s) Members(s) Load (lb) KL/r (ft-lb) Shear (lb) Reaction (lb) Reaction (lb)
Jamb Studs 600S250-54(50), Single 63.8 79 1169.8 425.4 425.4 319.6
Vertical Header 600S162-43(33), Boxed N/A N/A 53.1 63.8 N/A 63.8
Lat. Top Head 600T125-43(33), Single N/A N/A 88.0 105.8 N/A 105.8
Lat. Bottom Head 600T125-43(33), Single N/A N/A 0.0 0.0 N/A 0.0
Design Results
Deflection A+M V+M
Component(s) Members(s) Span Parapet Interaction Interaction Web Stiffners Design OK
Jamb Studs 600S250-54(50), Single L/836 L/0 0.499 0.44 No Yes
Vertical Header 600S162-43(33), Boxed L/51525 NA 0.02 0.03 No Yes
Lat. Top Head 600T125-43(33), Single L/16942 NA 0.12 0.12 No Yes
Lat. Bottom Head 600T125-43(33), Single L/0 NA 0.00 0.00 No Yes
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
* Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Notes:
1) Values in parentheses are stress ratios.
2) Bridging connectors are not designed for back-back, box, or built-up sections.
3) Reference www.strongtie.com for latest load data, important information, and general notes.
4) CFS Designer will not select bridging connectors unless all flexural and axial bracing settings are the same.
5) If the bracing length is larger than the span length, bridging connectors are not designed.
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
Design Loads
Wall Lateral Pressure : 33.17 psf
Parapet Lateral Pressure :
RO Lateral Pressure : Jamb Only
Lateral element force multiplier
Strength : 1.0
Deflection : 0.7
Header: Box (lateral top, bottom)
Gravity Load at Header: 10 psf
Additional Jamb Axial Load : 1000 lbs
Brace Settings
Flexural Distortional Distortional Interconnection
Component(s) Members(s) Bracing Axial KyLy Axial KtLt K-Phi(lb-in/in) Lm Spacing
Jamb Studs 600S162-97(50), (2) Non-Composite 72 in 72 in 72 in 0 None N/A
Vertical Header 600S162-43(33), Boxed Full N/A N/A 0 None N/A
Lat. Top Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Lat. Bottom Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Analysis Results
Axial Max Max. Moment Max. Bottom Top or End
Component(s) Members(s) Load (lb) KL/r (ft-lb) Shear (lb) Reaction (lb) Reaction (lb)
Jamb Studs 600S162-97(50), (2) Non-Composite 1040.0 133 2341.2 851.4 851.4 785.0
Vertical Header 600S162-43(33), Boxed N/A N/A 80.0 40.0 N/A 40.0
Lat. Top Head 600T125-43(33), Single N/A N/A 132.7 66.3 N/A 66.3
Lat. Bottom Head 600T125-43(33), Single N/A N/A 0.0 0.0 N/A 0.0
Design Results
Deflection A+M V+M
Component(s) Members(s) Span Parapet Interaction Interaction Web Stiffners Design OK
Jamb Studs 600S162-97(50), (2) Non-Composite L/1047 L/0 0.541 0.25 No Yes
Vertical Header 600S162-43(33), Boxed L/14232 NA 0.03 0.03 No Yes
Lat. Top Head 600T125-43(33), Single L/4680 NA 0.17 0.17 No Yes
Lat. Bottom Head 600T125-43(33), Single L/0 NA 0.00 0.00 No Yes
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
* Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Notes:
1) Values in parentheses are stress ratios.
2) Bridging connectors are not designed for back-back, box, or built-up sections.
3) Reference www.strongtie.com for latest load data, important information, and general notes.
4) CFS Designer will not select bridging connectors unless all flexural and axial bracing settings are the same.
5) If the bracing length is larger than the span length, bridging connectors are not designed.
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
Design Loads
Wall Lateral Pressure : 33.17 psf
Parapet Lateral Pressure :
RO Lateral Pressure : Jamb Only
Lateral element force multiplier
Strength : 1.0
Deflection : 0.7
Header: Box (lateral top, bottom)
Gravity Load at Header: 10 psf
Additional Jamb Axial Load : 1000 lbs
Brace Settings
Flexural Distortional Distortional Interconnection
Component(s) Members(s) Bracing Axial KyLy Axial KtLt K-Phi(lb-in/in) Lm Spacing
Jamb Studs 600S250-97(50), Single 72 in 72 in 72 in 0 None N/A
Vertical Header 600S162-43(33), Boxed Full N/A N/A 0 None N/A
Lat. Top Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Lat. Bottom Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Analysis Results
Axial Max Max. Moment Max. Bottom Top or End
Component(s) Members(s) Load (lb) KL/r (ft-lb) Shear (lb) Reaction (lb) Reaction (lb)
Jamb Studs 600S250-97(50), Single 1040.0 81 2341.2 851.4 851.4 785.0
Vertical Header 600S162-43(33), Boxed N/A N/A 80.0 40.0 N/A 40.0
Lat. Top Head 600T125-43(33), Single N/A N/A 132.7 66.3 N/A 66.3
Lat. Bottom Head 600T125-43(33), Single N/A N/A 0.0 0.0 N/A 0.0
Design Results
Deflection A+M V+M
Component(s) Members(s) Span Parapet Interaction Interaction Web Stiffners Design OK
Jamb Studs 600S250-97(50), Single L/709 L/0 0.573 0.40 No Yes
Vertical Header 600S162-43(33), Boxed L/14232 NA 0.03 0.03 No Yes
Lat. Top Head 600T125-43(33), Single L/4680 NA 0.17 0.17 No Yes
Lat. Bottom Head 600T125-43(33), Single L/0 NA 0.00 0.00 No Yes
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
* Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Notes:
1) Values in parentheses are stress ratios.
2) Bridging connectors are not designed for back-back, box, or built-up sections.
3) Reference www.strongtie.com for latest load data, important information, and general notes.
4) CFS Designer will not select bridging connectors unless all flexural and axial bracing settings are the same.
5) If the bracing length is larger than the span length, bridging connectors are not designed.
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
Design Loads
Wall Lateral Pressure : 32.19 psf
Parapet Lateral Pressure :
RO Lateral Pressure : 4-Ways
Lateral element force multiplier
Strength : 1.0
Deflection : 0.7
Header: Box (lateral top, bottom)
Gravity Load at Header: 10 psf
Brace Settings
Flexural Distortional Distortional Interconnection
Component(s) Members(s) Bracing Axial KyLy Axial KtLt K-Phi(lb-in/in) Lm Spacing
Jamb Studs 600S162-54(50), (2) Non-Composite 72 in 72 in 72 in 0 None N/A
Vertical Header 600S162-43(33), Boxed Full N/A N/A 0 None N/A
Lat. Top Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Lat. Bottom Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Sill 600T125-43(33), Single Full N/A N/A 0 None N/A
Analysis Results
Axial Max Max. Moment Max. Bottom Top or End
Component(s) Members(s) Load (lb) KL/r (ft-lb) Shear (lb) Reaction (lb) Reaction (lb)
Jamb Studs 600S162-54(50), (2) Non-Composite 146.6 126 2044.9 513.1 513.1 357.6
Vertical Header 600S162-43(33), Boxed N/A N/A 146.6 146.6 N/A 146.6
Lat. Top Head 600T125-43(33), Single N/A N/A 236.0 236.0 N/A 236.0
Lat. Bottom Head 600T125-43(33), Single N/A N/A 85.8 64.4 N/A 64.4
Sill 600T125-43(33), Single N/A N/A 166.3 144.9 N/A 144.9
Design Results
Deflection A+M V+M
Component(s) Members(s) Span Parapet Interaction Interaction Web Stiffners Design OK
Jamb Studs 600S162-54(50), (2) Non-Composite L/630 L/0 0.703 0.41 No Yes
Vertical Header 600S162-43(33), Boxed L/15533 NA 0.05 0.06 No Yes
Lat. Top Head 600T125-43(33), Single L/5263 NA 0.31 0.31 R1, R2 Yes
Lat. Bottom Head 600T125-43(33), Single L/15069 NA 0.11 0.05 No Yes
Sill 600T125-43(33), Single L/7624 NA 0.22 0.22 No Yes
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
* Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Notes:
1) Values in parentheses are stress ratios.
2) Bridging connectors are not designed for back-back, box, or built-up sections.
3) Reference www.strongtie.com for latest load data, important information, and general notes.
4) CFS Designer will not select bridging connectors unless all flexural and axial bracing settings are the same.
5) If the bracing length is larger than the span length, bridging connectors are not designed.
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
Design Loads
Wall Lateral Pressure : 32.19 psf
Parapet Lateral Pressure :
RO Lateral Pressure : 4-Ways
Lateral element force multiplier
Strength : 1.0
Deflection : 0.7
Header: Box (lateral top, bottom)
Gravity Load at Header: 10 psf
Brace Settings
Flexural Distortional Distortional Interconnection
Component(s) Members(s) Bracing Axial KyLy Axial KtLt K-Phi(lb-in/in) Lm Spacing
Jamb Studs 600S250-54(50), Single 72 in 72 in 72 in 0 None N/A
Vertical Header 600S162-43(33), Boxed Full N/A N/A 0 None N/A
Lat. Top Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Lat. Bottom Head 600T125-43(33), Single Full N/A N/A 0 None N/A
Sill 600T125-43(33), Single Full N/A N/A 0 None N/A
Analysis Results
Axial Max Max. Moment Max. Bottom Top or End
Component(s) Members(s) Load (lb) KL/r (ft-lb) Shear (lb) Reaction (lb) Reaction (lb)
Jamb Studs 600S250-54(50), Single 146.6 79 2044.9 513.1 513.1 357.6
Vertical Header 600S162-43(33), Boxed N/A N/A 146.6 146.6 N/A 146.6
Lat. Top Head 600T125-43(33), Single N/A N/A 236.0 236.0 N/A 236.0
Lat. Bottom Head 600T125-43(33), Single N/A N/A 85.8 64.4 N/A 64.4
Sill 600T125-43(33), Single N/A N/A 166.3 144.9 N/A 144.9
Design Results
Deflection A+M V+M
Component(s) Members(s) Span Parapet Interaction Interaction Web Stiffners Design OK
Jamb Studs 600S250-54(50), Single L/415 L/0 0.879 0.77 No Yes
Vertical Header 600S162-43(33), Boxed L/15533 NA 0.05 0.06 No Yes
Lat. Top Head 600T125-43(33), Single L/5263 NA 0.31 0.31 R1, R2 Yes
Lat. Bottom Head 600T125-43(33), Single L/15069 NA 0.11 0.05 No Yes
Sill 600T125-43(33), Single L/7624 NA 0.22 0.22 No Yes
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
* Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Notes:
1) Values in parentheses are stress ratios.
2) Bridging connectors are not designed for back-back, box, or built-up sections.
3) Reference www.strongtie.com for latest load data, important information, and general notes.
4) CFS Designer will not select bridging connectors unless all flexural and axial bracing settings are the same.
5) If the bracing length is larger than the span length, bridging connectors are not designed.
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0
Code: 2007 NASPEC w/2010 Supplement [AISI S100/S2-10] Simpson Strong-Tie® CFS Designer™ 5.0.1.0