UG-TIL-02-M044-101375 - 02-82-NA-0003: CENTRAL CONTROL BUILDING - PLUMBING AND Click here to view review comments in New Prodom (login

in New Prodom (login required)


Revision: 00 (IFR)
Approver: Daher, Nicolas
Finalized: 18-Apr-2024 (UTC +3)
Review Status: 2 - Accepted with comments

Comment ID Comment Response Status File Name Page Number


1941703 Not legible. Please adjust. Adjusted Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941705 Not legible. Proper detail provided Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941714 Please be consistent with the title description. Rectified and changed Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941715 Please add demarcation and reference drawing. Provided with reference Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941716 Please use the line type as per EIT south, north and west. Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941717 Please fix. Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941718 square Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941719 square Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941720 square Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941722 Please be consistent and use the line type as per EIT south, north and west. Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941724 line Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941725 Please indicate what this mean and where this will be dischaged to. From shelter roof to Building roof Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941728 Typical comment. Please indicate the items symbol indicated in drawing number UG-TIL-00-M044-100395 Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941730 line symbol indicated in drawing number UG-TIL-00-M044-100396 Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941731 line symbol indicated in drawing number UG-TIL-00-M044-100397 Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941733 Please indicate double skin drain pipe as discussed. Typical comment. Add in note number 15. to avoid any confusion in drawing. Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941736 Floor drain and eye wash are required, a floor drain to collect the water from the Keeping as it is. Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
eye wash. CTR shall keep it
1941737 Is this connected to the vertical RWP?€Please confirm whether eyewash liquid It is not connected to verticle rain water pipe. It will connect with Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
will compromise the drain discharge quality and contaminate any OD drain external OD3 Network. Portable eye wash trolly will have have its own
system? arrangments. Any drain discharge will be in very limited quantity and
only occur in the situation of any incident.
1941740 square Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941741 line Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1941742 Please be consistent with the title description. Rectified and changed Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955616 Please fix. Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955618 This is detail engineering. Please check with MDT regarding the system As Minimum pressure to be mainatained around 4 bar from water Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
pressure and confirm whether pressure reducer shall be required or not. main. Pressure reducer provided.
1955619 Please clarify what type of valves. Only stop valves are shown for the washbasin it is angle stop valve ( Shut-off valve) for washbasin, sinks and Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
in the typical details. For any other fixtures, angle valves were not shown. dishwasher.

1955620 please add normally open Referenc document mentioned Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955621 Please add tag number Tag number Added Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955622 shall be sentenced removed Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955623 Refer to this document for what information. Please indicate in the note. Removed Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955624 Please check against Uganda national building code whether the materials are There is no specific material description for condensate drain pipes in Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
acceptable. Uganda National standard.. Galvanized steel pipe is recommended by
AHIC.
1955625 Please remove Removed Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955626 line Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955627 line Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955628 line Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955630 Please add demarcation between different entity scopes. Typical comment. Added Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955631 Please add continuous drawing reference. Added Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955633 Wehere is the water meter? Added Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955634 Duty and standby pumps as per calculation note to be specified. There will be one pumps as duty, as specified in plumbing BOD. Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955636 Why two levels are shown? It’s a water tank indication for high and low level in tank. Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955637 line Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955639 Please use a proper ball valve legend. The ball shall be on water surface level. Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1

1955650 PIpe size Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1


1955654 Engineer to investigate if it's better to run the water main to roof level water tank Not feasible Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
room from where the pipework distributes.
1955657 The water distribution system shall be protected from backflow and every water Required minimum air gaps for plumbing fixtures and water tank will be Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
outlet protected from backflow. indicated in plumbing typical details to prevent backflow in accordance
1955663 please indicate overflow and drain from the tank. with Ugandan National standard.
indicated Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955665 The water tank area from waste water riser diagram is different from domestic Area is same, only projection is different in drawing for better Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
water riser diagram. visualisation.
1955725 Stopcocks or shut-off valves shall be installed at each sanitary appliance. Added in general note Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
Typical comment.
1955741 Pressure gauges on the inlet and outlet of the pump to be added. Added Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955743 Pipe to this connection missing. Rectified Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1955745 isolation valves on both sides of the motorized valve are required to replace the Provided Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
valve for maintenance/replacement.
1955756 Please ensure the length of pipe measured from the tap to the water heater shall Confirmed. It is less than 12 M. Unchanged UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
not exceed 12m as per Uganda code 2019.
1955763 Please check uganda codes/regulations if a check valve shall be installed in the Note 22 Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
cold water supply line to each heater.
1955999 This should be full way gate valve as per uganda code. Provided Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1956006 please indicate room areas for all the equipment presented on ground floor, Mentioned Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
similar to that in the waste water riser diagram above.
1956012 Please indicate vent pipe slope. Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1956021 Please amend as agreed and discussed in plumbing meeting held with Changed Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
TKN/MDT/CPY. AHU condensate drain should not be open drain within the
HVAC plant room.
1956027 Please draw the hopper properly. Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
1956032 Please change the title to 'domestic water system, rainwater system, sanitary Changed Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1
system and condensate drain riser block diagram'
1956037 Please ensure the title description for each drawing to fit in one cell. Changed Implemented UG-TIL-02-M044-101375_00_IFR_20240313.PDF 1