GENERAL NOTES AND SPECIFICATIONS

1. ALL ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST


EDITION OF THE PHILIPPINE ELECTRICAL CODE AND IN COMPLIANCE WITH THE
AUTHORITY HAVING JURISDICTION (AHJ).

2. THE ELECTRICAL SERVICE POWER IS A SINGLE PHASE (1Ø), TWO WIRE (2W), 230
VOLTS AC, 60 HERTZ.

3. WIRING METHOD SHALL BE AS FOLLOWS (MINIMUM REQUIREMENT):


A. MAIN SERVICE ENTRANCE-THW THRU OPEN OVERHEAD AND/OR WIRE TRAY.
B. SUB-FEEDERS, BRANCH CIRCUITS AND AUXILIARY- THHN THRU EXPOSED RIGID
STEEL CONDUIT (RSC) AND/OR METALLIC LIQUID TIGHT HOSE.

4. ALL WIRES SHALL BE OF COPPER UNLESS OTHERWISE INDICATED IN THE PLAN AND
INSULATED FOR 600 VOLTS.
5. ALL ELECTRICAL MATERIALS TO BE USED SHALL BE BRAN NEW, "LISTED" AND/OR
"LABELED" AND OF APPROVED TYPE FOR THE PARTICULAR LOCATION AND
PURPOSE OF USAGE.
6. ALL METAL FRAMES AND CONDUITS SHALL BE PROPERLY AND ADEQUATELY
GROUNDED AND BONDED. GROUND WIRE SHALL BE PROVIDED ON ALL EQUIPMENT
FEEDERS.
7. ALL CIRCUIT BREAKER AND PANELBOARDS SHALL BE OF "BOLT ON" TYPE AND FOR
INDUSTRIAL APPLICATION. MOTOR CIRCUIT PROTECTION IS DESIGNED FOR
THERMAL-MAGNETIC TRIP CIRCUIT BREAKERS.
8. NO REVISION IN THE DESIGN SHALL BE DONE WITHOUT THE PRIOR KNOWLEDGE AND
APPROVAL OF THE DESIGNER AND OF THE OWNER. ANY SUCH REVISION DONE
WITHOUT THE APPROVAL SHALL CAUSE RESPONSIBILITY OF THE DESIGNER TO
CEASE AS A WHOLE.
9. ELECTRICAL DRAWINGS ARE FOR REFERENCE ONLY. THE EXACT LOCATIONS AND
DIMENSION MAY VARY DUE TO STRUCTURAL CONDITIONS AND INDUSTRIAL DESIGNS.
THE CONTRACTOR IS HEREBY REQUIRED TO MAKE ADJUSTMENT AT THE JOBSITE
LOCATION WHEREVER NECESSARY AND GOVERNED BY ACTUAL FIELD CONDITIONS.
10. ALL WORKS SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER.

10. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE SUPERVISION OF A LICENSED
ELECTRICAL PRACTITIONER.

CKT. NO. OF AMPERES CB WIRE PIPE


LOAD DESCRIPTION V.A. VOLTS
NO. OUTLETS RATING
A B C SIZE TYPE SIZE TYPE

1 LIGHTING OUTLET 12 480 230 2.90 15AT,2P 2-2.0mm² THHN 20mm Ø PVC
SERVICE POINT
DISTRIBUTION UTILITY SUPPLY
2 LIGHTING OUTLET 10 400 230 1.74 15AT,2P 2-2.0mm² THHN 20mm Ø PVC
THREE-PHASE 3 WIRE
15AT,2P 240 VOLTS
3 LIGHTING OUTLET 5 200 230 0.87 2-2.0mm² THHN 20mm Ø PVC CL200, SP 2W
M KLWH METER
MDP
4 LIGHTING OUTLET 10 400 230 1.74 15AT,2P 2-2.0mm² THHN 20mm Ø PVC
MDP
5 CONVENIENCE OUTLET 2 1080 230 4.70 20AT,2P 2-2.0mm² THHN 20mm Ø PVC
100AT
6 CONVENIENCE OUTLET 2 1080 230 4.70 20AT,2P 2-2.0mm² THHN 20mm Ø PVC MAIN DISCONNECT
SWITCH

7 CONVENIENCE OUTLET 2 1080 230 4.70 20AT,2P 2-2.0mm² THHN 20mm Ø PVC 15AT 15AT
C1 C2
8 CONVENIENCE OUTLET 2 1080 230 4.70 20AT,2P 2-2.0mm² THHN 20mm Ø PVC 15AT 15AT
C3 C4
9 CONVENIENCE OUTLET 2 1080 230 4.70 20AT,2P 2-2.0mm² THHN 20mm Ø PVC
15AT 20AT
10 CONVENIENCE OUTLET 2 1080 230 4.70 20AT,2P 2-2.0mm² THHN 20mm Ø PVC C5 C6
20AT 20AT
11 CONVENIENCE OUTLET 2 1080 230 4.70 20AT,2P 2-2.0mm² THHN 20mm Ø PVC C7 C8
20AT 20AT
12 SPARE C9 C10
20AT SPARE
13 SPARE C11 C12
SPARE SPARE
14 SPARE C13 C14

TOTAL 9040 230 11.49 15.84 12.01 30AT,2P 2-8.0mm² THHN 20mm Ø PVC

GROUND

FEEDER TOTAL COMPUTED LOAD: COMPUTED VA=15.84x1.25


COMPUTED VA=19.8 A
FEEDER TOTAL COMPUTED LOAD: NET MAX. COMPUTED CURRENT=19.8A
USE 8.0mm² THHN COPPER CONDUCTOR
ON 20MM Ø RSC CONDUIT
FEEDER TOTAL COMPUTED LOAD: USE 2P, 30 AT BOLT-ON CIRCUIT
BREAKER

ENGINEER PROJECT TITLE SHEET CONTENT REVISION/REFERENCE OWNER SHEET NO.

APOLINARIO Jay, REBALDE Edrey Rose,


REDERA Maricar, DUHAYLUNGSOD Cleofe, ELECTRICAL PLAN 2 A4
CODENIERA Juliafe EGG ROOM PLAN -

TIN: REG NO. DRAWN BY: BLACK STUDIO DATE: 6/7/2024 RES NO. DATE: 6/7/2024
5
PRT NO. DATE: 6/7/2024 LOCATION CHECKED BY: JOGIEMAR RECOSOSA DATE: 6/7/2024 PROJECT NO. TIN: ADDRESS: