Conductor Test Report: Sample Details
Conductor Test Report: Sample Details
Sample Details:
Length 1000 mm Wire Size 9.0 X 3.0 mm
Insulation Thickness (mm) 0.3 Temperature 27 °C
Conductor Type Paper Covered Rectangular Copper Stripe
Test Data: The following test were conducted as per IEC-60851-5:2008 standard.
Parameter At Ambient Temperature At 20 °C At 75 °C
Resistance
660 641.84 784.5024
(μΩ)
Resistivity
0.00001782 1.73298E-05 2.11816E-05
(Ω-mm )
Conductivity
99.48
%
Summary:
Parameter Decleared Measured
Conductor Size (mm) 9.0 X 3.0 9.0 X 3.0
Covered Conductor Size (mm) 9.3 X 3.3 9.3 X 3.3
Insulation Thickness (mm) 0.3 0.3
Resistivity at 20°C (Ω-mm) N/A 1.73E-05
Conductivity (%) 99 99.48
Insulation Breakdown Voltage (KV) 2.1 2.1
Observations: Conductivity of this sample copper stripe is good and insulation break down voltage is as per
requirement.
_____________________________
Testted By:
MD. Islam Hossain
Engineer (QA &QC)
Adex Engineering Ltd.