F400-Xe
Withdrawable circuit breaker
1 to 36 kV
F400-Xe range Contents 0
1 to 36 kV
Overview 2
Field of application 2
Continuity of service in complete safety 3
F400-Xe, a comprehensive solution 4
Quality - environment 8
F400-Xe range 9
Description 9
Operating conditions 13
Personal protection 14
Choice of functional units 16
F400-Xe products 18
Technical characteristics 18
Feeders and incomers 19
Bussectioning 20
Bus riser 21
Busbar metering and earthing 22
Current and voltage metering 23
Protection, monitoring and control 24
Protection system 24
Sepam series 20, series 40, series 80 25
Instrument transformers 27
Switchgear 31
Withdrawable parts 31
SF circuit breakers 32
GMH operating mechanism 33
SF1, SF2 circuit breaker selection guide 35
Installation 36
F400-Xe connection 36
Implementation examples 37
Dimensions 38
Appendices 39
F400-Xe cubicle equipment 39
1
Overview Field of application 0
b F400-Xe offers:
v pre-engineered solutions that can be adapted to your specific requirements,
v significantly reduced maintenance,
v local support centers throughout the world.
Applications
Power distribution
b Distribution substation,
PE40314
PE40311
b Delivery substation,
b Secondary transmission
substation.
Industry
b Oil and gas,
b Chemical industry,
b Metallurgy,
b Car industry,
b Mining,
PE40315
PE40312
Infrastructures
b Airports,
b Ports,
b Water treatment, etc.
PE40313
PE40313
2
Overview Continuity of service
in complete safety 0
Right from the design stage, F400-Xe has taken three key user requirements
into account:
Reliability
b Each performance level in the F400-Xe range has been type tested.
b F400-Xe has been designed, manufactured and tested in accordance with
PE40316
Simplicity
b A user interface that can be understood by all.
b Interlocks and padlocks to prevent operator errors.
PE40317
Safety
b All operations are performed from the front. (operations of rotary type voltage
transformer and installation of medium voltage cable connections from the rear side).
b Racking in or out is only permitted with the door closed.
b The power-on indicator is located on the front of the functional unit.
b The earthing switch has making capacity.
b ‘‘Anti-reflex” handles are used for all operations.
b Internal arc withstand developed for all functional units.
3
Overview F400-Xe,
a comprehensive solution 0
Sepam series 20, series 40 and series 80 have all the functions required to provide:
b effective protection of people and property,
b accurate measurements and detailed diagnoses,
b full equipment control,
b local or remote information and control.
Easy upgradeability
Their modular design allows communication, digital I/O, analog output or
temperature acquisition functions to be added.
4
Overview F400-Xe,
a comprehensive solution (continued) 0
Simple choice
DE55465ENr
To order your Transparent Ready™ switchboard, simply choose either the TRe-1
or TRe-2 service level.
A customized level is also available.
The Transparent Ready™ F400-Xe switchboard option comes equipped with a Web
server including Web pages dedicated to power equipment data.
Easy to commission
Transparent Ready™ equipment is delivered ready to be connected and
commissioned. A “Quick Start” guide, packaged with your switchboard,
provides three easy-to-follow steps.
F400-Xe switchboard
Instantaneous readings b b
Automatic display of updated measurements
Circuit summary b b
Displays the average rms current for the three phases (A rms),
the active power (kW), the power factor, the circuit breaker status
(if applicable), etc.
Rms current b b
Displays the rms current for each phase (A rms) for all circuits
Maximum current b b
Displays the average demand current for each phase (A)
for all circuits
Power b b
Displays the present demand (kW), the peak demand (kW)
and the time and date of the records
Energy b b
Displays the active energy (kWh) and reactive energy (kvarh)
consumption and the time and date of the records
Instantaneous readings, all devices b
Displays automatically updated readings for all the communicating
devices used in the equipment
Basic data, energy and trend logs b
Displays automatically updated readings for all the communicating
devices used in the equipment
Record display b
Displays data as time curves or tables
Data table export b
Allows data tables to be exported in a standard Windows format
5
Overview F400-Xe,
a comprehensive solution (continued) 0
Implementing
We oversee the completion and commissioning of your installation: design, cost
optimization, guaranteed performances and dependability, commissioning tests, etc.
Operating
We help run your daily operations in real time: maintenance contract, technical
assistance, supply of replacement parts, corrective and preventive maintenance,
operation and maintenance training, etc.
Operating Implementing
Modernizing
We can bring the performance of your installation up to date: installation audit,
switchgear diagnosis, adaptation and modification, end of life recycling, etc.
Equipment renewal
If you would like to maintain the same performance with the renewed equipment
without any disturbance on operations. We technically renew MV and LV
switchboards, soft starters, variable control units and PLCs in order to enhance the
efficiency of your installation.
Maintenance contracts
Regardless of the brand of materials used in your installation, the equipments
covering all or a part of your installation are regularly controlled by protective
maintenance in order to ensure the proper function and performance. Eliminate the
unexpected faults in your installation by protective and preventive maintenance.
Spare part
Ensure that existing equipment and products work properly by using original spare
parts. Our objective is to provide service with the spare part stock for Medium
Voltage, Low Voltage and Industrial Control products.
6
Overview F400-Xe,
a comprehensive solution (continued) 0
Automation Retrofit
Software and hardware faults of the all PLC brands and operator control panels
belonging to Schneider Electric are corrected professionally.
7
Overview Quality - environment 0
with standards.
This procedure is:
b uniform throughout all departments,
b recognized by many customers and approved organizations.
But above all, it is its strict application that has enabled us to obtain the recognition
of an independent organization:
AFAQ (the French Quality Assurance Association).
The quality system used in the design and manufacture of F400-Xe is certified
as conforming to the requirements of the ISO 9001: 2000 quality assurance
standard.
Environmental conservation
MT20069EN
8
F400-Xe range Description 0
PE56330
Earthing switch
LV control
cabinet
Voltage
transformers (VT)
Current transformers
(CT)
Cable connection
9
F400-Xe range Description (continued) 0
Composition of an F400-Xe
PE56329
PE40321
switchboard
b F400-Xe switchboards are made up of several
interconnected functional units.
b Power connections are made between functional
units within a switchboard via a single busbar.
b The electrical continuity of all metal frames is
provided by the connection of each functional unit's
earthing busbar to the switchboard's main earthing
circuit.
b Low voltage wiring trays are provided in the
switchboard above the LV control cabinets.
b LV control cables can enter the switchboard through
the top and bottom of the cubicle.
Circuit breaker compartment
PE40323
PE40322
Cable compartment Busbar compartment
10
F400-Xe range Description (continued) 0
The F400-Xe cubicle is type LSC2B (Loss of Service Continuity Category) as defined
by IEC 62271-200. This category specifies the possibility of the power being allowed
to remain on in one compartment while another compartment is open.
The medium voltage parts are separated by metal partitions (PM class) which
are earthed.
The F400-Xe cubicle consists of three MV compartments:
b the circuit breaker compartment containing the withdrawable part (circuit breaker,
disconnector unit or earthing unit),
b the busbar compartment,
b the cable connection compartment containing the earthing switch,
the current sensors and any voltage transformers.
IAC (internal arc classification) The F400-Xe cubicle is classified as IAC AFLR as per IEC 62271-200 standard
The different sides of metal-enclosed switchgear can have appendix A.
different classes of accessibility. The following codification is
used to identify these panels (in accordance with The low voltage auxiliaries and the monitoring unit are located in a low voltage
IEC 62271-200). control cabinet which is separate from the medium voltage section.
A: accessibility restricted to authorized personnel Four basic functional units are provided:
F: access to the front panel b incomer or feeder AD6
L: access to the side panels
R: access to the rear panel b in-line bussectioning CL6 - GL6
b busbar metering and earthing TT6
b current and voltage metering VITM6
The AD and CL cubicles have withdrawable switchgear.
Cable compartment
LV control cabinet
DE56724
11
F400-Xe range Description (continued) 0
Withdrawable part
The withdrawable part includes:
b The circuit breaker or the earthing unit with its closing and opening mechanism,
or the disconnector unit,
b The racking in/out handle propulsion mechanism, interlocks for fixing the
withdrawable part firmly to the fixed part in the operating or disconnected position.
Surface treatment
b All the metal surfaces of the switchboard are treated to protect them from corrosion.
b The metal is manufactured in accordance with a galvanization process defined
by ISO 3575.
b The front surfaces are electro-plated sheets metal with an epoxy polyester
coating, standard color RAL 9002 and have been put through the surface tests laid
down in standards IEC 60068-2-11.
b The side surfaces are galvanized.
12
F400-Xe range Operating conditions 0
Operating conditions
Normal operating conditions in accordance with IEC 62271-1 (IEC
60694) for indoor switchgear
b Ambient air temperature:
MT20072
Storage conditions
In order to retain all the qualities of a functional unit during prolonged storage,
we recommend that the equipment is kept in its original packaging, in a dry place
sheltered from the sun and rain at a temperature between – 25°C and + 55°C.
Standards
The F400-Xe range conforms to the following IEC international standards:
b IEC 62271-1 (IEC 60694): common clauses for high-voltage switchgear,
b IEC 62271-200: AC metal-enclosed switchgear for rated voltages
between 1 and 52 kV,
b IEC 62271-100: high-voltage alternating current circuit-breakers,
b IEC 60282-2: high-voltage fuses,
b IEC 62271-102: alternating current disconnectors and earthing switches,
b IEC 60255: measuring relays and protection equipment,
b IEC 60044-1: current transformers,
b IEC 60044-2: voltage transformers.
13
F400-Xe range Personal protection 0
The F400-Xe internal arc protection is AFLR type (all four sides of the cubicle
are protected) in order to protect operators when they go behind the cubicle.
The F400-Xe switchboard is installed in a room with a minimum height of 4 m.
F400-Xe is designed to eliminate the effects of internal arcing safely, by:
b locating metal flaps above the enclosure to limit overpressure in the compartments
in the event of an internal fault,
b using nonflammable materials for the cubicle.
Switchboard operations
The switchboards are installed, operated and maintained from the front panel.
Certain installation and maintenance operations are performed from the rear
of the cubicle:
b installation of medium voltage cables,
b operation of voltage transformers.
14
F400-Xe range Personal protection (continued) 0
Rack-in inhibition
Rack-in/out
Earthing switch
position indicator Rack-in/out indicator
4-position selector
b extraction
b test
b rack-in
b in operation
Open pushbutton
Options
b Disabling of racking in. This function disables the possibility of racking the
withdrawable part in.
15
F400-Xe range Choice of functional units 0
Selection:
You want to supply power to a transformer.
You have selected a transformer feeder/breaker.
The corresponding functional unit will therefore be a TF-B, comprising an AD cubicle
fitted with a withdrawable circuit breaker and a transformer application Sepam.
Device Circuit breaker Circuit breaker Circuit breaker Circuit breaker Circuit breaker
F400-Xe single-line
diagrams
MT20080
MT20081
M M
16
F400-Xe range Choice of functional units (continued) 0
DE40364
MT20078
DE40363
M
M M
17
F400-Xe products Technical characteristics 0
The values below are given for normal operating conditions as defined
in IEC 62271-200 and IEC 62271-1 (IEC 60694).
PE40329
(1) On functional units equipped with circuit breakers the breaking capacity is equal to the short-time withstand current.
In each case the peak withstand current of the device is 2.5 times the short-time withstand current for 50 Hz,
and 2.6 times the short-time withstand current for 60 Hz.
(2) Contact us, for your requirements up to 40 kA rms 3s.
18
F400-Xe products Feeders and incomers 0
AD6
DE56730
Functions
b Cubicle
v IAC AFLR LSC2B PM.
DE56731
b LV control cabinet
P2
b Withdrawable part
P1 v SF1 1250 A circuit breaker,
v SF2 2500 A circuit breaker,
v disconnector unit.
P2
b Earthing switch
v making capacity.
P1
b Voltage indicator
v VPIS.
19
F400-Xe products Bussectioning 0
CL6
DE56734
Functions
b Cubicle
v IAC AFLR LSC2B PM.
DE56735
b LV control cabinet
b Withdrawable part
v SF1 1250 A circuit breaker,
v SF2 2500 A circuit breaker.
b Voltage indicator
v VPIS.
20
F400-Xe products Bus riser 0
GL6
DE56736
Fixed type VT
Rotary type VT
Functions
b Cubicle
v IAC AFLR LSC2B PM .
DE56737
b LV control cabinet
b Voltage indicator
v VPIS.
P1 P1
b Anti-condensation heating element
21
F400-Xe products Busbar metering and earthing 0
TT6
DE56738
Fixed type VT
Rotary type VT
Functions
b Cubicle
v IAC AFLR LSC2B PM.
DE56739
b LV control cabinet
b Voltage indicator
v VPIS.
22
F400-Xe products Current and voltage metering 0
VITM6
DE56740
Left cubicle
Right cubicle
Functions
b Cubicle
v IAC AFLR LSC2B PM.
DE56741
b LV control cabinet
b Voltage indicator
v VPIS.
b Current transformers
P2
v conventional DIN format current transformers.
P1
b Anti-condensation heating element
b Meter
23
Protection, monitoring Protection system 0
DE56710
Current transformer
system consisting of:
b instrument transformers to measure
Metering equipment
the required electrical values (phase protection relay
current, residual current, voltages, etc.),
b protection relays, with functions
appropriate for the part of the network
to be protected,
b metering equipment, to provide
information to operators,
b low voltage relays to control, amongst
other things, the breaking device (circuit
breaker) of the withdrawable part,
b various auxiliaries: secondary circuit test
units, etc. LPCT or LV toroid current transformer
(please consult us) Switchgear (circuit breaker)
all the necessary protection, metering, control, monitoring and indication functions
are performed by Sepam.
Like the F400-Xe range, the Sepam range of relays is designed to provide the
optimum solution for each application; it includes:
b Sepam S, for the protection of substation incomers and feeders,
b Sepam B, for the protection of busbars,
b Sepam T, for the protection of transformers,
b Sepam M, for the protection of motors,
b Sepam G, for the protection of generators,
b Sepam C, for the protection of capacitors.
Advantages of Sepam
Reliability
b Over 20 years of experience in multi-function digital relays for the protection
of medium-voltage electrical networks.
b Cumulative experience of more than 150,000 Sepam protection relays in use
in over 90 countries.
Quality
b Design quality based on dependability objectives and a thorough analysis of
environmental constraints: temperature, pollution, EMC, dielectric strength, etc.
b Manufacturing quality based on procurement agreements with suppliers and
quality control at all stages of the manufacturing phases.
Easy to use
b Local operation facilitated by the ergonomic man-machine interface (MMI)
providing users with clear, comprehensive information in their own language.
b Easy to set up with the flexible user-friendly configuration software.
24
Protection, monitoring Sepam series 20, series 40,
0
PE40013
1
3 4
Simplicity
Easy of installation
b Easy-to-install remote modules common to all Sepams.
Implementation assistance
b Predefined functions implemented by simple parameter setting,
b Powerful, user-friendly PC configuration software.
Intuitive use
b Clear graphic LCD display of all data required for local operation and diagnosis
of the installation,
b The working language can be customized to be understood by all users.
25
Protection, monitoring Sepam series 20, series 40,
0
b 8 temperature
sensor inputs
b 1 Modbus
communication port
protection
Frequency- B22
derived
(ROCOF)
Sepam series 40
b 10 logic inputs Current, S40 T40 G40
b 8 relay outputs voltage and
DE56713
b 16 temperature frequency
sensor inputs protection
b 1 Modbus Directional S41 M41
communication port earth fault
b logic equations editor
Sepam series 80
b 42 logic inputs Current, S80
b 23 relay outputs voltage and
DE56714
b 16 temperature frequency
sensor inputs protection
b 2 Modbus Directional S81 T81 M81
communication ports earth fault
b logic equations editor
phase
overcurrent
Transformer or T87 M88 G88
motor-
transformer
differential
26
Protection, monitoring Instrument transformers 0
and control
by phase(1) by phase
kV A kA size and type
12-36 1250/1600 31.5 2 2 x AOPC
12-36 2000 31.5 3 2 x ARL4
12-36 2500 31.5 4 2 x ARL5
(1) Cable section for size 3 terminations: 150 to 630 mm2.
They are specifically designed for the Sepam range and can be connected directly
to the “residual current” of the Sepam devices.
They differ only in their diameter:
b CSH 120 - internal diameter 120 mm,
b CSH 200 - internal diameter 200 mm.
CSH toroid CT
27
Protection, monitoring Instrument transformers 0
Benefits:
b the same probe measures the phase currents between 5-1250A
b accuracy guarantee in the measurement range:
v protection: class 5P for 5A-40kA
v measurement: class 0.5 for 100-1250A (0.75 for 20A, 1.5 for 5A)
b Easy installation:
TPL190 low power current transformers, v secondary cabling ready for connection
Phase current measurement in 5-1250A range
v easy connection on isolated cable in each cubicle type
b Safe use:
v secondary circuit trips under load
Technical characteristics
Type TLP190
Standard IEC60044-8
Minimum primary 5A
current
Rated primary current 100A
Rated secondary voltage 22.5 mV
Rated maximum primary current 1250A
Measurement 0.5 (100A-1250A), 0.75 (20A), 1.5 (5A)
accuracy class
Protection accuracy class 5P
Accuracy limit factor 400
Rated short-time 40 kA/1s
current
Isolation 0.75 kV
Rated power frequency withstanding voltage 3 kV
28
Protection, monitoring Instrument transformers 0 0
29
Protection, monitoring Instrument transformers (continued) 0
and control
Each one is protected by a fuse incorporated into the transformer primary winding.
They are operated simultaneously from the rear of the cubicle.
When the voltage transformers are in the “isolated”, position, the following operations
can be performed with the cubicle powered on:
b a fuse can be replaced by opening a safety flap,
b transformers can be accessed by installing a padlockable separator.
30
Switchgear Withdrawable parts 0
They include:
b the circuit breaker with its opening and closing mechanism, the disconnector unit
PE56329
Circuit breaker
A circuit breaker is a safety device used to operate and protect electrical distribution
networks. It is fitted in the F400-Xe cubicle to protect all the downstream components
DE56716
Earthing unit
The earthing unit is a safety feature used to earth the cubicle busbar. It is installed
in place of the circuit breaker and provides many locking possibilities.
DE56717
Disconnector unit
The disconnector unit enables the upper and lower part of the cubicle to be short-
circuited. It is installed in place of the circuit breaker and provides the same locking
DE56718
possibilities.
Racking handle
This handle is used to:
b rack the withdrawable part in/out,
DE56719
31
Switchgear SF circuit breakers 0
SF range
SF circuit breakers work on the basis of the “puffer” type principle in SF6,
PE50184
in SF circuit breakers.
The live parts are housed in an insulating enclosure which is sealed for life,
as specified in IEC 62271-100.
The switchgear used in the F400-Xe cubicles therefore has the following
characteristics:
b long service life,
b maintenance-free live parts,
b high electrical endurance,
b very low overvoltage,
b dependability,
b environmental insensitivity,
b possibility of continuous monitoring of the status of the circuit breaker.
Pre-compression (fig. 2)
When the contacts begin to open, the piston compresses the SF6 gas slightly
in the compression chamber.
Fig. 3 Fig. 4
32
Switchgear GMH operating mechanism 0
SF circuit breakers are actuated by the GMH operating mechanism which ensures
that the closing and opening speed of the breaking device is not operator-dependent.
028368
The circuit breakers are fitted with a GMH electrical operating mechanism.
They are used for remote operation and to ensure a fast resetting cycle.
Auxiliary contacts
The GMH operating mechanism is fitted with a block of 14 auxiliary contacts
including:
b 1 changeover contact for the electrical control,
b 1 changeover contact for indication,
b 1 contact for the power-on release.
The number of available contacts depends on the composition of the control
and on the options selected (see table below).
(1) Mitop: release with its own optional current used in combination with the Sepam 100 LA
protection relay.
Rated current 10 A
Breaking capacity AC 10 A at 220 V (cos j u 0.3)
DC 1.5 A at 110 or 220 V (L/R y 0.01 s)
33
Switchgear GMH operating mechanism 0
Auxiliaries diagram
DE56720
Sm1
Sm2 Sm3
Sn
M1
M
QF
J
M1 M2
KN
SE Y01 SP M3
YM Y02
YF
Mitop SQ
J Circuit breaker
M Spring charging motor
YF Closing release
M1-M2 End of charging contact
QF Auxiliary circuit breaker contacts
KN Anti-pumping relay
SE Latched release contact
Y01-Y02 “Shunt” opening releases
YM Undervoltage opening release
“Mitop” “Mitop” opening release (with its own current)
M3 Operating mechanism charged contact
SP Pressure switch contact
SQ Device ready-to-operate contact
Sm1 Closing pushbutton (external)
Sm2 Opening pushbutton for shunt releases (external)
Sm3 Opening pushbutton for undervoltage releases (external)
Sn Closing disabling contact (external)
34
Switchgear Circuit breaker selection guide
SF1, SF2 0
Circuit breakers
Type of cubicle Type of circuit breaker
Incomer/feeder SF1 - SF2
Bussectioning
Electric resetting device with opening and closing mechanism b
(GMH)
“Shunt” closing release b
Opening release 1 release b
2 releases v
Withdrawable part rack-in padlocking v
Auxiliary voltages
Spring charging motor
DC 24 48 110 220
AC 50 Hz 110 220
Opening or closing coils
DC 24 48 110 220
AC 50 Hz 110 220
35
Installation F400-Xe connection
36
Installation Implementation examples 0
In-line distribution
1 AD6 - Incomer (with or without voltage transformers).
2 AD6 - Feeder (with or without voltage transformers).
3 CL6 - Bussectioning (with or without voltage transformers).
4 GL6 - Bus riser (with or without voltage transformers).
DE56722EN
-
2 1 3 4 1 2
(1) Depending on the width of the first cubicle on the left of the switchboard.
Note: the switchboard is aligned on the front panel and all the cubicles have the same depth.
37
Installation Dimensions 0
Type Un (kV) In (A) Number of Width Depth Height Weight Weight with
cables without VT without VT VT
AD6 36 1250 4 maximum 900 3074 2255 1315 1440
2500 4 maximum 1100 3074 2255 1660 1785
CL6 36 1250 900 3074 2255 1185 1310
2500 1100 3074 2255 1510 1635
GL6 36 1250 1100 3074 2255 1230 1355
1250 1100 3074 2255 1230 1450*
2500 1100 3074 2255 1280 1405
2500 1100 3074 2255 1280 1500*
TT6 36 900 3074 1110
VITM6 36 1250 2000 3074 2255 2175
2500 2200 3074 2255 2450
* Weight with rotary VT. The rest are weight with fixed VT.
PE40336
38
Appendices F400-Xe cubicle equipment 0
36 kV - 70 kV - 170 kV
Current transformers
None b b b
Conventional DIN format v v b
Toroidal on cables v
LPCT on cables v
CSH toroids (volumetric balance) v
Cubicle
Voltage present indicator b b b b b
Degree of protection of the enclosure IP3X b b b b b
Degree of protection between compartments IP2X b b b b b
Internal arcing protection, 25 kA - 1s b b b b b
Lightning arrester v v
Anticondensation heating element (cable compartment and busbar) b b b b b
LV control cabinet
Keyless LV control cabinet locking v v v v
LV control cabinet lighting v v v v
Busbar
1250 A or 2500 A exposed b b b b
1250 A or 2500 A insulated v v v v
Connection
Cable connection from the bottom, 1 to 4 single-pole b
Cable connection from the bottom, 1 to 4 three-pole b
(1) if earthing switch
(2) the voltage transformer may be selected as rotary or fixed type
(3) rotary or fixed type should be selected
b : standard
v : option
39
Notes 0
40
Notes 0
41
Notes 0
42
AMTED399053EN © 2006 Schneider Electric - All rights reserved