Test type: EICR - EICR+Remedials - EIC DB Replacement + Remedials Main Switch (Bs) 60947-3

Address: 69 FISH STREET, E175EE 240 Volts 100 Amp


Location of DB/CONSUMER UNIT HALLWAY IP RATED LIGHT IN BATHROOM: YES/NO
Overall assessment: Satisfactory / Unsatisfactory SHAVER SOCKET: YES/NO Spot Lights: YES/NO
Earthing Type: TN-S TN-C-S TT Plastic DB / METAL DB / METAL WITH PLASTIC COVER DB
Age of Installation: 25+ Supply Conductor CSA - LINE 25 mm
Main fuse (size/ Bs number) LIM - EARTH 16 mm
Bonding Conductor (mm: Water: 10 Gas: 10 other: OLD GAS PIPES
DB Type and Make: 10 WAYS MAKE: Wylex/BG/MK/Crabtree/Haeger/ other:

Reference Method

AFDD Test Button


Overcurrent Device RCD Circuit Resistances Ω

Number of Points
Conductor CSA

Polarity
Type of Wiring

LIVE CPC Radial Insulation RCD/RCBO

Capacity (kA)
(R1) (R2) Circuit

Curve Type
Ring Final Continuity Resistance Trip times
Circuit No

Rating (A)

Rating (A)
EARTH times X1

I (mA)
Type
Circuit designation mm mm BS (EN) BS (EN) L =r1 N = rn CPC= r2 R1 +R2 √ LN/CPC L/N Zs mS

Main switch N/A N/A N/A N/A N/A 60947-3 N/A 100 N/AN/A N/AN/A N/AN/A N/A N/A N/A N/A N/A N/A N/A N/A

SOCKETS RING ON AFDD A C 3 2.5 1.5 62606 B 32 6 61009 A 32 30 0.3 0.3 0.5 0.2 999 999 0.55 28.1

SOCKET RING ON RCBO A C 3 2.5 1.5 61009 B 32 6 61009 A 32 30 0.3 0.3 0.5 0.2 999 999 0.55 23.2 N/A

SPARE N/A N/A N/A N/A N/A N/A N/A N/A N/AN/A N/AN/A N/AN/A N/A N/A N/A N/AN/A N/A N/A N/A N/A

RCD N/A N/A N/A N/A N/A N/A N/A N/A N/A 61008 A 63 30 N/A N/A N/A N/A N/A N/A N/A 29.3 N/A

radial circuit A C 2 2.5 1.5 60898 B 16 6 N/A N/AN/A N/AN/A N/A N/A 0.22 999 999 0.35 N/A N/A

Smoke Alarm/ I= R= 1 E= Heat alarm/ I= 1 R= E= CO alarm/ I= R= E= 1 Engineer Name:

Ze: 0.12 Ω PFC (L-PE) 1.89 kA SPD Details: T1 / T2 / T3 / N/A Tester Serial No: Page of