FOR FURTHER DETAJLS REFER TO PLUMBING

DRAWING NO CGK062-SD-M-2012 GENERAL NOTES FOR FIRE PROTECTION


FOR CONTINUATION REFER 1. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE NOTED.
DRA\MNG NO CGK062-SD-M-1029 2. REFERENCE LEVEL FOR IL IS LEVEL 01 (+68900mm).
3. ALL FIRE PROTECTION EQUIPMENT & COMPONENTS SHALL BE OF APPROVED TYPE.
JI.. lt·IDU~Till 11 4. CONTRACTOR MUST VERJFY ALL DIMENSIONS ON SITE BEFORE COMMENCEMENT
OFWORJKS.
rnTRAtKE:··f'U·l 5. THE CONNECTION BETWEEN THE WATER SUPPLY MAJ NS AND THE FIRE HYDRANT
-·1 SIT[ 80Ut·WMiY
SHALL NOT BE LESS THAN 150MM NOMINAL BORJE.
6. THE FIRJE HYDRANT SHALL CONFORM TO LATEST SIN-03-1735-2000 OR OTHER
ACCEPTED EQUIVALENT STANDARD.
7. FIRE HYDRANTS SHALL BE OF THE PILLAR TYPE HAVING TWO 63.5mm NOMINAL
BORE OUTLETS. THE EXTERNAL THREADS OF THE OUTLETS SHOULD MATCH THE
LOCAL FIRE SERVICE'S STANDARD HOSE THREADED COUPLING CONNECTION.
8. THE OUTLETS SHALL BE PROVIDED WITH PROTECTIVE STANDARJD CAPS OF CAST
IRON OR OTHER SUITABLE MATERJAL AND ATTACHED TO THE STAND PIPE BY CHAJNS
,__ l'l'.J
9. ALL U/G PIPE iNSTALLATION SHALL BE COMPILANCE TO SNI 7511 2011.
0250 U/G HYD 0100 U/G HYD
IL -3620 r\1M IL -722 MM
OHB
" 10. MATERJAL FOR U/G OG SPK: DUCTILE IRON CEMENT-LINED: BS EN 545
11. MATERJAL FOR U/G ICM SPK: DUCTILE IRON CEMENT-LINED: BS EN 545
12. MATERJAL FOR U/G HYD: DUCTILE IRON CEMENT-LINED: BS EN 545
$V c~ ·Q
13. MATERJAL FOR U/G STOP: DUCTILE IRON CEMENT-LINED: BS EN 545.
0100 U/G ~YD
IL-2224~M
LEGEND:-
~ FIRE HYDRANT

~ SLUICE VALVE (NORMALLY OPEN)

0 VALVE CHAMBER BOX

@ SIAMESE CONNECTION

ABBREVIATIONS:-
sv SLUICE VALVE

M WATER METER

U/G UNDERGROUND
'.J
-----------=1
0100U/GHYD
HYD HYDRANT
IL-571 MM

, I ICM HYD INCOMING HYDRANT PIPE


I VALVE CHAMBER
I I ICMSPK INCOMING SPRJNKLER PIPE
.1 FOR FUTURE
TO SPRINKLER TANK 0100 U/G HYD I
I PROVISION TO 8.POD
IL-1031 MMJ
OGSPK OUTGOING SPRINKLER PIPE

I
ii",
1~
,z
•::,
,jl
c<
~
I
STOP

IL
STAND PIPE

I NVERTLEVEL
r-
U1,
:::,,
,o
m "' I 0250 U/G ~YDI RL ROAD LEVEL
0
Z, I IL-1722 MMJ
FFL FINISHED FLOOR LEVEL
... i
~
I al
I
,·,.1 cw DOMESTIC WATER SUPPLY

0100 U/G HYD GV GATE VALVE


I IL -1031 MM!
CV CHECK VALVE

f OHB GATE VALVE

I
I
I 0200 U/G HYD
IL-1119MM

-· - - - - --- ---- ·- --- ___,,.,

f:"~I_
OHB

CD ?~!RALL LEVEL 1 - FIRE HYDRANT LAYOUT 025lrOTG"HYD


IL-1723 MM
FOR FUTURE PROVISION TO 8-POD
® ~\R E HYDRANT DETAIL(TYP.)
8

SLUICE VALVE Ground Level


02sornn

/<0(0(0(0(0(0(0(0(0(0(0(< .•

,=,~mru~"'-"" ~ m m;,;mum
DUCTILE IRON
CEMENTLII\IEO
(OICL)

LEAN CONCRETE
g, 0150 U/G DICL TO
FIRE HYDRANT TANK COMPACTED SOIL

M ...,., 0150 U/G DICL TO


-. FIRE SPRINKLER TANK VALVE CHAMBER SECTION VIEW '1..8.lfl CHAMBER PLAN YIEW
&S POD BLOO SCALE NTS SCALE NTS

0
VALVE CHAMBER DETAIL
N.T.S
'
® ~-~~ERGROUND PIPE CONNECTION DETAIL (TYP.)
0 AS BUilT DRAWING
TENANT METER CHAMBER - PLAN VIEW AWS
OESIGt!CONSULTANT
AURECONPTELTD
PT JAYA0BAYA.5HI
6. PROJECT NAME
CGK 062 - KllC
PROJECT NO. DRAWING NO.

GK062-A8D-M-100
MECHAAICM. ELECTRCJ<I..
PROJECT EXECUTIVE OESIGNMAN/IGER MEPMAN/lGER
6. !PONTOON BRIDGE PRO.IECT)

6. BUILDING TTTlE SCALE DRAWN BY CHECl(EDf!f

~~
--·--------·-. ·----
,...J.-;,~ ~" AS

0 PLAN VIEW OF TENANT METER CHAMBER 6. OVERALL LEVEL 1 • FIRE


HYDRANT LAYOUT INDICATED PIS

6. ....
ffill PT. JAYA OBAYASHI

DATE APPROVED BY
\.::..) 1:50 YEOW MENG KOH/ CHEE MING CHUA JUNWEI LU SATOSHI SUZUKI AGUS ANORIY ANTO YOGI KUSUMA REV DESCRIPTION BY CKD APVD DATE