Professional Documents
Culture Documents
200KVA Station Transformer
200KVA Station Transformer
200KVA Station Transformer
RFQ
S.No DESCRIPTION UNIT QTY
1 Station Transformer 200KVA 33KV/415V 50Hz Nos 10
GENERAL CONDITIONS
01. 200KVA Station Transformer should be follow the as per technical specification (Refer the Annexure-I).
02. The technical offer shall be submit with its GTP to be filled up by the manufacturer in manufacturer’s
Letter head pad (Refer the Annexure-II).
1|Page
REQUEST FOR QUOTATION
(200KVA Station Transformer)
ANNEXURE-I
2|Page
28.6 Earthing Terminals
Two substantial steel flag type terminals having two 14mm diameter holes on 55mm
centers shall be located one on either side and near to the bottom of the transformer to
facilitate connection to the local earthing system.
The following plates, or an approved combined plate, shall be fixed to each transformer
tank at an average height of 1500 mm above the ground level:
a) A rating plate bearing the data specified in IEC 76 Part 1. This plate shall also include
the short-circuit current rating and time-factor for each winding.
b) A Diagram plate showing in an approved manner the internal connections and the
voltage vector relationship of the several windings, in accordance with IEC 76 Part1
with the transformer voltage ratio for each tap and, in addition a plan view of the
transformer giving the correct physical relationship of the terminals.
c) A plate showing the location and function of all valves and air release cocks or plugs.
This plate shall also if necessary warn operators to refer to the Maintenance Instructions
before applying vacuum.
Plates are to be of stainless steel or other approved material capable of withstanding the
rigorous of continuous outdoor service at site.
The Contractor shall supply Station Auxiliary transformer with 10 MVA & 20 MVA OLTC
Transformer.
Auxiliary transformers shall be hermetically sealed two-winding, conservator type, three-phase, oil
immersed, ONAN, with Off Load Tap Changing, suitable for outdoor use.
The station auxiliary transformers shall be 33/0.415 kV and have a maximum continuous rating of
100 kVA, shall be capable of supplying the maximum continuous rating for all tap positions and
maintaining rated voltage on the low voltage winding, under the maximum ambient temperature
conditions, without the temperature rise of the top oil exceeding 50°C or the temperature rise of the
windings as measured by resistance exceeding 55°C.
Transformers shall be in accordance with the relevant IEC standard and this specification. Refer to
the Schedule of Technical Particulars and Guarantees for other relevant requirements.
Off-load tap-changing shall be carried out by means of an external hand-operated tapping switch
mounted on the side of the tank. All phases of the tapping switch must be operated by one hand
wheel.
The tapping switch shall have a spring-loaded captive bolt or other approved means on the moving
part which positively locates the switch correctly at each tapping position. This bolt must be
278
lockable at each tapping position and shall be provided with a suitable padlock and keys. Moving
the switch from one tapping position to another shall require that the bolt be withdrawn by hand
from its locating socket on the transformer tank against the spring pressure.
Tap-position numbers corresponding to the tapping switch bolt-locating sockets shall be cast or
engraved in a metal indication plate fixed to the tank and a keyed metal pointer on the tapping
switch operating handle shall show clearly at which tapping number the transformer is operating.
All tap-position indicators shall be marked with one integer for each tap position, beginning at
number 1. Adjacent taps shall be numbered consecutively in such a manner that when moving a tap
to a new tapping position which has a higher number, the no-load output voltage of the untapped
winding increases.
All gaskets, unless otherwise approved, shall be in one continuous piece without joints. Gaskets
shall not be compressed before use. Provision shall be made for earthing the body of each cable
box. Removable blank gland plates and suitable type and size of cable glands shall be supplied and
fitted for termination of the cables.
Dehydrating breather and draining holes protected by 1 mm aperture mesh shall be incorporated at
the base of the box to avoid moisture condensation within cable box and ensure drainage of
condensation respectively. Cable boxes shall be provided with suitable means for clamping the
armor wires of the cables.
Gland plates for single core cable shall be made from non-ferrous metal. The Contractor shall
guarantee (test certificate shall be supplied to prove) that the air clearances and the creep age path
on the bushing connecting to the associated switchgear or transformers shall be such that the
completed installation shall withstand in air the impulse and power frequency voltages appropriate
to the plant.
The cable box clearances would meet the requirements for BS 6435 for partially insulated cable
boxes. An earthing terminal shall be provided in each sealing end chamber to which the
connections from the transformer winding can be earthed during cable testing. Cable boxes shall be
279
provided on 33kV/11kV sides suitable for air insulations terminations of XLPE Copper Conductor
cables of minimum sizes as mentioned below:
The transformers shall be provided with approved devices of Kilhstrom for indicating the top oil
temperature and hottest spot winding temperatures. The devices shall have a dial type indicator
and, in addition, a pointer to register the highest temperature reached. Each winding temperature
device shall have four separate contacts fitted, two of which shall be used to control the two groups
of cooling plant motors (i.e. AF1 and AF2), one to give an alarm and one to trip the associated
circuit breakers. The Temperature indicating device shall be from MR Germany or equivalent
European class.
To simulate indication of the hottest spot temperature of the winding the device shall comprise a
current transformer associated with one phase only and a heating device designed to operate
continuously at 130 percent of transformer CMR current and for30 minutes at 150 percent of CMR
current, associated with a sensing bulb installed in an oil tight pocket in the transformer top oil.
The winding temperature indicators (WTI) shall be housed in the marshalling cubicle. The tripping
contacts of the winding temperature indicators shall be adjustable to close between 80°Cand 150°C
and to re-open when the temperature has fallen by not more than 10°C.
The alarm contacts and the contacts used to control the cooling plant motors on the above devices
shall be adjustable to close between 50° C and 100° C and to re-open when the temperature has
fallen by a desired amount between 10° C and l5° C.
All contacts shall be adjustable to a scale and must be accessible on removal of the relay cover.
Alarm and trip circuit contacts shall be suitable for making or breaking 150 VA between the limits
or 30 volts and 250 volts AC or DC and of making 500 VA between the limits of 110 and250V
DC. Cooler motor control contacts shall be suitable for operating the cooler Contractors direct or,
if necessary, through an interposing relay.
The temperature indicators in the marshalling kiosk shall be so designed that it is possible to move
the pointers by hand for the purpose of checking the operation of the contacts and associated
equipment. The working parts of the instrument shall be made visible by the provision of cut-away
dials and glass-fronted covers and all setting and error adjustment devices shall be easily
accessible.
Connections shall be brought from the device to terminal boards placed inside the marshalling
cubicle.
Terminals, links and a 63mm moving iron ammeter shall be provided in the marshalling kiosk for
each WTI for:
a) Checking the output of the current transformer.
b) Testing the current transformer and thermal image characteristics.
c) Disconnecting the bulb heaters from the current transformer secondary circuit to enable the
instrument to be used as an oil temperature indicator. Links shall be provided as shown on
the drawing enclosed with the offer.
280
31.2 Gas and Oil-Actuated Relays (Buchholz Relays)
Each transformer shall be fitted with gas and oil-actuated relay equipment having alarm contacts
which close on collection of gas or low oil level, and tripping contacts which close following oil
surge conditions. The Relay shall be from MR, Germany or equivalent European class.
Each gas and oil-actuated relay shall be provided with a test cock to take a flexible pipe connection
for checking the operation of the relay by inserting air in the relay. The floats of the Buchholz shall
be solid body. Each relay shall be fitted with UV protective covered glass window for indication of
gas volume.
To allow gas to be collected at ground level, a small bore pipe shall be connected to the gas release
cock of the gas and oil-actuated relay and brought down to appoint approximately1400 mm above
ground level, where it shall be terminated by a cock which shall have provision for locking to
prevent unauthorized operation.
The design of the relay mounting arrangements, the associated pipe work and the cooling plant
shall be such that multi operation of the relay will not take place under normal service conditions,
including starting or stopping of oil circulating pumps, whether by manual or automatic control
under all operating temperatures.
The pipe work shall be so arranged that all gas arising from the transformer will pass into the gas
and oil-actuated relay. The oil circuit through the relay must not form a delivery path in parallel
with any circulating oil pipe, nor is it to be fed into or connected through the pressure relief vent.
Sharp bends in the pipe work shall be avoided.
When a transformer is provided with two conservators, the gas and oil-actuated relays shall be
arranged as follows:
a) If the two conservators are connected to the transformer by a common oil pipe, one relay
shall be installed in the common pipe.
b) If the two conservators are piped separately to the transformer, two relays shall be installed,
one in each pipe connection.
The clearance between oil pipe work and live metal shall be not less than the minimum clearances
stated in the schedule of requirement.
281
The Contractor shall supply the first filling of all insulating oil required for the operation of the
Plant and, after treatment, a test shall be made in the Project Manager‟s presence to prove that the
breakdown voltage is at least 60kV at 2.5mm electrode gap.
Transformer Oil
Application Insulating mineral oil for Transformer
Grade of oil Class-1
a) Physical Properties
Appearance Liquid and free from suspended matter or sediment
Density at 200C 0.895g/cm3 (maximum)
Flash point (Closed cup) 0
140 C (minimum)
0 800 cst. (Maximum)
Kinematics Viscosity at-15 C
0 40 cst. (Maximum)
Kinematics Viscosity at-20 C
Pour point -300C (maximum)
b) Electrical Properties
Dielectric Strength at 50 Hz (with 2.5
On new untreated oil, the break down voltage shall be at
mm standard gap and 40 mm standard
depth) least >60KV.
Surge arresters shall be of the type employing non-linear metal oxide resistors without spark gaps.
The Contractor shall demonstrate by calculations that the surge arresters will adequately protect the
switchgear arrangement.
Surge arresters shall be housed in porcelain insulators designed to withstand extremes of the
environment described. The insulation shall have a minimum creepage distance of 25mm/kV rated
system phase to phase voltage. Porcelain shall comply with IEC 60233. The method of sealing
against the ingress of moisture shall be of a type well proven in service and the manufacturing
procedures shall include an effective leak test which can be demonstrated to the inspecting engineer
if required. The MCOV of the Arresters are given below. MCOV exceeding the given range will
not acceptable.
The detailed calculation for Surge arrester operation and performance should be provided during
implementation prior to supply of each Surge arrester.
282