Professional Documents
Culture Documents
Electric Motor Control Circuits
Electric Motor Control Circuits
ELECTRICAL
General principles on control of electric motors
Controller Purpose
4) Gear: The desired speeds and operating characteristics are the direct
function and purpose of the controllers. These protect engines,
operators, machines and materials while they operate.
5) Speed control: Some controllers can maintain very precise speeds for
industrial process purposes, but other types are needed to change
motor speeds stepwise or gradually.
6) Operator Safety: Many mechanical safeguards have given rise to
electrical methods. Electrical control pilot devices directly affect
controllers by protecting machine operators from unsafe conditions.
7) Protection against damage: Part of the function of an automatic
machine is to protect itself from damage, as well as the manufactured
or processed materials. For example, conveyor blockages are
prevented. Machines can be run in reverse, stopped, run at slow speed
or whatever is necessary to perform the protection work.
8) Maintaining Starting Devices: Once installed and properly adjusted,
motor starters will maintain reliable starting times, voltages, current
and torque, for the benefit of the driven machine and power system.
Properly sized fuses, circuit breakers, and disconnect switches for
starting are good installation practices governed by electrical codes.
EI
T
BUTTON STATION FOOT SWITCH
THE COLOR IS
THREE- INDICATED BY
PHASE THE LETTER ON
MAGNETIC THE LAMP
COIL
PNEUMATIC SWITCH TIMED PNEUMATIC
SWITCH
and the interlock and the start button are released. Parts of a
control
circuit.
The basic or most common elements in a control circuit are indicated below.
Power circuit.
1)Three-phase motor
Three-Phase Motor: It is
one that requires 3 phases to operate and with a voltage greater than or equal to
220V. The characteristic of this motor is that by reversing the outputs; That is, the
phases change the direction of rotation of the rotor and, unlike alternating current
motors, it consumes less current. It has a squirrel cage rotor that has shorted bars
that rotate magnetically around its stator.
Protection.
1) Magnetic starters:
Class 8501
Type P122
I Th2 12 A
660 VAC
These starters limit the current in the starting stage, avoiding reaching
currents that could cause harmful fluctuations in the power line. These
starters have overload and short circuit protection in all 3 phases and offer
ambient temperature compensation and also have start and stop buttons,
mounted in their cabinet.
• Thermal protection
• button station
• contactor
The contactor is designed to support the load of the motors; That is, it is
connected directly to the line, whereas the relays have weaker contacts and
are not connected to the lines directly. Contactors support even more current
than relays (up to 7A). These in turn vary in size depending on the load to
be fed.
2) Control relay: 220- 380- 500 VAC 4- 6- 8
A
Automatic controls:
1) Time relay:
a) Float switch:
1) Drum switch:
Indicators
1) Pilot lights:
110-220 VAC
50/60Hz
1.5W
The main function of the lights is to signal that something is happening:
*Green: Indicates that the engine is running or in good condition.
Relaxation.
*Red: Indicates that the engine has stopped or is in poor condition. Alarm.
*Amber: Indicates caution or that something is about to happen.
2) Digital ohmmeter:
It is an instrument used to measure electrical
resistance (R). Its unit of measurement is the
Ohm (Ω). There are 2 types of ohmmeters, the
first, which is the one that comes integrated with
the multimeter and the second, the analog one.
These types of devices should not work
with any voltage and/or amperage otherwise they
could be damaged. If this scale is not known, it
will not be damaged if it is not correct; However,
it would not mark the value, so the scale would have to be selected well to
give us the value accurately!
To measure high resistances, multiples are used and to measure small
resistances, submultiples are used.
Megaohms (M Ω) = 1,000,000Ω
Kilohms (K Ω) = 1000 Ω
Hectohms (Ω) = 100 Ω.
This instrument can be used to verify that terminals have continuity.
3) Cicada:
Generally, the buzzer, like the
red light, indicates prevention
or alarm; as well as the engine
being stopped.
Terminals:
They are the conductors of the current and must be verified with the
multimeter on the Ohms (Ω) scale to see if they are not cut from one point.
Material:
• 2 Button Stations
• 2 Magnetic starters
• 1 Three-phase motor
• 35 terminals
• 1 multimeter
Diagram:
a) Control
b)
Strength
Symboogea
| B A1 Commonly closed
Flow of current
BQH/I of sorzargue one connection of Mi
oo II
IB Start button 8
Coartco comrzmenf
AS closed from M2
A.C.
OO Termal
numbering.
Coil of Mi
M
BPI Q©
Stop button one
| B.P.S.
AC Bobirza
A.C.
Unemployment
bulletin 8
LE2 eende
redlight
Commonly open goniactoi
of MS
Functioning:
contact of M and energizes the coil of M and the green light, then the
2 1
open), while in the power circuit the contacts of M close and make the motor
1
rotate clockwise. Even if BA is released, the M coil and the green light will
1 1
open.
Pressing BP will de-energize M and the green light and the normally open
1 1
contact will open and the normally closed contact will close and the motor will
stop running.
in the power circuit the contacts of M close and make the motor rotate
2
Pressing BP will de-energize M and the normally open contact will reopen
2 2
and the normally closed contact will close and the motor will stop running.
Diagram:
R normally
Green open contact
light Wiring
numbering
F normally
Cicada open contact
Coil R
Functioning:
By pressing BAR , current passes to the R coil, which closes its normally open
contact, which is the interlock, and operates the red light and the buzzer that
are connected in parallel in relation to the R coil, indicating that the motor is
rotating clockwise. Since in the power circuit the normally open contacts of R
were closed
Or the other way around, BAF could be pressed first, energize the F coil that
sends an interlock signal to the commonly open F and turn on the green light,
indicating that the motor is rotating counterclockwise, then now the interlock
would not occur nor would it occur. would energize the R coil by pressing
BAR ; Otherwise, the red light and the buzzer would only be energized, but
without reversing the rotation, since the mechanical protection prevents the 2
coils from being energized at the same time.
time. In both cases the system is de-energized by pressing any stop button.
When you press BAF, the current passes to the F coil which, once energized,
sends a locking signal to its normally open contact, the green light turns on
indicating that the motor is rotating counterclockwise and the electrical
protection is activated and energized. the coil A of the control relay which
commands to open its commonly closed contact of A , this is the one that is
connected in series with the start button of R , that is why when you want to
press it the red light, the buzzer or the buzzer no longer turns on. the coil of R ,
since the line is disconnected.
CONTROL CIRCUIT
Or conversely, the BAR could be pressed, and the current passes to the coil R
which, once energized, sends a locking signal to its normally open contact,
turns on the red light and the buzzer indicating that the motor is rotating
clockwise. clockwise and the other electrical protection is activated,
energizing coil B of the control relay which commands the opening of its
normally closed contact of B, which is the one connected in series with the
start button of F , so when you want to press it The green light or the F coil no
longer turns on because the line is disconnected.
Material:
•
1 Limit switch
• 1 level switch
• 1 Drum Switch
• 1 Magnetic starter
• 2 Button Stations
• 1 Pilot lights
• 35 Terminals
• 1 Multimeter
• 1 Three-phase motor
Diagram:
CONTROL CIRCUIT
Switch of
drum
Green light
Coil M
current flow
Contact normally
closed coil M
Functioning:
When energizing the circuit, it will be in the off position, then current will
flow through the normally closed contact of M and the red light will be
energized. Indicating that the engine is out of service.
CONTROL CIRCUIT
When the circuit is energized, the motor must turn on and the green
light indicating that the motor is energized. If the level switch and the limit
switch are closed, both will allow the electric current to pass.
The motor will stop working if there is a level (since the switch will be
open) or if the limit switch is open. If any of the 2 switches open, the flow of
current will be prevented; On the other hand, if they were connected in
parallel, it did not matter if one was open, as long as one was closed, it would
be enough for the current to pass through there. Meanwhile, when coil M is
energized, it commands its normally open M contact to open and turns off the
red light. Then in the power circuit its normally open contacts close and
energize the motor.
By energizing the circuit and pressing any start button, either BAR or BAL, coil
M is energized and the green light turns on indicating that the engine is
running, then coil M commands its normally open M contact to close and the
circuit and opens the normally closed contact of M turning off the red light.
While in the power circuit the normally open contacts of M are closed and the
motor is energized.
In both cases; Whether manual or automatic, pressing BPL de-energizes coil M
which commands its normally open contact to open (unlocks) and to close the
normally closed contact of M , turning on the red light again indicating that the
motor is out of service.
CONTROL CIRCUIT
Material:
• 1 Control relay
• 2 Button Stations
• 1 Pilot lights
• 2 Magnetic starters
• 1 Cicada
• 2 Time relays (10 and 20 seconds)
• 35 Terminals
• 1 Multimeter
• 2 three-phase motors
Diagram:
Symbology
current flow
Wiring
Normally closed contact numbering
of coil A
Functioning:
When you energize the circuit, the buzzer will turn on, RT will start counting 1
10 seconds and after those 10 seconds RT will close its normally open contact
1
of RT but engine 1 will not work as long as neither of the 2 start buttons is
1
By pressing any start button (either local or remote), coil A will be energized,
its normally closed contact will open and the buzzer will stop working, the
normally open contact will close and latch the circuit and start engine 1 and
the green light indicating that it is in service, RT will also be energized and
2
will begin to count 20 seconds, after 20 seconds RT will order its normally
2
open contact to close RT energized motor 2 and its red light indicating that it
2,
is last is in service.
Pressing any stop button (whether local or remote) will de-energize all the
coils, returning their contacts to their normal position, turning off the lights,
the motors and turning on the buzzer again. The exception here is the RT coil 1
which will remain energized and its normally open contact will remain closed.
And nothing will happen until the entire system is de-energized or any start
button is pressed.
5. Timed ignition of 2 motors by means of time relays.
Material.
• 1 Control relay
• 2 Button Stations
• 1 Pilot lights
• 2 Magnetic starters
• 1 Cicada
• 2 Time relays (10 and 20 seconds)
• 35 Terminals
• 1 Multimeter
• 2 three-phase motors
Diagram:
Functioning:
When energizing the circuit, the current will pass through the normally closed
contact of A and will turn on the buzzer indicating that both motors are out of
service.
Pressing any start button (whether local or remote) will energize coil A , which
will open its normally closed contact and turn off the buzzer, close its
normally open contact and interlock the circuit, energizing RT and RT , then
1 2
RT counts 10 seconds to close its normally open contact and energize motor 1
1
to close its normally open RT contact and energize motor 2 and a red light to
2
Pressing any stop button (whether local or remote) will de-energize all the
coils, returning their contacts to their normal position, turning off the lights,
the motors and turning on the buzzer again.
FORCE CIRCUIT
CONTROL CIRCUIT
Material:
• 1 Drum Switch
• 1 Limit switch
• 1 level switch
• 1 Control relay
• 2 Button Stations
• 1 Pilot lights
• 2 Magnetic starters
• 1 Cicada
• 2 Time relays (2 for 10 seconds)
• 35 terminals
• 1 Multimeter
• 2 three-phase motors.
Diagram:
Functioning:
When energizing the circuit, it will be in the off position, then current will
pass through the normally closed contact of A and the buzzer will be energized
indicating that both motors are out of service.
CONTROL CIRCUIT
When the circuit is energized, the coil of A must be turned on, which
commands its normally closed contact of A to open and at the same time the
buzzer goes off, it also commands its normally open contact of A to close,
locking the circuit and energizing RT and RT , both count 20 seconds to close
1 2
their normally open contacts of RT and RT respectively and at the same time
1 2
energize the coils M and M then turn on the green and red lights also
1 2
When you press the local or remote start button, coil A should turn on,
commanding its normally closed contact of A to open and at the same time the
buzzer goes off, it also commands its normally open contact of A to close,
interlocking the circuit and energizing RT and RT , both count 20 seconds to
1 2
close their normally open contacts of RT and RT respectively and at the same
1 2
time energize the coils M and M then the green and red lights also turn on
1 2
indicating that the 2 motors are in service. Pressing any of the 2 stop buttons
will de-energize the motors and lights, then the coil contactors return to their
initial position and the buzzer is energized again indicating that the 2 motors
are out of service again.
FORCE CIRCUIT
CONTROL CIRCUIT
REFERENCES