Professional Documents
Culture Documents
Standard A.010 RNE
Standard A.010 RNE
Standard A.010 RNE
The materials displayed here are the responsibility of their authors and have exclusively educational purposes, in
educational activities with members of the student community, without direct or indirect profit Law No. 822 Article * 41
subsection C Template developed by: Virtual Education Center 201 1
www.urp.odu.pe
National Building Regulations
National
STANDARD A. 010
Building
GENERAL DESIGN CONDITIONS Regulation
Article 1.- To fulfill its objective, this National Building Regulation is based on
the following general principles:
GENERAL PRINCIPLES
Article 1.- To fulfill its objective, this National Building Regulation is based
on the following general principles:
Article 8.- The location and location plan must contain the
URBANIZATION :
NAME OF THE ROAD :
PROPERTY N* :
- magnetic north,
Uao3
NET DENSITY
BUILDING COEF
MAXIMUM HEIGHT
or -
NORMATNO LOT AREA TOTAL ROOFED AREA DATE
(*) For new buildings, enter information only in this column. ( m ) For remodeling, it is not added to the subtotal area
required to build on the property. (”) To calculate the subtotal area , the area to be demolished is subtracted . Detail the accumulated area (upper floors, basements, semi-basements, etc. ) in section 8 Observations of the FUE.
GE STANDARD. 020
COMPONENTS
RNE AND CHARACTERISTICS OF THE PROJECTS
Article 9.-
Art. 2 r--------------------------------------------------------------------------------------------------------------------
Exceptionally, designers may propose alternative and/or innovative solutions that satisfy the criteria established in
the third article of this Standard , for which the proposed alternative must be sufficient to achieve the objectives in a
manner equivalent to or superior to what is established herein. regulation.
Yo
Yo
In this case, the designer may, if he wishes, base his proposal using NFPA 101 regulations or other equivalent
standards recognized by the Competent Authority.
It should be noted that compliance with this NFPA 101 Regulation is not a requirement , it will only be used to support
an alternative solution.
STANDARD A.010
CHAPTER
RNE I DESIGN CHARACTERISTICS
Urban and Building Parameters
Art. 4
The urban and building parameters must be defined in the Urban Plan.
Parameter Certificates must state:
a) Zoning.
b) Sections of current roads and, where appropriate, of roads planned in
the Urban Plan of the town.
c) Permitted land uses.
d) Building coefficient.
e) Minimum percentage of free area.
f) Building height expressed in meters.
g) Withdrawals.
h) Regulatory lot area, applicable to the subdivision of lots.
i) Net density expressed in inhabitants per hectare or in minimum area of
the units that will make up the building.
j) Parking requirements for each of the permitted uses.
k) Risk or protection areas that could affect you.
l) Qualification of immovable cultural property, if applicable.
m) Particular conditions.
CHAPTER II RELATIONSHIP OF THE BUILDING WITH THE PUBLIC ROAD
STANDARD A.010
Art. 8
RNE
Buildings must have at least one access from the outside. The number of entrances and their dimensions are defined according to
the use of the building. Access from the outside can be pedestrian and vehicular. The mobile elements of the accesses, when
activated, may not invade the roads and areas of public use.
Main Door 1 00mt Minimum Width RNEA020 Art. 12 Pta.Deldepto90m 9mne2hojosune
Pedestrian Pue ria P r in cipaled if classcensor 1 . 20mt. RNE A120 ArtB a Only for buildings with elevator.
RNEA010Art32 A120 A«21y
Ramp 1.00m Width Minimum Max.12% 9.a
Includes handrailssee conditions of %
Ramp 0 Elevator RNE A 120 Art. 7.9a and 21 Minimum straight entrance and exit platform dimension 1x120m
ACCESS Give to trained RNEA020.Art.12 Minimum Multifamily Pia 1 20m. RNE A120 Art.B
Front elevator min . 1.50my turning radius RNE A120 Art.6 c and 11 e Turning every 25 linear meters
Doors Invasion Invades Public Area RNE A010 Art.B and An 67.0 Includes Garage Door
Building Up to 15m high 3m vehicle height
Ed if Withdrawals +20m Access to Emergency Vehicles RNE A 010 Art. 8 From 16m to * 4m vehicle height
In the case of buildings that are removed from public roads vehicles (ambulance, first aid vehicle), with a minimum height
by more than 20 m, the architectural solution must include and turning radii according to the attached table and at a
at least one road that allows the accessibility of emergency maximum distance of 20 m from the furthest building:
STANDARD A.010
RNE EDIFICATION
VEHICLE
HEIGHT
ACCESS
WIDTH
TURNING
RADIUS
Adjacent WALLS Request (Project) Plastering, draping and frosting RNEA010Ar.9 Starting from the 2nd
floor.
STANDARD A.010
RNE II RELATIONSHIP OF THE BUILDING WITH THE PUBLIC
CHAPTER
ROAD
Art. 11
Frontal withdrawals can be used to:
a) The construction of steps to go up or down with a maximum of 1.50
m from the sidewalk level .
b) The construction of water cisterns and their respective pump rooms.
c) The construction of guard houses and their respective bathrooms.
d) Vehicle parking lots with light roofs or without roofs.
e) Semi-basement parking spaces, whose upper ceiling level does not
exceed 1.50m above the level of the sidewalk in front of the lot.
f) Opaque front sills .
g) Walls for electric energy meters
h) Natural gas and LPG regulators and meters .
i) Underground storage of LPG and combustible liquids.
Cistern slipways. fences, meters, gas, eaves, limestones, pools
Frontal Permitted uses RNEA010Ar.11 substation SCl equipment, others
Corner Minimum octave 3m on the bisector RNE A 010 Art.13 Allow visibility
Side/ Back According to Municipality Parameters RNE A01Ü Artlla
STANDARD A.010
RNE II RELATIONSHIP OF THE BUILDING WITH THE PUBLIC
CHAPTER
ROAD Art. 11
Frontal withdrawals can be used to:
Discharge devices (floor intakes) and return (LPG liquid fuel) CANTILEVER +
j) OVER RETREAT
o) Floor level discharges from smoke ventilation systems in the event of fire.
p) And others duly supported by the designer.
q)
STANDARD A.010
RNE II RELATIONSHIP OF THE BUILDING WITH THE PUBLIC
CHAPTER
ROAD Art. 12 (fences)
Fences are intended to provide visual and/or hearing protection and provide security to the
building's occupants; must have the following characteristics:
a) They may be placed on the property line, and may be opaque.
and/ or transparent . The placement of fences
opaque does not vary the size of the required withdrawals.
b) The height will depend on the environment.
c) They must have a finish consistent with the building they
surround.
d) Connections may be installed for use by firefighters (Siamese
Valve).
e) Boxes may be installed for “loading and return” reception of
LPG
f) Connections may be installed for the discharge of hydrocarbons
and also water.
g) Boxes for energy meters may be installed.
h) When safety devices are installed that could put people at risk, they must be properly
marked.
STANDARD A.010
RNE II RELATIONSHIP OF THE BUILDING WITH THE PUBLIC
CHAPTER
ROAD Art. 13 (Ochaves)
Corner Minimum octave 3m . on the bisector RNE A 010 Art.13 Allow visibility
Side/ Back According to Municipality Parameters RNE A 010 Al14.a
STANDARD A.010
RNE II RELATIONSHIP OF THE BUILDING WITH THE PUBLIC
CHAPTER
ROAD Art. 14 (overhangs) Tank stands, zeros, meters, gas, eaves, limestones, pools sub station
Frontal Permitted uses RNE A 010 Art.11 equipment pos SCl, others
Corner Minimum octave 3m on the bisector RNE A 010 Art.13 Allow visibility
Side/ Back According to Municipality Parameters RNE A 010 Art 14.
wW
Attr. 17 The separation of buildings between properties as
well as the separation between buildings within the same
property (lot) are established for seismic safety reasons
that are established in the corresponding structural
calculation, in accordance with earthquake resistant
standards.
STANDARD A.010
RNE III SEPARATION BETWEEN BUILDINGS
CHAPTER
VISUAL Dormt Living rooms, Dining studios Parameters RNEA010Art 18.a Min.5m 01/3 building
Art. 18
In Residential Complexes , made up of several multi-family buildings, the separation between them, for reasons of privacy and
natural lighting, will be determined based on the use of the rooms that Bedrooms or studies Living rooms and dining rooms
S: 1/3Hb S: 1/3H
Minimum Minimum
5.00 5.00
STANDARD A.010
RNE III SEPARATION BETWEEN BUILDINGS Art. 18
CHAPTER
Dormt Living rooms, Studies, dining rooms Parameters RNEA010Art 18.a Min.5m 01/3 building
RECORD Minimum Separation
VISUAL (between Parameters RNEA010Art.
Kitchen and Covered Patios Min.4m or % ah. edification
18.b
housing blocks)
Terraces To Neighbors Dividing wall minimum height 230m. WEA 020 Art. 20 Height of patios: tongs and last floor.
S: 1/4Ha
Minimum
STANDARD A.010
RNE III SEPARATION BETWEEN BUILDINGS
CHAPTER
Art. 19 WELLS FOR NATURAL LIGHTING AND VENTILATION
Edit 15m See for Building < a 1 5m 10% minimum side 1 8Om
Minimum RNEA.010Ar19.ayc
Edit > at 15m View for Building > 15m 20%
2.20m per side
Parameters RNEA010Art.
LIGHT WELLS Dimensions Dormt Living rooms, Dining studios 1/3 facing + ground floor from 1 m. from the floor.
19.b
Parameters RNEA010Art.
Kitchen and Covered Patios 19.c % facing + bottom from 1 in . of floor
2m
minimum
Wells for natural lighting and ventilation must meet the following characteristics:
For single-family homes , they will have a minimum dimension of 2.00 m per side
measured between the faces of the walls that define the well.
STANDARD A.010
RNE III SEPARATION BETWEEN BUILDINGS
CHAPTER
Art. 19 WELLS OF LIGHT – MULTIFAMILY HOUSING
Edit 15m See for Building < 1 5m 10% minimum side 1 8Om
Minimum RNEA.010Ar19.ayc
Edit > at 15m View for Building > 15m 20%
2.20m per side
Parameters RNEA010Art. 1/3 facing + ground floor from 1 m. from the
LIGHT WELLS Dimensions Dormt Living rooms, Dining studios
floor.
19.b
Parameters RNEA010Art.
Kitchen and Covered Patios 19.c % facing + bottom from 1 in . of floor
a) They will have minimum dimensions of 2.20 m per side, measured between the
faces of the walls that define the well.
STANDARD A.010
RNE III SEPARATION BETWEEN BUILDINGS
CHAPTER
Art. 19 WELLS OF LIGHT – MULTIFAMILY HOUSING
Edit 15m See for Edd < a 15m 1 0% minimum slope 1 80m
Minimum RNEA.010Ar19.ayc
Building at 15m View for Edd > at 15m 20%
2.20m per side
Parameters RNEA010Art.
LIGHT WELLS Dimensions Bedroom Living rooms, Dining studios 1/3 lower facing ♦ from 1 m. from the floor.
19.b
Parameters RNEA010Art.
Kitchen and Covered Patios 19.c % facing + bottom from 1m from the floor
T
O
b)
The perpendicular distance
between the openings of the
rooms of bedrooms, studies,
rooms
and
dining rooms , which use the
well measured at the central
point or axis of the opening and
the opposite wall that makes up
the well must not be less than
one third of the height of the Yo Yo
ie________Yeah
lowest face of the well, l<I S: 1/3Hb
>11 €------—>
A = 1/3H
Minimum 2.20 1
Minimum 2.20
STANDARD A.010
RNE
measured from 1.00 m above the lowest floor.
Edit 15m See for Building < 1 5m 10% minimum side 1 8Om
Minimum RNEA.010Ar19.ayc
Edit > at 15m View for Building > 15m 20%
2.20m per side
Parameters RNEA010Art. 1/3 facing + ground floor from 1 m. from the
LIGHT WELLS Dimensions Dormt Living rooms, Dining studios
floor.
19.b
Parameters RNEA010Art.
Kitchen and Covered Patios 19.c % facing + bottom from 1 in . of floor
When the dimension of the well perpendicular to the openings it serves is greater than 10% than the minimum established in
sections b) and c) above, the perpendicular dimension of the well may be reduced by a proportional percentage to a
minimum of 1.80. m
In buildings 15 meters high or more , when the dimension of the well perpendicular to the openings it serves is less than
the minimum established in sections b) and c) above by up to 20% , the minimum perpendicular dimension of the well must
increase. in a proportional percentage.
STANDARD A.010
RNE IV MINIMUM DIMENSIONS OF THE ENVIRONMENTS
CHAPTER
Art. 21
The Dimensions, area and volume of the building environments must be those necessary to:
KITCHENS , SH, circulation passage , warehouse and Nat or art air renewal must be guaranteed.
VENTILATION Room Ventilation storage can illuminate through other environments RNE A DIO Art 21.c,51Y52 The warehouses and warehouses can be ventilated through
mechanical ventilation ducts.
STANDARD A.010
RNE IV MINIMUM DIMENSIONS OF THE ENVIRONMENTS
CHAPTER
Art. 22
Rooms for equipment or space for mechanical installations may have a minimum height of 2.10m, as long as they allow the
entry and permanence of standing people for installation, repair or maintenance.
Interior of homes ≥ 0.90m. Passages that serve as access to up Passages that serve as
to 2 homes ≥ 1.00m. access to up to 4 homes ≥
STANDARD A.010
RNE V ACCESS AND CIRCULATION PASSAGES
CHAPTER
Art. 25
CIRCULATION PASSAGES
entry to the
evacuation route
apartment door
Maximum: 56 m without sprinklers
71 m with sprinklers
STANDARD A.010
RNE
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
STANDARD A.010
RNECesar Cerron Estares
Arch.
Andres.cerron@urp.edu.pe
Art. 26
STAIRS
STANDARD A.010
RNE
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
Art. 26.- There are 2 types of stairs :
A. INTEGRATED
They are those that are not isolated from horizontal circulation and whose objective is to satisfy the transit needs of
people between floors in a fluid and visible manner .
8.Have a minimum free width of the staircase section of 1.20 m. This width may include the projection of the
handrails.
9.Have handrails on both sides separated from the wall by a maximum of 5cm. The width of the
handrail will not be greater than 5 cm.
STANDARD A.010
RNE
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
b. EVACUATION, Characteristic
s
10. They must be built of non-combustible material, in
any case they must maintain the structural mm WALL
L FIREBREAK
resistance to fire requested in section 15.
11. There must be no obstacles, combustible materials,
ducts or openings inside the stairwell.
12. Passages from the inside of the box to the outside STANDIN
must have fire protection (sealant) no less than the G AREA
► LOBBY
systems are permitted. PREVIOUS
AREA
LOBBY
STANDARD A.010
RNE
14. Have stairwell enclosures with a fire resistance of 1 hour if it is up to 15 meters high; 2 hours in case they are from 15
b. EVACUATION, Characteristic
meters high to 72 meters high;sand 3 hours if they are 72 meters high; and 3 hours if
they are 72 meters high or more.
15. Have fireproof frames, doors and accessories with a resistance of no less than 75% of
the resistance of the stairwell they serve and must also be smoke proof in accordance
with Standard A.130.
16. The space under the stairs cannot be used for any use if it is located inside the stairwell.
STANDARD A.010
RNE
b. EVACUATION
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
Characteristic
18. s uprights is not permitted through the evacuation staircase, except for fire safety systems. They must
Access to ducts and/or
have a fire hose pass, square type with a side of 0.20 m, no more than 0.30 m high, measured at the top of the pass, duly
marked inside the staircase, maintaining the fireproof enclosure with material that is easily frangible from the inside of the
staircase.
19. The evacuation staircase must not have openings other than the access doors.
20. The evacuation staircase may not be of a spiral type, unless it communicates a maximum of two continuous levels, serving
no more than 5 people, with a handrail on both sides and with a light risk classification.
STANDARD A.010
RNEVI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
CHAPTER
b. EVACUATION, Characteristic
Guy s 'Not Presumed3 r
,Indicate Type RNEA010Ar.26.B.3.3
Broad Minimum measurements 1 20m wide RNEA010Art.26.B.8
Steps and Contrasteps Comply with rule 20p+ 1 p=.60m or 64m RNEA010Ar.29.c Res dential.25m steps max 18 m counterstep
Non-Flammable Materials
1st Floor Hall RNE AÜ1Ü Art. 26.b3
No need for a previous lobby
To Technical Rooms Minimum width 90m RNEA010Art.28.f
Between lower and upper floors Located at download level
Addressing Barrier RME AÜ1Ü Art.26.B.4
Exterior openings on each floor with
OPEN EVACUATION
STANDARD A.010
RNEVI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
CHAPTER
TYPES OF EVACUATION STAIRS
B 1 WITH PREVIOUS VENTILATED LOBBY (FOR SMOKE EVACUATION)
1. Access door to the previous vestibule ventilated from the floor area must be fire resistant, at least ¾
of the resistance time of the enclosure and with automatic closing .
Door that connects the ventilated lobby with the staircase , must have a minimum fire resistance of
2. 20 minutes, and must have automatic closing.
Access will only be through a prior ventilated vestibule that separates the stairwell from the rest of
the building.
3.
If you choose to provide natural lighting to the stairwell (stand area), the following alternatives can be
used:
4.1 Distances less than or equal to 3 m : A closed opening with translucent material and a firebreak
on any of its faces is permitted, which will not exceed 1.50 m2 when the distance between the opening
and any point of an opening or other building is less than 3m. .
4.2 For distances greater than 3 m : there is no area limitation for the translucent material and no fire
protection requirement, only smoke protection.
5. The depth of the previously ventilated vestibule, measured between the central axes of the door
openings in the evacuation direction, must be at least 1.80 m . If there is a second entrance to the
previous ventilated vestibule, it is not necessary to increase the depth of the vestibule.
For residential buildings only, the equipment for air injection and extraction must be located on
6. each level of the staircase ; the installation of centralized equipment (a single fan or extractor for
the entire staircase) is not permitted.
STANDARD A.010
RNEVI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
CHAPTER
TYPES OF EVACUATION STAIRS
B 1 WITH PREVIOUS VENTILATED LOBBY (FOR SMOKE EVACUATION)
a) Evacuation stairs with a previous vestibule that ventilates directly to the outside.
The previous vestibule may vent towards the outside of the building (towards an open place) as long as there is no nearby
opening within a radius of 6 m measured from the ends of the opening through which it ventilates. Likewise, it must have an
opening open to the outside of a minimum of 1.50 m2.
STANDARD A.010
RNE
CHAPTERVI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
TYPES OF EVACUATION STAIRS
B 1 WITH PREVIOUS VENTILATED LOBBY (FOR SMOKE EVACUATION)
b) Evacuation stairs with a previous vestibule that ventilates through a mechanical extraction system
The previous vestibule may be ventilated by means of a mechanical extraction system, towards the outside of the building, as long as
a smoke enclosure is established in said vestibule. The mechanical extraction system must be installed in each previous vestibule of
STANDARD A.010
theRNE
level to which it delivers.
Likewise, the mechanical extraction system can ventilate outside the building through its own ventilation duct, that is, used
exclusively for said extractors. Solutions in which the duct has openings coming from other areas of the building will not be accepted.
STANDARD A.010
CHAPTER VI VERTICAL CIRCULATION OPENINGS TO THE EXTERIOR VANOS AND EVACUATION DOORS B 1
RNE
WITH PREVIOUS VENTILATED LOBBY (FOR SMOKE EVACUATION)
c) Evacuation stairs with a previous vestibule that ventilates through a mechanical extraction system
Solution D:
Solution to:
He
lobby
He
The previous
previous
vestibule ventilates
It ventilates through a
through a mechanical
J.00 mechanical extraction
extraction system to 3.00
system to a ventilation
Solution B: This enclosure may be made of glass towards the Solution C: The previous
outside of the building (towards an open place) as long as there is vestibule ventilates through a
no window or opening within 3.00 m . minimums measured from mechanical extraction system to a
the end of the glass horizontally and/or perpendicularly. ventilation duct located outside
the vestibule.
STANDARD A.010
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
RNE
B 1 WITH PREVIOUS VENTILATED LOBBY (FOR SMOKE EVACUATION)
b) Evacuation stairs with a previous vestibule that ventilates through a mechanical extraction system
The design must guarantee that the mechanical extraction system is activated automatically when a fire event occurs in the
building, so it must be interconnected with the building's fire detection and alarm system.
The power supply necessary for the operation of the mechanical extraction systems must be protected against fires with a
resistance of no less than 2 hours.
Mechanical extractors must be supplied by a secondary energy source. The automatic activation of the system must be carried out
by a smoke detector located within 3 m of the entrance door from the hall to the previous lobby .
The design, calculation and sizing of the mechanical extraction system and its components must be carried out in accordance with
the requirements established in the NFPA Code 101 Chapter 7, as well as in accordance with the following design criteria.
STANDARD A.010
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
RNE
B 1 WITH PREVIOUS VENTILATED LOBBY (FOR SMOKE EVACUATION)
b) Evacuation stairs with a previous vestibule that ventilates through a mechanical extraction system
a) The vestibule must have at least one air change per minute .
b) The air extraction in the vestibule should be 150% of the air injection.
air to the lobby.
c) The injection and extraction ducts must be independent of each other, and
only used for ventilation purposes; no other type of installation is allowed
inside these ducts.
d) The base of the air injection grille must be located no more than 0.15
m above floor level , inside the vestibule.
e) The top of the air extraction grille should be located no more than 0.15
cm below the ceiling level , inside the vestibule.
f) When the stair doors are open , they should not obstruct the injection
or extraction grilles .
g) Between the top of the door opening and the ceiling level, there must be a
distance of 50cm, so that the Lobby becomes a smoke trap. Shorter
distances are allowed when the engineering design of the Extraction
System, as well as field tests, support it.
h) The staircase (stairs area) must have a pressure relief damper at the
top, mechanically operated, with the capacity to discharge at least 70.8
m3/min and a positive pressure of no less than 0.00025 bar (0.10 inch of
water) with all doors to the lobby area closed.
STANDARD A.010
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
RNE
B 2 EVACUATION STAIRS WITH PREVIOUS NON-VENTILATED LOBBY
PRESSURIZATIO
N
FIRE WALL
STANDARD A.010
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS B 4
RNE
OPEN
1. They are open to the outside on at least one side with an area of at least 1m 2 on each floor.
2. The opening open to the outside will be at a distance of 6.00 m or more from an opening of the building it serves.
3. This separation must have a fire resistance of no less than 1 hour . The separation of 6.00 m . It must be measured
horizontally and perpendicular to the opening.
4. This staircase is only accepted for buildings no higher than 30 m in height measured above street level.
4.1 Exception 1 : In existing buildings, where the incorporation of an additional evacuation staircase is required, it may be
opened up to a maximum of 60 meters high.
4.2 Exception 2: For new buildings, the height of the open staircase may be unlimited as long as an architectural design is
offered that minimizes the perception of effects such as vertigo, referring to the visual impact of height on evacuators.
ABROAD
6.00m 6.00m
STAIRS OF
EVACUATION
LADDER
CLOSED
STANDARD A.010
VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR,
CHAPTER
RNEAND EVACUATION DOORS Art. 27
VANOS
The number and width of the stairs will be determined according to the travel distance of the
evacuator measured from the room furthest from the stairs and the floor with the greatest capacity .
The number of evacuation stairs is calculated based on compliance with the following criteria:
a) Regardless of the load capacity of the stairs and the relationship with the number of occupants, at
least two evacuation stairs are required in every building, with the exception of Art. 28 of
Standard A.010.
b) Useful width required to evacuate, measured based on the maximum occupant load per floor or
level, established Standard A.130 Art. 22 (Width of evacuation components).
c) Evacuator travel distance (Art. 25 paragraph C)
d) Alternative escape route concept
e) According to the specific requirement established by the RNE Standard A.130 , Article 22 (For
calculation results greater than 1.20 m in width, rounding in modules of 0.60 m is not applicable)
and Article 23.
f) When two or more stairs are required, and the building has a sprinkler system , these must
be located on opposite routes with a minimum distance between escape doors equivalent to
1/3 of the greater diagonal of the floor of the building they serve.
g) If the building does not have a sprinkler system , the stairs must be located on opposite routes
with a minimum distance between escape doors equivalent to ½ of the longest diagonal of
the floor of the building they serve.
STANDARD A.010
VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR,
CHAPTER
RNEAND EVACUATION
VANOS
DOORS
Art. 27
f) When two or more stairs are
required, and the building has a
sprinkler system , these must be
located on opposite routes with a
minimum distance between
escape doors equivalent to 1/3 of
the greatest diagonal of the floor
of the building to which they are
located. serving.
b) In office buildings , a minimum of two evacuation stairs are required, unless all of the following requirements are met so that there can be only one staircase :
1. No more than 30 meters in height measured from the lowest level of the fire truck access.
2. In the case of integrated stairs used as an evacuation route, the maximum travel distance from the furthest point of the building to the outside of the building is not
greater than 45 m if the building does not have sprinklers or 60 m if the building has sprinklers .
3. In the case of evacuation stairs, it complies with any of the alternatives proposed in this Standard and delivers directly to the outside of the building or to a hall on the first floor compartmentalized
firebreak and the travel distance from the door of the evacuation staircase to the door of the building does not exceed 10 m
4. The maximum travel distance, from the furthest point of the plant to the entrance door to the evacuation staircase, is not greater than 30 m .
5. The complete plant (flat) has a maximum area of 650 m2 .
6. The maximum load of evacuees per plant (floor) is less than 100 people .
7. The entire building has a centralized smoke detection and fire alarm system in accordance with Standard A.130 .
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
Art. 28 Regardless of its use, every building must have at least 2 evacuation stairs, except in the following cases:
c) In accommodation buildings , they require at least two evacuation stairs, unless they meet all the requirements so that they can have a single evacuation staircase :
1. No more than 12 meters in height measured from the lowest level of the fire truck access.
2. There are no more than 12 rooms per floor .
3. The building is protected with sprinklers.
4. The evacuation staircase does not serve more than half of the floor level below the discharge level .
5. The travel distance from the room door to the exit is less than 10.7m .
6. The staircase is compartmentalized or separated from the rest of the building with resistance walls. fire of minimum 1hr .
7. In every opening of the enclosure that separates the staircase from the building, doors with devices must be located. Automatic closing and fire resistance for 1hr walls .
8. All exit access corridors must have a fire resistance of at least 1 hour .
9. Both vertical and horizontal separation between rooms must have a minimum fire resistance of 30 minutes.
d) In commercial buildings , it requires at least two evacuation stairs, unless all the requirements are met so that it can have a single evacuation staircase :
1. No more than 9 meters in height measured from the lowest level of the fire truck access.
2. In the case of integrated stairs used as an evacuation route, the maximum travel distance, from the furthest point of the building to the outside of the building , is not greater than 45 m if the building does not have
sprinklers or 60 m if the building has sprinklers .
3. In the case of evacuation stairs, they comply with any of the alternatives proposed in this Standard and deliver directly to the outside of the building, with a maximum travel distance, from the furthest point.
distance from the plant to the entrance door to the evacuation staircase is no more than 30 m.
4. The complete plant has a maximum area of 300 m2.
5. The entire building has a centralized smoke detection and fire alarm system in accordance with Standard A.130 article 53.
6. The use of integrated stairs is permitted, complying with the evacuator travel distances described in point 2 , as long as the evacuation route passes more than 6 m from any fireplace, grill, chimney or any other
artifact that has an exposed live flame (fire) . Does not include ovens with door devices or locking mechanisms.
7. The use of a single evacuation staircase is not allowed in Shopping Malls, Shopping Complexes and Markets (wholesale and retail).
STANDARD I A.010 I RNE
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND EVACUATION DOORS
Article 28.- Regardless of its use, every building must have at least 2
evacuation stairs, except in the following cases:
f) In any use, for areas or rooms inside buildings , above or below floor
level, where engines such as generator sets and/or fire pumps
operate, with a total fuel (diesel) storage volume of no more than
3,785 liters (1,000 gallons), which is supplying the engine(s), the
national hydrocarbon legislation will not be applicable, a single
access staircase to the area is required, with a width of no less
than 0.90 m; when the capacity and travel distance of the evacuator
allow it.
STANDARD A.010
CHAPTER VI VERTICAL CIRCULATION, OPENINGS TO THE EXTERIOR, VANOS AND
RNE
EVACUATION DOORS
Article 29.- Stairs in general, integrated or evacuation, are made up of sections, landings and railings.
to Conditions that must be met are the following:
) The stairs will have a maximum of seventeen steps between landings.
b The dimension of landings must be a minimum of 0.90 m in length for linear stairs; Another type,
the width of the landing will not be less than that of the flight of the stairs.
c) In each flight of stairs, the steps and counter steps are uniform, the rule must be met: 2
counter steps + 1 step , they must be between 0.60 m and 0.64 m, with a minimum of 0.25 m for
steps in housing, 0. 28 m in commerce and 0.30 m in places with a mass flow of public, health
and education and a maximum of 0.18 m for counterpasses, measured between the vertical
projections of two adjacent edges.
The width for stairs is considered between the enclosing walls that make it up, or their
d) limits if one or both sides are open. The presence of handrails does not constitute
a reduction in the width of the staircase . The stairs will have a minimum width of
1.20 m
e) Stairs over 1.20 m up to 2.40 m will have handrails on both sides. If they are more than
f) 2.40 m, they must also have a central handrail. Only in integrated stairs may there be
diagonal steps as long as 0.30 m from the beginning of the step, it is at least 0.28 m.
g)
STANDARD A.010
CHAPTER VII HEALTH SERVICES
RNE
Art. 36
Buildings that contain several independent real estate units must have water meters for each unit.
The meters must be located in places where it is possible to read them without having to enter the interior of the unit being
measured.
Sink
LIGHTNING Environment Lighting Have sufficient lighting RNE A010Art 21447-50 storages They can be illuminated through other environments
Art. 47 The environments of the buildings will have components that ensure the natural and artificial lighting necessary for use by its occupants.
Art. 48 The rooms will have direct natural lighting from the outside and their openings will have a sufficient
area to guarantee a level of lighting in accordance with the use for which it is intended.
The environments intended for kitchens, sanitary services, circulation passages, warehouses and
storage may illuminate through other environments.
The circulation passages that serve for evacuation, and in general the evacuation routes, can have natural or
artificial lighting or a combination of both.
Art. 49 The light transmission coefficient of the transparent or translucent material , which serves to
close the openings, will not be less than 0.90 m . If it is lower, increase the dimensions of the opening.
Art. 50 All environments will also have artificial lighting means in which the luminaires that can be installed
must provide the lighting levels for the function that takes place in them, as established by Standard EM.010.
STANDARD A.010
RNE X VENTILATION AND ENVIRONMENTAL CONDITIONING REQUIREMENTS
CHAPTER
Art. 51
All rooms must have at least one opening that allows air to enter
from the outside. The environments intended for sanitary services,
circulation passages, warehouses, control rooms, environments
that for safety reasons cannot have access to exterior openings,
halls, basement and storage environments or where activities are
carried out in which people enter Eventually, they may have a
solution for artificial lighting, mechanical ventilation through
exclusive ducts or other environments.
Kitchens, SH, circulation passage, warehouse and Final or art air renewal must be guaranteed.
storage can illuminate through other environments
VENTILATION Room Ventilation RNEA010Art. 21.c,51Y52 The warehouses and warehouses can be ventilated by mechanical
means or ventilation ducts.
STANDARD A.010
RNE X VENTILATION AND ENVIRONMENTAL CONDITIONING REQUIREMENTS Art. 52
CHAPTER
The ventilation elements of the environments must have the following requirements:
a) The opening area of the opening to the outside will not be less than 5% of the surface of the room that is ventilated.
b) Sanitary services, warehouses and warehouses can be ventilated by mechanical means or through ventilation ducts.
WINDOW
Kitchens, SH, circulation passage, warehouse and Final or art air renewal must be guaranteed.
storage can illuminate through other environments
VENTILATION Room Ventilation RNEA010Art. 21.c,51Y52 The warehouses and warehouses can be ventilated by mechanical
means or ventilation ducts.
STANDARD A.010
RNE X VENTILATION AND ENVIRONMENTAL CONDITIONING REQUIREMENTS
CHAPTER
Art. 54 Air conditioning systems will provide air at a temperature of 24 ° C to 2 ° C , measured in dry bulb and a relative
humidity of 50% to 5%. The systems will have mechanical filters to have adequate air cleaning.
Art. 58 All mechanical installations, whose operation may produce annoying noises or vibrations to the occupants of a
building, must be equipped with devices that isolate the vibrations of the structure, and have acoustic insulation that prevents
the transmission of annoying noises to the environment. abroad.
structure vibrations
STANDARD A.010
RNE XII
CHAPTER
CHAPTER XI CALCULATION
PARKING LOTSOF OCCUPANTS OF A BUILDING
Art. 61,
Art. 64, 65,calculation
59 The 66, 67, 68,of 69
occupants of a building (Capacity) will be made according to what is established in Standard
A.130 and according to the occupancy rates for each type according to Standards A.020, A.030, A.040, A.050 , A.060,
A.070, A.080, A.090, A.100 and A.110 of the RNE.
Individual Dimensions 2.70m
According to Municipality for necessary
De Lae Housing RNEAOlOArt 65 a,b 2 continuous 2 50m
quantities / Minimum dimensions 3a* 2 40m)
The number of occupants is exclusively applicable to the calculation of and
Tolerance 5% structure emergency
always 5m exits, passageways for people to
Visiting Visit Minimum According to Municipality Ordinance
circulate, elevators, provision of sanitary services, width and number of stairs. Dimensions Individual 3 80 x 5m
Disabled At least 1 RNEA120.Art16.C 6 to 20 stac 1 disabled
Law 29783-2012 21 to 50 2 units 1 51 to 400 2 c /50 stac
Art 11,16,19 ♦ of 400 vehicles 16 eslc *1 w /100 additional
be
PARKING calculated
LOTS according Basement
Access and Ramps to its use. When different uses are contemplated in the same area, the most demanding number
3m Flat Removal
Semi basement no > a N *150m from the floor measured
from the sidewalk level
% 15% maximum
of occupants must be considered.
sidewalk cut + than 150 vehicles RNE A 010 Art 68
Turning radius 5mt. Measurements to Caml road axis RNE A 010 Art. 67g
Up to 40 vehicles 3mt
6mt or separated
41 to 300 vehicles If they consider separate entrance and exits, they must
Income (entrance and exit) RNEAOlOArt. 67b.4,5y6 comply with the required half width.
12m (double entry and
301 a+ vehicles
exit)
Ride Cars In buildings < 500m2 RNEAOlOArt. 61 Be careful, it is not a land area
Natural + 20 vehicles on 1 floor The monoxide extraction inlets must be located at the
top and not affect adjacent buildings Art 9
Ventilation Artificial + 20 vehicles in 2 or + basements
RNE A 010 Art. 69,Art 9
STANDARD A.010
RNE
STANDARD A.010
RNE XII PARKING LOTS
CHAPTER
RIDE CARS
Art. 61 The parking lots will be located within the same building they serve, and only in exceptional cases due to a parking deficit,
will they be located on different properties. These spaces may be located in the basement, semi-basement, at ground level or on
the upper floor and constitute a complementary use to the main use of the building.
In buildings with an area of less than 500 m2 , where access to parking spaces located in basements may be done using forklifts
(car lifts).
The use of mechanical or robotic assistance systems (elevators) is also permitted to allow two or three level parking (one vehicle
on top of the other) on a single floor, for semi-basements, basements, at ground level, and on high floors.
STANDARD A.010
CHAPTER XII PARKING LOTS
RNE
Art. 64 The parking spaces to be considered are for cars and vans to transport people with up to 7 seats .
For the parking of other types of vehicles, it is necessary to carry out calculations of parking spaces and
maneuvers according to their characteristics.
Art. 65 Private use is considered to be any parking that is part of a housing project, services, offices and/or any
other use that requires low turnover. The characteristics to be considered in the provision of spaces for private
use will be the following
a) The minimum clear dimensions of a parking space shall be: (When placed):
i) Three or more continuous parking spaces: Width: 2.40 m each structural element _ occupy S 5% of the
minimum width
ii) Two continuous parking lots:
iii) Individual parking spaces: iv) In all Width: 2.50 m each
cases: Length: Width: 2.70 m each
b) The structural elements may occupy up 5.00 m / Height 2.10 Minimum width Minimum width
to 5% of the width of the parking lot , when it has the minimum dimensions.
c) The minimum distance between opposing parking spaces or between the back of a parking space and the
opposite closing wall will be 6 m.
d) If the parking spaces are located in front of routes of entry or evacuation of people, this area must be
declared as a Rigid Zone , its use as parking is not permitted and the separation space of the rigid zone
must be the same as the width. useful calculated for the evacuation route . As long as the evacuation route
design requires the use of this rigid zone between vehicles. The sidewalks, depending on their width, can be used
to channel evacuation flows.
e) Double parking spaces , that is, one after the other, are counted to reach the number of parking spaces
required in the urban plan , but they constitute a single real estate unit . In this case, its length can be 9.50 m
f) Do not locate parking spaces within a 10 m radius of a hydrant or 3 m from a firefighter connection
(injection siamese).
STANDARD A.010
CHAPTER XII PARKING LOTS
RNE
Article 66.-Public use is considered to be all parking that is used for Commerce (shopping center, supermarket, department store, group of stores,
home improvement store) or any other commercial category that requires high turnover. The characteristics to be considered in the provision of parking
spaces for private use will be the following:
a) Minimum clear dimensions of a parking space will be:
1) Three or more continuous parking spaces: Width: 2.50 m each
2) Two continuous parking lots: Width: 2.60 m each
3) Individual parking spaces: Width: 3.00 m each D private use: 6.00 m
D public use: 6.50 m
4) In all cases : Length: 5.00 m / Height: 2.10
injection siamese
b) The structural elements may occupy up to 5% of the width of the parking lot , when it has the minimum dimensions.
c) The minimum distance between opposite parking spaces or between the back of a parking space and the opposite closing wall will be 6.50 m.
d) Parking spaces must not invade or be located in front of people's entry or evacuation routes.
e) No parking spaces should be located within 10 m of a fire service connection (siamese injection) or within 3 m of a fire connection.
3m
f) The width, height and turning radius of the Fire Department units must be considered in access and circulation.
hurtful ________
STANDARD A.010
CHAPTER XII PARKING LOTS
Arti.RNE
67 The areas intended for vehicle parking must meet the following requirements: a) Access and exit to
a parking area may be proposed jointly or separately.
b) Vehicle entry must respect the following dimensions between walls:
1) For 1 vehicle: 2.70 m.
2) For 2 vehicles in parallel: 4.80 m.
3) For 3 vehicles in parallel: 7.00 m.
4) To enter a parking area for less than 40 vehicles: 3.00 m.
5) To enter a parking area with more than 40 vehicles. up to 300vehicle:6.00 m or an entry and exit
independent 3.00 m. DC..
6) To enter a parking area of 300 vehicles, to further: 12.00m. either a income double 6.00 m.and exit double
of 6.00 m
c) The entrance doors to parking lots may be located at the property line as long as the opening of the door does not invade the sidewalk,
d)
otherwise they must be located at a sufficient distance to allow the opening of the door without interfering with the movement of people
through it. the sidewalk.
a
n The access ramp to the basement, semi-basement or upper floors must have a slope of no more than 15% . Changes between planes of different
d) slopes must be resolved using transition curves.
Ramps must start at a minimum distance of 3 m from the property line . At this distance the floor must be horizontal at the level of the
sidewalk. In the case of semi-basement parking lots, whose upper roof level does not exceed 1.50 m above the level of the sidewalk in front
F) of the lot, the access ramp to the parking lot may begin at the property line .
STANDARD A.010
Vehicle access to parking lots may be located in setbacks, as long as it does not affect vehicle traffic on the road where it is accessed.
RNE
The turning radius of the ramps will be 5 m measured to the axis of the vehicular
circulation lane.
Art. 69 Ventilation of vehicle parking areas, regardless of their size, must be guaranteed, naturally or mechanically.
Parking areas with more than 20 vehicles in single-level basements, at ground level or on upper floors, whether or not they have a building for commercial
or residential use above them, will require sufficient natural ventilation to allow the elimination of the carbon monoxide emitted. by vehicles.
Parking areas with more than 20 vehicles in basements above the second basement require a mechanical carbon monoxide extraction system, unless
efficient natural ventilation can be demonstrated. Monoxide extraction systems may also be used for the extraction of smoke from fires (smoke
management system) and in this case the solution that predominates in the design is smoke management, and the height of the intakes. Monoxide
extraction must be located at the top. The provisions of Standard EM 030, article 5, paragraph 2, do not apply.
The extraction system must have gas outlet ducts that do not affect adjacent buildings.
Andres.cerron@urp.edu.pe