Annexure-3 (LDB & SLDB)

S. NO PARAMETERS
1 Applicable standard
2 Voltage
3 Phase
4 Frequency
5 Neutral System
6 System Fault level
7 Rated insulation Voltage
8 Duty
9 Ambient Temperature
10 Construction
10.1 Type of board
10.2 Mounting
10.3 Sheet Steel type & thickness
10.4 Degree of protection of enclosure
10.5 Front access
10.6 Back access & clearance
10.7 Incoming cable & outgoing cable entry
11 Bus-Bar
11.1 Main busbar
11.2 Busbar Material
Maximum temperature rise including the
11.3 specified ambient temperature and derating
factor if any
Short time withstand current of Phase &
11.4
Neutral bus
11.5 Short time withstand current of earth bus

11.6 Earth busbar

11.7 Insulation
11.8 Colour coding

Clearance between Phase & Phase and


11.9
Phase & Earth / Neutral
12 Circuit breaker
12.1 Incomer
12.2 Incomer MCCB
12.3 Outgoing feeders

12.4 Outgoing MCBs

13 Wiring
13.1 Standard applicable
13.2 Power Circuit
13.3 Control circuit
13.4 Inter panel Wiring

13.5 Min Spare terminal blocks


Supply for panel space heater, illumination &
14
control supply
15 Indication lamps
15.1 Type
15.2 Incomer
15.3 Outgoing
16 Painting
16.1 Surface Treatment for Painting
16.2 Paint shade
nnexure-3 (LDB & SLDB)

REQUIREMENT OFFERED BY BIDDER


IS-8623 & IS-13947
240V, -10% to +10%
2
50Hz ± 5%
Solidly Grounded
10kA (RMS) for 1 second
1.1kV for 1 min
Continuous operation
50˚C

Metal enclosed, cabinet type, Indoor, dust & vermin proof


with neoprene gasket conforming to IS-8623 (part 1-3)
Wall / Column mounting on brackets
Cold Rolled sheet steel (CRCA), 2 mm thick.
3mm thick Gland plate, removable
IP-54
Hinged door
No rear access
Bottom

2 ph, 2 wire
High conductivity copper

90˚C

10 kA (RMS) for 1 sec


10 kA (RMS) for 1 sec
Cu earth bus-bar of adequate size & running throughout the
length of panels at bottom. Two separate terminals shall be
provided for external earth connection in conformity with
Indian Electricity Rules
Heat Shrunk PVC Sleeve.
IS 5578: 1984
IS 11353: 1985
25 mm (Minimum)

1 no. incomer of suitable rating DP MCCB


All MCCBs shall be of 10KA breaking capacity with short
circuit, overload and earth fault protection.
DP RCBO with 30mA sensitivity
All RCBOs shall be of 10KA breaking capacity with
overload, short-circuit and protection against earth leakage
currents

IS; 5575 - 1984 : Guide for marking insulated conductor


Insulated (1.1 kV) Flexible Copper Wire/ strip min 2.5 mm2
Copper 2.5 mm2 multi strand PVC wire, insulated
To be completed in each transportable Section. Provision
for inter shipping section wiring shall be provided with
complete termination facility
20% Spare teminal block to be considered
To be tapped from the bus bar of each section vide a
protective device (MPCB/ MCB) rated for 10kA short circuit
current

LED cluster with luminous intensity min. 100 mcd.


Feeder ON, OFF & TRIP indication to be provided
Not Reuired

Seven tank process.


RAL 7035 of IS:5
REMARKS